Type 0911
2 stage controller
2-Punkt-Regler
2 Régulateur Ponctuel
Id. No. 788 263
788 264
788 265
788 266

We reserve the right to make technical changes without notice.
Technische Änderungen vorbehalten.
Sous resérve de modification techniques.
© 2004 - 2017 Bürkert Werke GmbH & Co. KG
Operating Instructions 1706/03_EU-ml_00804604

0911 - 1
english
1 GENERAL INFORMATION ........................................................................................................................ 2
1.1 Symbols ......................................................................................................................................................... 2
1.2 Safety notes ................................................................................................................................................ 2
1.3 Scope of delivery...................................................................................................................................... 3
1.4 Warranty provisions ............................................................................................................................... 3
2 SYSTEM DESCRIPTION ............................................................................................................................ 4
2.1 General description ................................................................................................................................. 4
2.2 Operation ...................................................................................................................................................... 4
2.3 Before the installation ............................................................................................................................. 7
2.4 Parameters .................................................................................................................................................. 8
2.5 Controlling the loads ............................................................................................................................. 11
3 TECHNICAL DATA ..................................................................................................................................... 12
4 ASSEMBLY, INSTALLATION AND COMMISSIONING .......................................................... 13
4.1 General information regarding the installation and operation ......................................... 13
4.2 Assembly .................................................................................................................................................... 13
4.3 Electrical connections .......................................................................................................................... 14
5 HOT-KEY FUNCTION ................................................................................................................................. 16
6 FACTORY SETTING .................................................................................................................................. 17
7 MAINTENANCE ............................................................................................................................................ 18
8 REPAIR WORK .............................................................................................................................................. 19
8.1 Faults............................................................................................................................................................. 19
8.2 Ordering table for basic unit/accessories ................................................................................ 20
2-STAGE CONTROLLER
TYPE 0911

2 - 0911
english
1 GENERAL INFORMATION
Please observe the notes in these operating instructions together with the
conditions of use and permitted data that are specified in the data sheets of
the 0911 controller, so that the device will function perfectly and will have a
long service life.
• Keep to the standard engineering rules when planning and operating the
device!
• Installation and maintenance work may only be carried out by specialist
personnel using the correct tools!
• Observe the current regulations on accident prevention and the safety
regulations for electrical devices during the operation and maintenance of
the device!
• Comply with the intended usage of the device.
• Only operate the device with its housing fitted.
• Before connecting the device, check that the power supply corresponds to
the values printed on the device.
• Check that the connections are correct before switching on the device.
• Observe the maximum load of the relay contacts (see technical data).
• Ensure that all sensors are installed with sufficient separation from voltage-
conducting lines. This will avoid incorrect temperature readings and will
protect the device from voltage interference at the sensor inputs.
• For applications in the industrial sector with critical environments, switch an
RC element in parallel (FT1).
• Always switch off the mains supply before carrying out manipulations on
the system.
• Take suitable measures to exclude unintended operation and damage by
unauthorised operation!
1.1 Symbols
1.2 Safety notes
The following symbols are used in these operating instructions:
marks a work step that must be carried out.
ATTENTION! indicates information which, if ignored, could lead to a risk to
your health or to the functionality of the device.
NOTE indicates important additional information,
tips and recommendations.

