AutomationDirect ProSense DPM3-E Series User manual

ProSenSe DPM3-e SerieS
Digital Panel Meter for
true rMS ac or Dc voltage
anD aMPerage electrical
inPut SignalS
Models:
uSer Manual
DPM3-E-H DPM3-E-L
DPM3-E-A2R-H DPM3-E-A2R-L
TRMS
TRMS

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
2
UL
CUS
R
In this Chapter...
General Information......................................................................................................4
Package Contents.........................................................................................................4
Recycling Instructions...................................................................................................4
General Safety Considerations ......................................................................................4
Symbols Identification ..................................................................................................4
Maintenance ................................................................................................................5
Technical Support ........................................................................................................5
Agency Approvals.........................................................................................................5
Device Description.........................................................................................................6
Dimensions and Mounting............................................................................................7
Installation....................................................................................................................7
Wiring Terminals............................................................................................................8
Wiring Examples ..........................................................................................................10
DC/AC Voltage Input Wiring (Ranges: 2, 20, 200, 600 V) ..........................................10
DC/AC Current Input Wiring (Ranges: 1A, 5A)...........................................................10
DC/AC Current Input Wiring (Range: 200mA)............................................................10
DC/AC Current Input Wiring (Ranges: 50/60/100mV shunt)......................................11
Display and Key Pad ....................................................................................................11
Configuration:..............................................................................................................12
Programming numerical values ..................................................................................12
Input Configuration.....................................................................................................13
Display Configuration..................................................................................................14
Scaling .......................................................................................................................14
Programming of the scale ..........................................................................................15
SCAL method .............................................................................................................15
tEACH method ...........................................................................................................15
Weighted Average Filter P ..........................................................................................15
Round ........................................................................................................................16
Brightness ..................................................................................................................16
Eco.............................................................................................................................16
Additional Functions....................................................................................................16
MAX/MIN function.....................................................................................................16

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
3
Configuration Lockout................................................................................................17
Programming Mode...................................................................................................17
Return to Factory Configuration .................................................................................17
Direct Access to Relay Setpoints .................................................................................17
Logic functions...........................................................................................................17
Logic functions menu.................................................................................................18
Table of programmable functions...............................................................................19
Configuration Lock Out...............................................................................................20
Lock-out menu diagram .............................................................................................21
Lock-out menu diagram continued ............................................................................22
Output Options............................................................................................................23
Relay Configuration....................................................................................................23
Description of Operation............................................................................................23
Relay Configuration menu diagram............................................................................24
Direct access to the relay setpoints value programming.............................................24
Analog output............................................................................................................25
Analog output menu diagram ....................................................................................25
Technical Specifications...............................................................................................26

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
4
General Information
Package Contents
• DPM3-E Series True RMS Electrical Parameter digital panel meter
• Quick start guide
• Mounting panel accessories (a sealing gasket and 2 fixing clips)
• Wiring accessories (plug-in terminal block connectors and 2 key tools for wire insertion)
• 4 adhesive engineering unit label sheets
Recycling Instructions
This electronic instrument is covered by the 2002/96/CE European Directive so, it is properly
marked with the cros]sed-out wheeled bin symbol that makes reference to the selective collection
for electrical and electronic equipment which indicates that at the end of its lifetime, the final
user cannot dispose of it as unsorted municipal waste.
In order to protect the environment and in agreement with the European legislation regarding
waste of electrical and electronic equipment from products put on the market after August 13,
2005, the user can give it back, without any cost, to the place where it was acquired to proceed
to its controlled treatment and recycling.
General Safety Considerations
All instructions and guidelines for the installation and manipulation that are present in this
manual must be considered to ensure personal safety and to prevent damage to either the
instrument or any equipment connected to it.
Safety of any equipment incorporated to this instrument is the responsibility of the system
installer.
If this electronic indicator is used in a manner not specified by the manufacturer in this manual,
the protection provided by the instrument may be impaired.
Symbols Identification
Warning: Potential risk of danger.
Read complete instructions when this symbol appears in order to know the potential risk and
know how to avoid it.
Warning: Risk of electric shock.
Instrument protected by double isolation or reinforced isolation.

