AB-7354-U
8
(2/2)
Item Specification
Valve sensor*3
Pressure
measuring
Measuring
range
0 to 290 psig*4
Accuracy 0.5 %FS (factory preset)*5
Temperature
measuring
Measuring
range
32 to 176 F (0 to 80 °C)
Accuracy 1.8 F (1 C) (factory preset)*6
(within 32 to 176 F (0 to 80 °C) measuring range, at -13 to 104 F (25 to 40 °C) temperature
difference between measuring temperature and ambient temperature)
Pt100
input
Temperature
measuring
Accuracy*7Conversion accuracy:
0.72 F at 32 to 176 F (
0.4 C at 0 to 80 °C) ambient temperature
1.08 F at -4 to 32 F (0.6 C at -20 to 0 °C) ambient temperature
Error due to wiring length: 0.27 F at 49.2 49.2 ft (0.15 C at 15 15 m)
in the 32 to 176 F (0 to 80 °C) measuring range
Temperature sensor
for pipe surface
Accuracy 1.8 F (1 C) (factory preset)*8
Energy calculation*9
(with two
temperature
sensors (Pt100
input) connected)
Accuracy Temperature difference
b/w supply and return
water
Flow measuring accuracy*
5 %RD 7 %RD 1 %FS 3 %FS
T = 9.0 F (5 C)
25 %RD
27 %RD
21 %FS 23 %FS
T = 18 F (10 C)
15 %RD
17 %RD
11 %FS 13 %FS
T = 27 F (15 C)
12 %RD
14 %RD
8 %FS 10 %FS
Notes:
*3 Valve sensor is the temperature and pressure sensors mounted onto the valve of the product, measuring valve surface temperature and
inlet and outlet flow pressure.
*4 When you test the withstand pressure of the valve sensor, up to 493 psig pressure can be applied to the valve sensor.
*5 The above pressure measuring accuracy is for the 44.6 to 149 F (7 to 65 °C) flow temperature. If the flow temperature is out of the 44.6 to
149 F (7 to 65 °C) range, the valve sensor flow measuring accuracy may decrease.
*6 For accurate measuring of flow temperature, thermal insulation is required. Refer to the subsection Heat insulation for applying thermal
insulation and AB-6923 Specifications/ Instructions of Temperature Sensor for Pipe Surface, Installation, Procedure.
*7 Overall accuracy is calculated based on the sensing accuracy of the temperature sensors connected, the conversion accuracy, and the
error due to wiring length.
*8 Heat and cold insulation is required to measure the flow temperature.
Refer to AB-6923 Specifications/ Instructions of Temperature Sensor for Pipe Surface, Installation, Procedure.
*9 Energy calculation accuracy is calculated from the flow measuring accuracy at 1.8 F (1 C) measuring error of the temperature difference.
*10 The flow measuring accuracy in the table corresponds to the data shown in the above flow measuring accuracy graph.
Data in Model FVY513EJ
Data type Description
Flow data Following items are displayed on Display Panel (Model QY5010S1000):
Actual flow rate, supply water temperature, return water temperature, valve inlet pressure, valve outlet pressure,
actual flow rate (% in bar graph), actual valve position (% in bar graph)
Following items are retrieved via RS-485 communication (Modbus protocol):
Control setting value, actual valve position, actual flow rate, set flow rate, supply water temperature, return water
temperature, valve inlet pressure, valve outlet pressure, instantaneous energy, totalized flow rate, totalized
energy, cool/heat status, point status*1
Device data Following items are retrieved via RS-485 communication (Modbus protocol):
Model number, date of manufacture, version of hardware, version of software, serial number, power-ON time,
operating time, operating level, number of operations, number of reverse, range, device status*2
Notes:
*1 Point status indicates an error of analog data. Refer to AB-7363-U Instruction Manual of ACTIVAL Flow Measurement and Control
Valve Standalone Model for details.
*2 Device status indicates the status of this product. Refer to AB-7363-U Instruction Manual of ACTIVAL Flow Measurement and Control
Valve Standalone Model for details.