0911 - 3
english
1.3 Scope of delivery
Immediately after receiving the delivery, ensure that the contents agree with
the scope of the delivery. This includes:
• 1 Type 0911 controller
• 1 set of operating instructions (where required, on a data carrier)
• 1 front seal
• 2 Mounting clamps
1.4 Warranty provisions
Bürkert provideds a guarantee of one year on the correct functioning of the
controller, under the precondition that the device is employed for its intended
use and under compliance with the specified conditions for use.
If the functions of the device are not in order, the respective device will be
repaired free of charge or will be replaced.
ATTENTION! The warranty only covers the the controller and its compo-
nents, but does not cover consequential damage of any kind
that could arise from the failure or malfunctioning of the device.
In case of discrepancy, please contact our Customer centre immediately:
Bürkert Steuer- und Regelungstechnik
Service-Abteilung
Chr.-Bürkert-Str. 13-17
D-76453 Ingelfingen
Tel. : 07940-10111
or your Bürkert Sales Centre.
• Please observe the prescribed environmental conditions with regard to
dampness and temperature limits. Malfunctions cannot be excluded if these
conditions are not complied with.
• Call in your authorised Bürket sales centre in case of doubt or faulty
functioning.
In the case of the non-observance of these notes or of unauthorised
manipulation of the device, we will accept no liability, and the guarantee on the
device and its accessories will become void!

4 - 0911
english
2-point controller, 74 x 32 mm, with predefinable control function (e.g., heating/
cooling or moisten/dehumidify)
The following models are available:
2.1 General description
2 SYSTEM DESCRIPTION
2.2 Operation
BUTTONS
SET Display of the set-value,
Changing and confirming a default during the programming phase
up-
wards
down-
wards
LED 2
SET
button
ES LED
LED1
Type Configurable Input Parameter UDM
(Defined by display unit)
TU
Temperature
controller
PTC, NTC, Pt100
Thermoelements J, K, S
UDM = °C
UDM = °F
AU
Control device with
current / voltage
input
4 ... 20 mA
0 ... 1 V
0 ... 10 V
0 = °C; 1 = °F
2 = % RH
3 = bar
4 = PSI
5 = without units
BUTTON COMBINATIONS
Locking and unlocking the keypad
SET+ Selecting the programming level
SET+ Return to the room temperature display
+
Alarm
LED
Output 1

0911 - 5
english
LED Mode Meaning
on Output active
LED1 blinks Programming level (blinks together with LED2)
LED2 blinks Programming level (blinks together with LED1)
E.S. on Energy-saving mode (second set-value) has
been activated by the digital input
Alarm
LED on
- Signals an Alarm state
- If you are in the lower programming level
"Pr2", which can only be accessed using
a password, the lighting up of the Alarm LED
signals that the displayed parameters can
also be accessed in the first level Pr1
(without password).
LED MESSAGES
SET-VALUE DISPLAYS
Briefly press the SET button once. The set-value
display appears in the display.
Briefly press the SET button again, or wait 5
seconds in order to display the room temperature.
SWITCH DEVICE ON/OFF
Hold the SET button down for at least 4 sec
(only for parameter OnF = yes).
CHANGE THE SET VALUE
Hold the SET button down for 2 seconds.
Change the set-value within 10 s with the or
buttons.
You can save the new set-value by briefly pressing
the SET button or by waiting 10 seconds.

6 - 0911
english
ENTER PROGRAMMING LEVEL
Hold the SET + buttons down for at least 3
seconds
Select with Pr2 and then confirm with the SET
button.
Enter the password 321 and then confirm with the
SET button.
Enter the „3“ and then 1x SET button
Enter the „2“, and then 1x the SET button
Enter the „1“, and then 1x the SET button
You are now in the Parameter List.
USER LEVEL PR1
Press down the SET + buttons for 3 seconds.
PR1 contains all the parameters accessible to the
user. The device shows the first parameter that is
available in the user level.
SERVICE LEVEL PR2 (PASSWORD 321)
See:
Accessing the programming level.
ADDING/REMOVING PARAMETERS INTHE USER LEVEL „PR1“
Accessing the programming level
The status can be changed with the SET +
buttons.
If a parameter is not visible in the PR1 level, this will
be indicated by an LED point.
CHANGINGTHE DEFAULT PARAMETERS
Enter a desired value with SET + or .
Then confirm with the SET button.
Enter a desired parameter with or .