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
5
Maintenance
To ensure instrument accuracy, it is recommended to check its performance according to the
technical specifications listed in this manual.
For front cover cleaning, just wipe with a damp cloth and neutral soap product. DO NOT USE
SOLVENTS!
Technical Support
We strive to make our manuals the best in the industry. We rely on your feedback to let us
know if we are reaching our goal. If you cannot find the solution to your particular application,
or, if for any reason you need technical assistance, please call us at:
1-800-633-0405
Our technical support group will work with you to answer your questions. They are available
Monday through Friday from 9:00 A.M. to 6:00 P.M. Eastern Time. We also encourage you
to visit our web site where you can find technical and non-technical information about our
products and our company.
www.AutomationDirect.com
Agency Approvals

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
6
Device Description
The ProSense DPM3-E series offers a simple, feature packed digital display of True RMS AC
or DC voltage or amperage electrical parameters. The 5-digit tri-color red, green or amber
LED display is easily scaled into any engineering units from -19999 to 19999 with a selectable
decimal point location. Two point direct or reverse acting linear scaling values can be entered
manually or by introducing actual sensed values in Teach mode. Models are available with
two SPDT relay outputs that can be set to activate on an increasing or decreasing input signal
with hysteresis or time delay operation. Additionally the display color can be set to change
on relay operation. Models are also available with a 4-20mA analog output. The meter is
powered from an external AC or DC power supply. The 1/8 DIN housing is easy to install
in a panel and the meter face has an IP65 rating. Configuration parameters can be totally or
selectively locked out to prevent unauthorized or accidental changes to the meter’s operation.
Other features include memory and reset of minimum (valley) and maximum (peak) display
values, display hold function, filtering to minimize display bounce, and display brightness
adjustment. ProSense digital panel meters are backed by a 3 year warranty.
• 96 x 48mm 1/8 DIN
• Simple menu driven pushbutton configuration
• 5 digit (-19999 to 19999) tri-color (red, green, amber) LED display
• Selectable decimal point
• True RMS for AC voltage and current inputs
• AC/DC voltage input 600V, 200V, 20V, 2V
• AC/DC current input 200mA, 1A, 5A, shunt 50mV, shunt 60mV, shunt 100 mV
• AC or DC powered
• Display scaling or teaching modes
• Optional 4-20mA analog output
• Optional (2) Form C SPDT
Activation on increasing or decreasing input signal
Hysteresis or time delay operation
Display color change on relay operation
• Configuration for direct or reverse acting
• Total or selective configuration lock out
• Programmable functions include:
Minimum (valley) and maximum (peak) value memory
Minimum (valley) and maximum (peak) value reset
Hold
• Filtering to minimize display bounce
• Display brightness adjustment
• 3 year warranty

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
7
Dimensions and Mounting
(2) Fixing clips
Sealing gasket
DPM3 Meter
Panel mounting surface
TRMS
Installation
To install the instrument, prepare a 92mm x 45mm panel cut-out and slide the unit inwards
making sure to place the sealing gasket between the front side panel and the front bezel.
While holding the unit in place, put the fixing clips on both sides of the case and slide them
through the guide tracks until they reach the panel at the rear side.
Press slightly to fasten the clips to the latching slots
on the case and get the unit fully assembled and close
fitted to achieve a good seal.
To remove the instrument from the panel, pull the
rear fixing clips latching tabs outwards until they are
disengaged, then slide the fixing clips back over the
case.
Installation
Dimensions 96 x 48 x 83.1mm (1/8 DIN)
Panel Cutout 92 x 45mm
(Max. panel thickness 10mm)
Case Material Polycarbonate UL 94 V-0

