Bürkert 8311 User manual

Instruction manual
© Bürkert 2000 Subject to technical change without notice

ENGLISH
ENGLISH
1.1 Utilisation..................................................................................................................................................................................................5
1.2 Precautionsatinstallationandcommissioning.........................................................................................................6
1.3 Conformity to standards6
2.1 Design.........................................................................................................................................................................................................8
2.2 Measuringprinciple.........................................................................................................................................................................8
2.3 Availableversions..............................................................................................................................................................................9
2.4 Accessories............................................................................................................................................................................................9
4.1 Generalrecommendations.....................................................................................................................................................14
4.2 Mountingonthepipe..................................................................................................................................................................14
4.3 Electricalconnection...................................................................................................................................................................15
4.3.1 Cableplugs...........................................................................................................................................................................15

ENGLISH
ENGLISH
4.3.2 Versionwithtransistoroutput(NPN/PNP)...........................................................................................16
4.3.3 Versionwithrelayoutput...........................................................................................................................................17
5.1 Generalrecommendations.....................................................................................................................................................18
5.2 Functionalities...................................................................................................................................................................................18
5.3 Programmingkeys........................................................................................................................................................................19
5.4 Defaultconfiguration...................................................................................................................................................................19
5.5 Normalmode......................................................................................................................................................................................20
5.6 Possibleswitchingmodesofthe8311.......................................................................................................................21
5.7 Calibrationmode.............................................................................................................................................................................22
5.8 Simulationmode..............................................................................................................................................................................25
6.1 Cleaning.................................................................................................................................................................................................26
6.2 Errormessages................................................................................................................................................................................26
7.1 Examplesofconnectionswiththe8311....................................................................................................................28
7.2 Descriptionofthelabelofthecontroller8311.....................................................................................................31

ENGLISH
ENGLISH
0-2 6 7
0-5 12 15
0-10 25 30
0-20 50 60
0-50 120 150

ENGLISH
ENGLISH
- The 8311 controller has only been designed to measure the relative
pressure of a liquid or a gas
- The following units are available to display the measured pressure: bar,
kPa, psi, mPa, Torr, mmHg, atm, MWS, mbar
- The measuring element must be solidly screwed onto its support
There will be no manufacturer warranty for damages caused by unexpec-
ted handling or wrong usage of the device The warranty on the device
becomes invalid if any modification or change is made on the device

ENGLISH
ENGLISH
- When the device is powered and the cover is open, protection against
electric shocks is not effective
- Always ensure the materials in contact with the medium to measure
are chemically compatible
- To clean the device, only use chemically compatible products
- Do not insert any object (screwdriver for instance) inside the sensor
body If the body is dirty, use compressed air to clean it
Conformity to standards
- EMC: EN 50 081-1, 50 082-2
- Security: EN 61 010-1
- Vibration: EN 60068-2-6
- Shock: EN 60068-2-27

ENGLISH
ENGLISH

ENGLISH
ENGLISH
The pressure controller 8311 is made up of an electronic module and a
measuring element It may switch a solenoid valve, activate an alarm or
establish a control loop
The switching point can be adjusted by means of the three keys located
under the display
The controller housing can be turned by 180°
The controller 8311 can be inserted in a fitting before being mounted on
any type of pipe
The electrical connection is carried out via an EN175301-803 connector
and/or a steerable M12 multipin connector
The controller 8311 uses a piezo-resistive ceramic cell

ENGLISH
ENGLISH
5-pin M12 cable plug, to be wired
5-pin M12 cable plug, moulded on a shielded cable (2 m)
EN175301-803 cable plug (type 2508) with cable gland
EN175301-803 cable plug (type 2509) with NPT 1/2’’ reduction
12-30 VDC NPN and PNP M12 connector 439932 439940 439936
12-30 VDC Relay M12 and EN 175301-803 connectors 439935 439943 439939

ENGLISH
ENGLISH
Pipe diameter any type of pipe with a 1/2‘’ threaded connection piece (G, NPT or Rc)
Medium temperature -20 °C to +100 °C, +100 °C with a max ambient temperature of +40 °C
Measuring range 0-10 bar, standard
0-2, 0-5 bar, 0-20 bar and 0-50 bar on request
Accuracy ±15% of the full scale (full scale = max value of the measuring range)
Repeatability
- typical 025%
- max 1%
Measuring element ceramic cell
Protection rating IP 65 connectors being plugged-in and tightened
Installation class
(overvoltage class) 2
Power supply 12-30 VDC
Current consumption
Version with PNP output max750 mA + consumption of the load, if the PNP output is connected
max 50 mA + consumption of the load, if the PNP output is not connected
Version with relay output max 80 mA, without load
Protection against
polarity reversal yes
Transistor output NPN and PNP, open collector, 700 mA max, NPN output: 0,2-30 VDC and PNP output:
supply voltage (see example in the Annex)
or

ENGLISH
ENGLISH
Relay output 250 VAC, max 3 A or 30 VDC, max 3 A; programmable
Protection against
short-circuits yes for the transistor output
Type of cable recommended shielded, wire section between 014 and 0,5 mm2
NPN/PNP version 5-pin M12 cable plug (not supplied)
Relay version EN175301-803- (supplied) 1) and 5-pin M12- (not supplied) cable plugs
1) EaseOn with connector type 2511 on request
Housing polycarbonate, fiber glass reinforced
Front plate polyester
Parts in contact
with the medium stainless steel 316L (DIN 14404), FKM in the standard versions (EPDM as an option),
ceramic cell (Al2O3)
Ambient temperature 0 °C to +60 °C, max +40 °C if the fluid temperature is near +100 °C
Relative humidity < 80%, non condensated