0911 - 7
english
LOCKING AND UNLOCKINGTHE KEYPAD
Hold down the buttons and for at least 3
seconds. The POF message appears on the
display.
The keyboard is locked. You can only view the
set-value and the minimum and maximum
temperature. The POF message also appears if you
hold down a button for longer than 3 s.
The keyboard will be unlocked if you hold down
the buttons and for 3 s. POn appears in the
display for a few seconds.
NOTE All parameter values can be seen by repeatedly pressing the
SET buttons.
2.3 Before the installation
PREDEFINE THE SENSOR TYPE
Hold down the SET + button for at least 3
seconds.
Select the parameter Pbc (sensor type) and then
confirm with the SET button to see the current
default.
Type TU (temperature controller):
J = Thermoelement J; Pt = Pt100;
C = Thermoelement K; Ptc = PTC;
S = Thermoelement S; ntc = NTC
Type AU
(control devices with voltage/current input):
cur = 4...20 mA; 0-1 = 0...1 V; 10 = 0...10 V
Confirm the default with the SET button.
Briefly switch off the power to the device.
The configurable input type is noted on the controller
label. Please enter this input type if it does not
corresponds to the connected sensor type.

8 - 0911
english
2.4 Parameters
Control
Hy1
Hysteresis 1
Switch hysteresis of Set-value 1 with
positive or negative values. The default
range is dependent on the input type.
The parameter may not be entered as
zero.
LS1
Lowest set-value setting
Set-value limits for operator
US1
Highest set-value setting
Set-value limits for operator
S1C
control effect
in = inverse (heating, humidification)
dir = direct (cooling, dehumidification)
AC
Minimum switch duration
0...250 sec relay switch-off duration
on
Minimum switch-on period
0...250 sec relay switch-on period
ono
Minimum delay
0...120 min; minimum delay between two
activations of the control relay.
Alarms
ALC
Configuration
rE = relative to the set-value (in Kelvin)
Temperature alarm
Ab = absolute values (in °C)
ALL
Low temperature alarm
If SET - ALL is undershot,
a low temperature alarm will be triggered
after the delay time ALd.
ALU
Over-temperature alarm
If SET + ALU exceeded, a high
temperature alarm will be triggered after
delay time ALd.
ALd
Alarm delay
0...999 min; Minimum time in which the
at
temperature
conditions for an alarm situation
Overshoot/Undershoot
must be present.
Sensor Lower limit Upper limit
NTC -40°C 110°C
PTC -50°C 150°C
Pt100 -200°C 600°C
TcK 0°C 1300°C
TcJ 0°C 600°C
TcS 0°C 1400°C
MEASUREMENT LIMITS FOR THE SENSOR TYPES

0911 - 9
english
Alarms
ALH
Hysteresis for the
Automatic alarm acknowledgement:
Limit value alarms
With high alarm undershot by
ALL and ALU
ALU - ALH and with low alarm with
under shooting of ALL + ALH
(0.1 K...upper measurement range)
dAO
Alarm delay at
0...23.5 hours; suppression of
with Mains ON
Alarms after commissioning.
S01
Status of the control relay
oFF = opened
with sensor fault
on = closed
tbA
Status of the control relay
oFF = Relay deactivated
after acknowledgement (by
on = Relay activated
(any button) in an
alarm situation
AS
Configuration of the alarm
cL = Terminal 4-5 closed
relay at an alarm
oP = Terminal 4-6 closed
Measured value display
LCI
Lower analog
Lower display value for current input
Display value
4 mA or with voltage input 1 V
(-1999...1999)
or 10 V (only for inputs 4-20
mA, 0-1V, 0-10 V)
UCI
Upper analog
Upper display value for current input
Display value
20 mA or for voltage input 1 V or 10 V
(-1999...1999)
(only for the 4-20 mA, 0-1V, 0-10 V
inputs)
OPb
calibration of the sensor
regardless of the measurement range
rES
Resolution
in = only whole numbers
dE = also tenths
ce = hundreths
UdM
Units
Display of the units directly in the
illuminated display. Regardless of which
controller type is being used:
see
General description
PbC
Type of sensor
Type of inout
Temperature sensor U):
J = Thermoelement „J“; Pt = Pt100;
C = Thermoelement „K“; Ptc = PTC;
S = Thermoelement „S“; ntc = NTC
Current / voltage input
cur = 4...20 mA; 0-1 = 0...1 V;
(AU)
10 = 0...10 V
P3F
Third terminal of a
(if present)
Pt100 sensor
no = Pt100 2-wire wired
yES = Pt100 3-wire wired