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
8
Wiring Terminals
CN2 and CN3 Terminals CN1, CN4, CN5
and CN6 Terminals
CN6
Analog Output
1(-) 4-20mA
2 (+) 4-20mA
CN5 (Relay 1)
1NO1
2CM1
3 NC1
CN4 (Relay 2)
4NO2
5CM2
6NC2
DPM3-E-A2R-H & DPM3-E-A2R-L
2 SPDT Relays
NO: Normally open, CM: Common,
NC: Normally closed
Insertion Tool (included with meter)
Insert wires into the proper terminal
while using the insertion tool to open
the clip inside the connector. Release
the insertion tool to fix wire to the
terminal.
Insertion Tool (included with meter)
Insert wires into the proper terminal
while using the insertion tool to open
the clip inside the connector. Release
the insertion tool to fix wire to the
terminal.
CN1 CN2 CN3
1 2
1 2 3 4 5
1 2 3 4
1
2
3
4
5
6
CN4 CN5
CN6
1
2
CN2
Electrical Inputs
1Common
2Shunt / 2V
3200mA
41A / 5A
520 / 200 / 600V
CN3
1Common
2Peak
3Valley
4 Hold
Polarity insensitive for
DC power
CN1
AC Supply DC
Supply
1 Line 1 VDC
2 Neutral 2 VDC
Terminals
Connector CN1 CN2 CN3 CN4 &
CN5 CN6
Wire cross section 0.08 to 2.5mm²
(28 to 12 AWG)
0.08 to 1.5mm²
(28 to 14 AWG)
0.08 to 0.5mm²
(28 to 20 AWG)
0.08 to 2.5mm²
(28 to 12 AWG)
0.08 to 2.5mm²
(28 to 12 AWG)
Strip length 8 to 9mm 5 to 6mm 5 to 6mm 8 to 9mm 8 to 9mm
Manufacturer Wago 231-
202/026-000 Wago 734-105 Wago 733-104 Wago 231-
303/026-000
Wago 231-
302/026-000
Cage clamp
connection
Insertion tool
or screwdriver
with 0.5 mm x
3.0 mm blade
Insertion tool
or screwdriver
with 0.3 mm x
1.8 mm blade
Insertion tool
or screwdriver
with 0.3 mm x
1.8 mm blade
Insertion tool
or screwdriver
with 0.5 mm x
3.0 mm blade
Insertion tool
or screwdriver
with 0.5 mm x
3.0 mm blade
Refer to the instructions in this manual to preserve safety protections.

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
9
WARNING: If this instrument is not installed and used in accordance with these
instructions, the protection provided against hazards may be impaired.
To meet the requirements of EN 61010-1 standard, where the unit is permanently connected to
main supply, it is obligatory to install a circuit breaking device easily reach by the operator and
clearly marked as the disconnecting device.
To guarantee electromagnetic compatibility, the following guidelines should be kept in mind:
• Power supply wires should be separately routed from signal wires and never run in the same conduit.
• Use shielded cable for signal wiring.
• Cables section should be ≥0.25 mm².
Before connecting signal wires, signal type and input range should be verified to be within the
right limits. Do not connect simultaneously more than one input signal to the meter.
CAUTION: Connect only one input signal range to the meter. Hazardous signal levels may be
present on unused inputs.
CAUTION: The isolation rating of the input common of the meter with respect to the option
card common and to the Logical Functions common (if used) is 250 Vrms and 500 Vrms with
respect to AC Power (terminals 1 and 2 of connector CN1). To be certain that the ratings are
not exceded, these voltages should be verified by a high-voltage meter before wiring the meter.
CAUTION:
1. Where possible, connect the neutral side of the signal (including current shunts) to the input
common of the meter. If the input signal is sourced from an active circuit, connect the lower
impedance (usually circuit common) to the imput signal common of the meter. (pin 1 CN2)
2. For phase to phase line monitoring where a neutral does not exist, or for any other signal input
in which the isolation voltage rating is exceeded, an isolating potential transformer must be
used to isolate the input voltage from earth. With the transformer, the input common of the
meter can then be earth referenced for safety.
3. When measuring line currents, the use of a current transformer is recommended. If using
external current shunts, insert the shunt in the neutral return line. If the isolation voltage
rating is exceeded, the use of an isolating current transformer is necessary.

