Ascon Tecnologic - KM series - ENGINEERING MANUAL -Vr.0.0 PAG. 14
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Absolute band alarm with alarm indication
out of the band
LHAi = Absolute band alarm with alarm indication
inside the band
SE.br = Sensor break
Note: The relative alarm are “relative” to the current set point
(this may be different to the Target set point if you are
using the ramp to set point function).
[42] Ab3 – Alarm 3 function
Available: When [40] AL3t is different from “nonE”
Range: 0... 15 with the following rule:
+1 = Not active at power up.
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
+8 =
Relative alarm not active at set point change
Example: Setting Ad3 equal to 5 (1+4) the alarm 3 will be
“not active at power up” and “Acknowledgeable”.
Note: For other details see [26] Ab1 parameter.
[43] AL3L - For High and low alarms, it is the low limit
of the AL3 threshold
- For band alarm, it is low alarm threshold
Available: When [41] AL3t is different from “nonE” or [41]
AL3t is different from “SE.br”.
Range: -1999 to [44] AL3H engineering units.
[44] AL3H - For High and low alarms, it is the high limit
of the AL3 threshold
- For band alarm, it is high alarm threshold
Available: When [41] AL3t is different from “nonE” or [41]
AL3t is different from “SE.br”.
Range: From [43] AL3L to 9999 engineering units.
[45] AL3 - Alarm 3 threshold
Available: When:
• [41]AL3t=LoAbAbsolutelowalarm;
• [41]AL3t=HiAbAbsolutehighalarm;
• [41]AL3t=LodEDeviationlowalarm(relative);
• [41]AL3t=LidEDeviationhighalarm(relative).
Range: from [43] AL3L to [44] AL3H engineering units.
[46] HAL3 - Alarm 3 hysteresis
Available: when [41] AL3t is different to “nonE” or [41] AL3t
is different from “SE.br”.
Range: 1... 9999 engineering units.
Note: For other details see [30] HAL1 parameter.
[47] AL3d – Alarm 3 delay
Available: When [41] AL3t different form “nonE”.
Range: From oFF (0) to 9999 seconds.
Note: The alarm goes ON only when the alarm condition
persist for a time longer than [47] AL3d time but the
reset is immediate.
[48] AL3o - Alarm 3 enabling during Stand-by mode
and out of range indications
Available: When [41] AL3t is different from “nonE” or [41]
AL3t is different from “SE.br”.
Range: 0 = Never;
1 = During stand by;
2 = During overrang and underrange;
3 = During overrange, underrange and stand-by.
)LbA group - Loop break alarm
General note about LBA alarm.
The LBA operate as follows:
When you apply 100% of the power output to a process,
the process variable, after a time due to the process inertia,
begins to change in a known direction (increases for an
heating action or decreases for a cooling action).
Example: if I apply 100% of the power output to a furnace,
the temperature must go up unless one of the component in
the loop is faulty (heater, sensor, power supply, fuse, etc...)
The same philosophy can be applied to the minimum power.
In our example, when I turn OFF the power to a furnaces,
the temperature must go down, if not the SSR is in short
circuit, the valve is jammed, etc..
LBA function is automatically enabled when the PID requires
the maximum or the minimum power.
When the process response is slower than the programmed
limit the instrument generates an alarm.
Notes: 1. When the instrument is in manual mode, the
LBA function is disabled.
2. When LBA alarm is ON the instrument continue
to perform the standard control. If the process
response come back into the programmed limit,
the instrument reset automatically the LBA
alarm.
3. This function is available only when the
programmed control algorithm is equal to PID
(Cont = PID).
[49] LbAt –LBA time
Available: When [53] Cont = PID
Range: • oFF = LBA not used;
• 1...9999seconds.
[50] LbSt – Delta measure used by LBA during
Soft start
Available: When [49] LbAt is different from oFF
Range: • oFF = loop break alarm is inhibit during soft start
• 1...9999engineeringunits.
[51] LbAS – Delta measure used by loop break alarm
(loop break alarm step)
Available: when [49] LbAt is different from oFF
Range: from 1 to 9999 engineering units.
[52] LbcA - Condition for LBA enabling
Available: when [49] LbAt is different from oFF
Range: uP = Enabled when the PID requires the maxi-
mum power only.
dn = Enabled when the PID requires the mini-
mum power only
both =
Enabled in both condition (when the PID re-
quires the maximum or the minimum power).
LBA application example:
LbAt (LBA time) = 120 seconds (2 minutes)
LbAS (delta LBA) = 5°C
The machine has been designed in order to reach 200°C in
20 minutes (20°C/min).
When the PID demand 100 % power, the instrument starts
the time count.
During time count if the measured value increases more
than 5°C, the instrument restarts the time count. Otherwise