10 - 0911
english
NOTE You can access hidden paramaters by holding down the keys
SET + for 3 sec in the programming level HY. The message Pr2
appears.
Digital inputs
HES
Temperature increase/
Set-value is increased/lowered by HES
Reduction
during the energy saving phase.
i1F
Function of the digital
EAL = external alarm; OFF = unused;
Input
bAL = serious external alarm;
Es = Energy saving mode Start/Stop;
onF = switch the device ON/OFF
externally;
C-H = reverse the control effect
i1P
Polarity of the digital
CL: active with closed contact
input
OP: active with opened contact
did
Alarm delay time
For i1F = EAL or i1F = bAL.
of the digital input
The corresponding alarm
(1...120 min)
display or message then takes place
Miscellaneous
Adr
Serial address RS485
Address for XJ500 recording
(1...247)
system. Identifies the device if it
is linked into a ModBUS-compatible
system.
OnF
Set device to STAND-BY
no = not possible via keyboard
yes = STAND-BY can be activated by
holding down the SET button of at least
4 sec. During a STAND-BY, OFF is
displayed.
Ptb
Number of the parameter-
only read-out value
table
rEL
Version
only read-out value
Pr2
Display of the parameters in
display only
Level Pr2

0911 - 11
english
HEATING
Parameter S1C = in; The value HY has been preset to 2 K in the factory.
If the temperature falls below the value SET-HY, the controller output will be
switched on and will be switched off again when SET is exceeded.
2.5 Controlling the loads
CONTROLLER OUTPUT
The control is dependent on the measured temperature (= sensor
temperature). Program the control direction (heating or cooling) with the
parameter S1C.
S1C = dir Cooling SET = Set-value
S1C = in Heating Hy = Switch hysterisis
COOLING
Parameter S1C = dir; The value HY has been preset to 2 K in the factory.
If the temperature exceeds the value SET + HY, the compressor will be
switched on and will be switched off again when the temperature is below SET.
ON
t
t
temperature
SET
SET-HY
heat
t
temperature
compressor
SET
SET+HY
ON
t

12 - 0911
english
3 TECHNICAL DATA
• Housing ABS, self-extinguishing
• Dimensions Front 74 x 32 mm, Depth 60 mm
• Assembly Panel-mounting unit for 29 x 71 mm cutout
• Protection class IP65 from front, only with front seal RG-C
IP20
• Connections Screw terminals
• Pipe cross-section ≤2.5 mm2
• Auxiliary energy depending on model
12...24 V AC / DC; ± 10%
230 V AC; ± 10%; 50 / 60 Hz
optional 110 V AC; ± 10%; 50 / 60 Hz
• Power consumption max. 3 VA
• Display three digits, red LED, height 12 mm
• Inputs configurable NTC / PTC or
NTC / PTC / Pt100 / Thermoelement J, K, S
or 4...20 mA / 0...1 V / 0...10 V
• Relay outputs Changeover 8(3) A, 250 V AC
• Other outputs acoustic alarm (optional)
• Data memory EEPROM
• Ambient temperature 0 ... +60°C / +32 ... +140°F
• Storage temperature -30 ... +85°C / -22 ... +185°F
• Air humidity 20 ... 85% (non-condensing)
• Measurement range according to sensor
• Resolution 0.1°C or 1°F
• Accuracy at + 25 °C better than 0.5% of the measurement range