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
10
Wiring Examples
DC/AC Voltage Input Wiring (Ranges: 2, 20, 200, 600 V)
Note: MAXIMUM VOLTAGE APPLICABLE IS: 600V DC/ AC
Terminals CN2
12345
N
L
V
Voltmeter 20/ 200/ 600 V
DC/ AC
Terminals CN2
12345
V
N
L
Voltmeter 2 V
DC/ AC
DC/AC Current Input Wiring (Ranges: 1A, 5A)
Terminals CN2
12345
I
N
L
1/5 A DC/ AC
DC/AC Direct Connection Connection using and AC Current Transformer
Terminals CN2
12345
I
N
L
1A / 5A AC MAX.
R1R2
Important:
When using a current transformer, the input impedance (Ri) of the DPM3 is 14 mOhms.
To maintain measurement accuracy, use connecting wires of appropriate gauge and length to
prevent the total resistance of the measuring circuit (R1+R2+Ri) from exceeding the Burden
rating of current transformer .
DC/AC Current Input Wiring (Range: 200mA)
Terminals CN2
12345
I
N
L
200mA DC/AC

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
11
DC/AC Current Input Wiring (Ranges: 50/60/100mV shunt)
Terminals CN2
12345
I
SHUNT
N
L
Shunt
50/ 60/ 100 mV
Display and Key Pad
PROG
MIN
MAX
TRMS
1
2
3
4
ENTER
DATA
MAX/MIN
MICRA
4
1
2
3
5
6
789
10
11
12
13
Programming Panel
# Description Run Mode Programming Mode
1True RMS Indicates reading AC using
true RMS ---
2MAX Indicates peak displayed ---
3MIN Indicates valley displayed ---
4PROG --- Indicates programming mode
5DISPLAY Displays the input variable Displays programming parameters
6UP Direct access to setpoints Increments the value of the flashing
digit
7SHIFT/MAX/MIN
KEY Recalls Max/Min values Moves to the right
8ENTER KEY Enters in PROG mode.
Displays data Accepts data. Advances program
9Free space for
units label ---
10 LED Output 4 --- ---
11 LED Output 3 --- ---
12 LED Output 2 Activaton Output 2 Programming output 2
13 LED Output 1 Activation Output 1 Programming output 1

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
12
Configuration:
When the power is applied to the meter, a display test begins automatically to check the function
of the LED’s and digits. Once this test is finished the display shows the internal software version
and then the unit goes to RUN mode.
Configuration follows a structure composed of a number of menus and submenus. By pressing
the ENTER key, the display show “Pro”. Pressing the SHIFT key repeatedly provides access
to the main menu level which includes menus for input configuration (CnInP), display
configuration (CndSP), relay configuration if present (SEtP), analog output configuration if
present (Anout), logic functions configuration (LoGIn). Press ENTER to access the submenus
under each main menu.
If configuration has been totally locked-out, when pressing ENTER to access the main menu
level, the display shows dAtA instead of Pro. This indicates that it is only possible to see
programmed information and that it is not allowed to modify any parameter from the entire
configuration. In this visualization mode, the meter automatically switches back to RUN mode
after 15 seconds sine the last key press.
-
1
Input
Menu
2
3
4
5
Display
Menu
Relay
Configuration
Menu
Analog
Output
Menu
Logic
Functions
Menu
ENTER: Vertical displacement.
UP: Changes active digit.
SHIFT: Horizontal displacement.
Programming Key Pad
The progress through the programming routines is done by pressing ENTER key. In general,
push SHIFT key a certain number of times to select an option and push ENTER key to validate
the change and move forward to the next step of the program.
Programming numerical values
When the parameter is a numerical value, the display will show the first of the digit to be
programmed blinking.
Digit selecting: Press repeatedly the SHIFT key to shift from left to right over all the display
digits.
Changing the digit value: Press repeatedly the UP key to increase the value of blinking digit
until it has the desired value.
The minus sign is programmed depending on the variable type. A variable that represents the
value of an input will be able to take a value in the range -19999 to 19999, without taking into
account the decimal point. When a digit is selected it shows values from (0) to (9), and then
(-1), (-), and comes back to show values from 0 to 9. A variable that represents a display value