ENGLISH
ENGLISH
54 22
SW 27
G1/2'' - NPT1/2'' - Rc1/2''
92
18
54
EN 175301-803
30
61
M12
SW 22
40

ENGLISH
ENGLISH

ENGLISH
ENGLISH
Always check the chemical compatibility of the materials the controller is
made of with the products it may be in contact with, for instance: alco-
hols, strong or concentrated acids, aldehydes, bases, esters, aliphatics,
aromatics, ketones, aromatics or halogenated hydrocarbons, oxidizing
agents and chlorinated products For more information, please contact
your Bürkert sales office
The pressure controller 8311 can be inserted in a fitting before being
mounted on any type of pipe
During mounting, follow the instructions given with the fitting
Always replace the cover
in its initial position
Do not tighten the controller
using the housing;
use an appropriate tool
For a G1/2”-version,
ensure the gasket is in
place
ENTER
O
U
T0....9

ENGLISH
ENGLISH
Always ensure the power supply is switched off before working on the
device All the cable plugs must be plugged out Use:
- a shielded cable with an operating temperature > +80 °C
- a high quality voltage supply (filtered and regulated)
1 2
4
3
1
5
2
- To open the plug, unfasten screw [1]
- Remove part [3] from part [2]
- Unscrew cable gland [5]
- Insert cable into part [2] via cable gland
- Wire part [3] (see 433)
- Replace part [3] into part [2], by 90°-steps
- Tighten cable gland [5] Place gasket [4] between the cable plug and
the fixed connector of the controller and plug the 2508 onto the fixed
connector
- Tighten screw [1] to ensure tightness and correct electrical contact
- Loosen threaded ring [1]
- Remove part [2] from the connector
- Wire acc to pin assignment (see 432 or
433)

ENGLISH
ENGLISH
4
5
3
12
0 VDC
V+
(12-30 VDC)
PNP
0 V
V+ V+
IN
0 V
(*)
Sensor Sensor
Receiver
Load
Receiver
Load
PNP transistor output
NPN transistor
output
Output
Output
(*) Functional earth
1 brown
2 white
3 blue
4 black
5 grey
NPN
0 V
V+ V+
IN
0 V
(*)
The controller is fitted with a steerable M12 fixed
connector:
Unfasten counternut Turn the fixed connector to the
right position, but by max 360° to avoid twisting of the
cables inside the housing Fasten counternut using the
appropriate tool while maintening the fixed connector
in the right position

ENGLISH
ENGLISH
1
32
The controller is fitted with a steerable M12 fixed connector:
Unfasten counternut Turn the fixed connector to the right position, but by max 360° to avoid
twisting of the cables inside the housing Fasten counternut using the appropriate tool while
maintening the fixed connector in the right position
When the voltage at the relay terminals is higher than 24 V and the
cable plugs are not correctly plugged-in and tightened, there is a risk to
electrocute yourself
Always check all the cable plugs before powering the device to ensure
the good operating of the device
Common
Not connected
Normally Closed
Normally Open
Not connected
Not connected
4
5
3
12
0 VDC
V+
(12-30 VDC)

ENGLISH
ENGLISH
Keep in mind that the process may be influenced by all the parameter
settings you make Fill-in the table on page 24 with your settings of the
controller
The device has three operating modes:
Display of the measured pressure and the switching thresholds pro-
grammed From the Normal mode, you can access the Calibration and
Simulation modes
Access to the programming of all the parameters (unit, zero adjustment,
K-factor, calibration through the „Teach-in“ feature, output, filter , bar-
graph) From the Calibration mode, you can go back to the Normal Mode
Entering a theoretical pressure value to test the configuration program-
med in the Calibration mode From the Simulation Mode, you can go
back to the Normal mode

ENGLISH
ENGLISH
At the first powering up, the configuration of the controller 8311 is as follows:
Pressure unit: bar
Output: hysteresis
OLO: 0,2 bar
OHI: 1 bar
DEL: 0 s
Filtre: 2
BGLO: 0 bar
BGHI: max value of the measuring range
Extension board: no
To display the measured value and the
configuration (8 characters:
4 numeric et 4 alphanumeric charact)
To modify the digital value (0…9);
To go back to the previous function
To select the character;
To go to the next function
To validate a function;
To validate the entered data
To indicate the status of the
switching output (red LED)

ENGLISH
ENGLISH
+
> 5 s
+
> 5 s
3
1
++
> 5 s
ENTER
ENTER
0......9
0......9
ENTER
0......9
2
0.000
BAR
1.000
O HI
0.200
O LO
Press the keys
simultaneously
of the measured
pressure
NB: When the units flash,
the max value of the pressure
range has been exceeded
the high threshold
value (O HI)
to the previous
function
the low threshold
value (O LO)
the next function
Other manuals for 8311
4
Table of contents
Languages:
Other Bürkert Controllers manuals

Bürkert
Bürkert 2012 User manual

Bürkert
Bürkert eCONTROL 8611 User manual

Bürkert
Bürkert 8690 User manual

Bürkert
Bürkert Type 8605 User manual

Bürkert
Bürkert 8692 User manual

Bürkert
Bürkert TopControl ON/OFF User manual

Bürkert
Bürkert 8619 multiCELL WM AC User manual

Bürkert
Bürkert 0911 User manual

Bürkert
Bürkert 8691 User manual
Popular Controllers manuals by other brands

ACTUATECH
ACTUATECH GD15 instruction manual

Trinamic
Trinamic TMCM-1140 Hardware manual

Flowserve
Flowserve Limitorque MX Safety manual

Siemens
Siemens SIMATIC NET MOBIC T8 Information on the Product

Siemens
Siemens N350E Operating and mounting instructions

Clarke
Clarke CAT190 Operating & maintenance instructions