0911 - 13
english
4 ASSEMBLY, INSTALLATION AND COMMISSIONING
4.1 General information regarding the installation and operation
ATTENTION! • Do not lay cables for inputs next to lines carrying voltage.
• Avoid heavy vibrations, aggressive gases, heavy soiling
and damp.
NOTE • Before connecting the device, check that the power supply
corresponds to the values shown on the rating plate.
• Observe the maximum loading of the relay contacts (see
Technical data
).
• Ensure that you install all sensors with sufficient separation
from lines carrying voltage, in order to avoid incorrect
temperature measurements and to protect the device from
voltage interference over the sensor inputs.
Panel Mounting clamp
4.2 Assembly
The device is designed for panel mounting in a 71 x 29 mm cutout, and is
secured with a mounting clamp.
In order to guarantee the front protection of IP65, a rubber seal must be fitted
behind the mounting frame (optional for RG-C).
Thje ambient temperature form problem-free operation lies in the range from
0 ... +60°C.
Ensure sufficient ventilation through the cooling slots.

14 - 0911
english
Panel Mounting frame
Front seal
4.3 Electrical connections
Use cable with a cross-section of max. 2.5 mm2. The device is provided
with the corresponding screw terminals.
Check the auxiliary energy before you connect the power supply
(see
Technical data
).
Do not load the relay contacts higher than permitted. If necessary, use a
contactor.

0911 - 15
english
PIN ASSIGNMENT
12 V AC/DC or 24 V AC/DC
Standard signal input: 0...1 V; 0...10 V = 7(+), 9(-)
4...20 mA = 7(+), 9(-)
Thermoelement J, K, S = 7(+) - 9(-)
sensor: Pt100 = 7 - 9(8)
voltage supply: 24 V AC/DC = 11 - 12
230 V AC
Standard signal input: 0...1 V; 0...10 V = 9(+), 11(-)
4...20 mA = 9(+), 11(-)
Thermoelement J, K, S = 9(+) - 11(-)
sensor: Pt100 = 9 - 11(10)
voltage supply: 230 V AC = 7 - 8
operating
contacts
(1, 2, 3)
alarm
contacts
(4, 5, 6)
operating
contacts
(1, 2, 3)
alarm
contacts
(4, 5, 6)

16 - 0911
english
DOWNLOAD (HOT-KEY CONTROL DEVICE)
Switch off the electrical power to the controller, or set it to STAND-BY.
Insert the HOT-KEY up to the stop in the marked position on the controller.
Re-activate the controller.
The default parameters in the HOT-KEY will be automatically written into the
controller. During this time, the message DoL blinks in the display. The
programming procedure is finished after 10 seconds, and normal operation
starts automatically with the new parameter set.
The HOT-KEY can be removed.
5 HOT-KEY function
Writing the stored parameter set from the HOT-KEY into the control device:
end for a correct data transfer
err for a failed data transfer
In this case, briefly switch off the power to the device to repeat the
procedure. If you want to cancel the procedure, simply remove the HOT-
KEY.
The following messages are possible at the end of the data transfer:
UPLOAD (CONTROL DEVICE HOT-KEY)
Insert the HOT-KEY into the provided position when the controller is
switched on again.
Operate 1x with . The message uPL can be seen in the display.
Press the SET button in order to start the data transfer. uPL starts to blink.
You can remove the HOT-KEY again after about 10 seconds.
Writing the current default parameters of the control device into the HOT-KEY:
end for a correct data transfer
err for a failed data transfer
In this case, press the SET button again to repeat the procedure. If you
want to cancel the procedure, remove the HOT-KEY.
The following messages are possible at the end of ther data transfer:

0911 - 17
english
6 FACTORY SETTING
PA1Description Range Default PE2
SET Set-value LS1 + US1 0 Pr1
HY1 Switch hysterisis 1 dependent on measurement
range -1 Pr1
LS1 Lowest set-value 1 Lower measurement range +
SET1 min Pr2
US1 Largest set-value 1 Upper measurement range +
SET1 max Pr2
S1C Control effect Output 1 in = inverse; dir = direct in Pr2
Ac Delay time for the relay 0...250 sec 0 Pr2
on Minimum switch-on time
for a relay 0...250 sec 0 Pr2
ono
Minimum waiting time
between two consecutive
activations of the same
load
0...120 min 0 Pr2
ALC
Alarm limits are absolute
values or related to the
set-value
rE = relative; Ab = absolute rE Pr2
ALL Lower Alarm Limit
(ALC = rE; ALC = Ab)
dependent on measurement
range 10 Pr2
ALU Upper Alarm Limit
(ALC = rE; ALC = Ab)
dependent on measurement
range 10 Pr2
ALH Switch hysterisis for
temperature alarms
dependent on measurement
range 2Pr2
ALd Alarm delay time during
the operation 0...999 min 15 Pr2
dAO Alarm delay time after
commissioning 0...23.5 h 1.3 Pr2
So1 Output 1 for sensor error oFF = open; on = closed oFF Pr2
tbA Alarm relay can be
acknowledged no; yES yES Pr2
AS Polarity of the Alarm
relay CL...oP oP Pr2
LCI3Lower analog display
value depending on sensor var. Pr2
1Parameter
2Programming level
3Only for devices with voltage and current input

18 - 0911
english
7 MAINTENANCE
When operated in accordance with the instruction in this handbook, the 0911
controller is maintenance-free.
PA1Description Range Default PE2
UCI3Upper analog display
value depending on sensor var. Pr2
Opb Sensor calibration depending on measurement
range 0Pr1
rES Resolution in = NO; dE = 0.1; cE = 0.01 in Pr2
UdM Units
Type TU: °C = °C, °F = °F;
Type AU: 0 = °C, 1 = °F;
2 = RH, 3 = bar, 4 = PS,
5 = without display
var. Pr1
PbC Type of sensor
Pt = Pt100; J = tcJ; c = tck;
S = tcS; Ptc = PTC;
ntc = NTC; 0.1 = 0...1 V;
10 = 0...10 V; cur = 0...20 mA
var. Pr1
P3F 3rd sensor present no = no; yES = yes no Pr2
HES Energy-saving mode Down scale / Full scale 0 Pr2
i1F Configuration of the
digital input
c-H / oFF / off / HES /
EAL / bAL EAL Pr2
i1P Polarity of the digital
input
cL = closed;
oP = open cL Pr2
did Alarm delay of the digital
input 0...120 min 0 Pr2
Adr Serial address for XJ500 RS485 address 1 Pr2
OnF Activate Standby
function no = no; oFF = active no Pr2
Ptb Parameter table Read value - Pr2
rEL Software version Read value - Pr2
Pr2 Parameter access to Pr2 Read value 321 Pr1
1Parameter
2Programming level
3Only for devices with voltage and current input
Other manuals for 0911
1
Table of contents
Languages:
Other Bürkert Controllers manuals

Bürkert
Bürkert 8692 User manual

Bürkert
Bürkert 8691 User manual

Bürkert
Bürkert 2012 User manual

Bürkert
Bürkert eCONTROL 8611 User manual

Bürkert
Bürkert 8311 User manual

Bürkert
Bürkert 8690 User manual

Bürkert
Bürkert 8619 multiCELL WM AC User manual

Bürkert
Bürkert Type 8605 User manual

Bürkert
Bürkert TopControl ON/OFF User manual
Popular Controllers manuals by other brands

Alstom
Alstom GEM80-400 Series Technical manual

IFM
IFM CR7132 Original operating instructions

Weathermatic
Weathermatic SmartLink SmartLine owner's manual

Samson
Samson EB 8315 EN Mounting and operation instructions

Harman Kardon
Harman Kardon CITATION 5.0 Quick start instructions

Arkel
Arkel KM-20 user manual