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
13
will be able to take a value in the range -19999 to 19999, without taking into account the
decimal point. In these case the first digit shows 0, 1, -1, 2, 3 or -.
Completion of each submenu routine returns the meter to Pro mode. To save data entered or
changed during configuration press the ENTER key while in Pro mode. StorE will be displayed
for a few seconds while all of the configuration data is stored in memory. The meter will then
return to RUN mode.
Input Configuration
The figure below shows the input configuration menu. Divided into four submenus, each one
of them separated by the dotted line in the manual, each menu corresponds to the programming
of the different types of input: Volt dc, Volt ac, Amp dc, Amp ac. Once the type of signal has
been selected you have then to select the range. Usually the 100, 60, 50mV (nU) ranges are
shunts signals. .
ENTER: Vertical displacement.
UP: Changes active digit.
SHIFT: Horizontal displacement.
Programming Keys
(Bottom view)
CnInP
U-dC U-AC A-dC A-AC
600 U
PRO
200 U 20 U 2 U 5 A 1 A 0.2 A 100nU 60nU 50nU

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
14
Display Configuration
CndSP
tEAcHScAL FILtP round briGH Eco
InP 1
±18.888
±18888
InP 2
dSP 1
±188.88
±18.888
dSP 2
±188.88
-Pro-
InP 1
±18.888
±18888
InP 2
dSP 1
±188.88
±18.888
dSP 2
±188.88
-Pro-
8
-Pro-
88
-Pro-
-HI-
-oFF-
-Lo-
-Pro-
-on-
-Pro-
88
NOTE: In the programming of the 600 V DC
or V AC range, 600.0 is accepted as a
maximum in both ScAL and tEAcH methods .
ENTER: Vertical displacement.
UP: Changes active digit.
SHIFT: Horizontal displacement.
Programming Key Pad
Scaling
For linear signals, scaling is achieved by programming two coordinates (InP1, DSP1) and
(InP2, dSP2), between which is established a linear relation where each input signal value
corresponds to a display value. The relationship can be direct or reversed. In order to obtain
more accuracy, points 1 and 2 should be located approximately at both extremes of the process.
display2
display1
input
1
Input2
Direct scale
input
2
input
1
display1
display2
Reversed scale

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
15
Programming of the scale
There are two methods for programming the scale, the SCAL method and the tEACH
method.
2
CndSP
SCAL
InP 1
±8
8.888
dSP 1
±1
8888
InP 2
±8
8.888
dSP 2
±1
88.88
±1
88.
88
Dec. point
ENTER: Vertical displacement.
UP: Changes active digit.
SHIFT: Horizontal displacement.
tEACH
Programming Key Pad
SCAL method
The input and display values are programmed manually. This method can be used when the
value of the signal at each points of the process is known.
tEACH method
The input values are introduced directly from actual electrical values. The input signal device
must be connected to the meter and operational when each point is programmed. The display
values are programmed manually. This method can be used when it is possible to bring the
process to the conditions of each one of the points to be programmed.
Weighted Average Filter P
0to 9 (4Hz to 0.05 Hz)
Sets low-pass filter cutoff frequency (Fc) which allows the meter to smooth out undesirable
display reading fluctuations. The value can be modified through the SHIFT key. This parameter
will set in reverse order the cut-off frequency of the low pass filter, getting the filter deactivated
for 0 value.

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
16
Round
01 05 10
Will take each one of the values by pressing successively on the SHIFT key. with 01 there will be
no round, 05 will round the display value at 0 to 5, and with 10 will round at 0 to 10.
Brightness
HI Lo
Display brightness level selection.
Hi: high brightness
Lo: low brightness
Display color selection between green, red or amber is possible for both RUN and Pro modes.
Eco
on off
Allows choosing an operative mode with an up to 45% of ENERGY SAVING*
on: After a programmable time without pressing any key, display will turn off leaving only the
right decimal point flashing; all functions remain active. Display will be again active after
pressing any key.
oFF: Deactivates the function.
* Measured at 230V AC power supply, display 100.00, amber colour and with no options.
Additional Functions
Several functions can be controlled via Key Pad that will produce different actions depending
on the instrument operating mode:
MAX/MIN function
With the meter in RUN mode: Activated after pressing the SHIFT key. From RUN mode, a
press shows the maximum value (peak) read by the instrument since the last time it has been
switched on, unless a RESET MAX/MIN is done, the MAX led will light up. A second press
shows the minimum value in the same conditions as before, with the consequent minimum
(valley) indication through the MIN led. A third press brings the instrument back to RUN
mode.
Reset MAX/MIN
With the meter in RUN mode: Pressing the SHIFT key for 3 seconds, while the meter shows
the peak value (MAX), will produce a reset of the value. Pressing SHIFT key for 3 seconds while
the meter shows the valley value (MIN) will produce a reset of the value.

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
17
Configuration Lockout
In mode RUN if the ENTER key is pressed for 3 seconds, the meter will show the indication
CodE, and following 0000, allowing the user to introduce the security code. If the code that
has been introduced is wrong, the meter will go back to RUN mode, if it is correct, it will
allow the access to the security menu. See section detailing Configuration Lockout.
Programming Mode
One press on the ENTER key will bring the instrument to the Programming Mode -Pro-
mode.
Return to Factory Configuration
After accessing programming mode, Pro press and hold the up key for 3 seconds. Allows
entering a code of access to the reset of the configuration parameters, this code is 74. When
entering this code the instrument shows the LoAdIng dEFAuLt ConFIGurAtIon legend,
and then StorE, which means that they have been stored in the non volatile memory of the
meter.
Factory c
onfigura
tion
INPUT
: 600V DC
DISPLAY
Input 1: 0000.0 Display 1: 0000.0
Input 2: 600.0 Display 2: 600.0
Filter P: 0
Round: 01
Brightness: High
DISPLAY COLORS Run Mo
de
:
Green
, Prog
Mode
.:
Amber
SETPOINTS
Setpoint 1: +01
.000, Setpoint 2: +02.000
Mod
e
: HI
Dly: 00.0
Alarm
Color
:
No C
hange
ANALOG OUTPUT
CONFIGURA
TION
Display HI: 1000.0
Display LO: 0000.0
LOGIC FUNCTIONS PIN 2=function 3, PIN
3=function 4
and
PIN 4=function
6
Eco: off
-
-
3s?
=74?
Direct Access to Relay Setpoints
If the DPM3 has relay outputs present the meter allows direct access to the programming of
the setpoint values. After accessing programming mode, Pro, pressing the UP key provides
access to each relay setpoint value.
Logic functions
The connector CN3 provides 3 optocoupled inputs that can be operated from external switches.
Three different functions may be assigned to the inputs using the front panel keys. Each function
is associated to a pin (PIN 2, PIN 3 or PIN 4) that is activated by applying an external switch
closure with respect to PIN 1 or COMMON. Function assignments to the inputs are achieved

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
18
through the programming of a number between 0 and 15 corresponding to one of the functions
listed in the following table.
Factory configuration
As shipped from the factory, the CN3 connector allows remote control of the PEAK, VALLEY
functions as well as the HOLD function.When a HOLD is made, the display value remains
frozen while the corresponding pin is activated. The HOLD state affects neither the meter
internal operation nor the analog and relay outputs if present.
Logic functions diagram
1 2 3 4
1 2 3 4
CN3
1 2 3 4
PIN (INPUT) Factor Default
Functions Function
PIN 1 COMMON
PIN 2 (INP-1) PEAK Function No. 3
PIN 3 (INP-2) VALLEY Function No. 4
PIN 4 (INP-3) HOLD Function No. 6
The external electronics applied to the CN3 connector inputs must be capable of withstanding
a potential of 40V / 20 mA present at all terminals with respect to COMMON. In order to
guarantee the electromagnetic compatibility please refer to the connection instructions in the
Wiring Terminal section.
Logic functions menu
-
-
-
-
-
-
-
-
-
ENTER: Vertical displacement.
UP: Changes active digit.
SHIFT: Horizontal displacement.
Programming Key Pad

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
19
Table of programmable functions
• Nº: Number to select the function.
• Function: Function name.
• Description: Description and characteristics of the function.
• Activation by:
Falling edge: the function is activated applying a falling edge to the
corresponding pin with respect to common.
Low level: the function will remain activated as long as the corresponding
pin is held at a low level.
No. Function Description Activation By
0Deactivated None None
1Deactivated None None
2Deactivated None None
3PEAK Displays the peak value. (MAX.) Low level
4VALLEY Displays the valley value. (MIN) Low level
5RESET PEAK/VALLEY Perform a reset of the peak or the valley, depending on which is being
displayed. Falling edge
6HOLD Freeze the display while all the outputs remain active Low level
7Deactivated None None
8Deactivated None None
9Deactivated None None
10 Deactivated None None
11 BRIGHTNESS Change the display brightness from Hi to Low Low level
12 SETPOINT VALUE Displays the selected setpoint value (see diagram next page) Low level
13 False Setpoints Simulates that the instrument has a four setpoints option installed Low level
14 Deactivated None None
15 Deactivated None None
16 Remote keypad The three logic inputs act as a remote keypad* Edge
* It’s mandatory programming the 3 logical inputs with function 16

DPM3-E Electrical User Manual, 1st Edition
User Manual - DPM3-E Series Electrical Panel Meters
20
Configuration Lock Out
The meter is delivered with the programming not locked out, giving access to all the
programming levels. Once completed the meter programming the following security measures
are recommended:
1. Lock out the programming access to prevent from programmed parameters modifications.
2. Lock out Key Pad functions to prevent from accidental modifications.
3. There are two lockout modes: selective and total. If the parameters are going to be readjusted
frequently, make a selective lockout. If no adjustment is going to be made, make a total
lockout. Key Pad functions lockout is always possible.
4. The access to the lockout routine is allowed by entering a personalised code. We recommend
changing the code set at factory and to write down your personalised code and keep it in a
safe place.
TOTAL LOCKOUT
The access to the programming routines to read data is allowed even if all parameters are locked
out totLC=1, but it won t be possible to enter or modify data. In this case, when entering in
the programming mode, the display shows the indication “-dAtA-”.
PARTIAL LOCKOUT
When only some parameters are locked out, all configuration data can be read but only non
protected parameters can be modified. In such case, when entering in the programming
mode, the display shows the indication -Pro- “.
Menus or submenus that can be locked out are:
• Relay 1 configuration (SEt 1). If present in meter.
• Relay 2 configuration (SEt 2). If present in meter.
• Input configuration (InPut).
• Display (diSP).
• Display color (CoLor).
• Relay setpoints value (SPVAL). If present in meter.
• Analog output configuration (Anout). If present in meter.
• Logic inputs configuration (LoGIn).
• Direct access to MAX. and MIN values (MAHMn).
This manual suits for next models
4
Table of contents
Other AutomationDirect Measuring Instrument manuals

AutomationDirect
AutomationDirect ProSense VFS50-5-1001 User manual

AutomationDirect
AutomationDirect ProSense FG1 Series User manual

AutomationDirect
AutomationDirect ProSense DPM3-P Series User manual

AutomationDirect
AutomationDirect prosense TTD-20-N40160F-H User manual

AutomationDirect
AutomationDirect ProSense DPM2-E Series User manual

AutomationDirect
AutomationDirect ProSense DPM1-P Series User manual

AutomationDirect
AutomationDirect OP-406 User manual

AutomationDirect
AutomationDirect ProSense DPM1 Series User manual

AutomationDirect
AutomationDirect ProSense LPM1 Series User manual

AutomationDirect
AutomationDirect ProSense DPM3 Series User manual