5: WIRING
1: Strip 0.2 to 0.25 inches (5 to 7 mm)
of wiring insulaon.
2: Connect the wires as indicated.
SHIELD WIRE WARNING: Con-
nect the shield of the power wires
to the earth ground of the central
control system (e.g., chassis,
ground bus bar, etc.).
WARNING: The mains power supply
cable should be of an approved type
based on local regulaons. Connec-
on to the mains power supply
must be made via an approved,
readily-accessible, switched and
fused plug and socket (or as per
local wiring regulaons) which
should be within 10 feet (3 meters)
of the control unit.
CABLE OPENINGS: The metal IP51 controller
housing provides a number of PG7 openings for
cable glands or plugs. Each MGD-100 IP41 transmit-
ter will have a single opening for an M20 cable
gland, as well as an oponal knockout opening.
Each MGD-100 IP66 tranmier has 3 openings
These openings can be used for field wiring, direct
aachment of a sensor or wiring of a remote
sensor. Unused openings must be closed with a
suitable plug and gasket, maintaining the IP or Ex d
rang.
114A Georges Street Lower
Dun Laoghaire • Co Dublin • Ireland
Phone: +353 1 284 6388 • Fax: +353 1 284 6389
NOTE: To make wiring connecons,
you must first open the MGD-100
housing. The enclosure lid of the IP66
housing has four capve screws.
NOTE: Aer wiring is completed,
carefully re-assemble the enclosure
and its components, nong the
keyed ribbon cable and sensor
connectors. Aer installaon is
complete, be sure to refer to the
User Manual (part number 6109-
9000) for detailed instrucons on
registering the sensors and configur-
ing the MGD-100 for proper opera-
on.
Controller PCB
Volt Free
Alarm
Relay
RV1
Mains
Power
Fail Safe Jumper Seng:
OFF
ON
OFF: High Relay Is Energized
On Alarm (Energized on High
Alarm Condion)
ON: High Relay Is Normally
Energized (De-energized on
High Alarm or Mains
Failure Condion)
Transformer
Channel 1 Channel 2
(Oponal)
SENSOR 1
ON OFF
SENSOR 2
ON OFF
FAIL
SAFE
ON
OFF
HIGH
Relay
NC COM NO
MAINS
12V
Fuse 2
Fuse 1
A
u
d
i
b
l
e
A
l
a
r
m
B
u
z
z
e
r
KEY
RED
RED
Chan 1
Alarm LED Chan 2 Alm
LED (Opt.)
GRN
Controller PCB
High Alarm
Relay
(Volt Free)
RV1
SC
SENSOR
Fail Safe Jumper Seng:
OFF
ON
OFF: High Relay Is Energized
On Alarm (Energized on High
Alarm Condion)
ON: High Relay Is Normally
Energized (De-energized on
High Alarm or Mains
Failure Condion)
Transformer
Channel 1 Channel 2
(Oponal)
SENSOR 1
ON OFF
SENSOR 2
ON OFF
FAIL
SAFE
ON
OFF
HIGH
Relay 2
NC COM NO
MAINS
12V
Fuse 2
Fuse 1
A
u
d
i
b
l
e
A
l
a
r
m
B
u
z
z
e
r
LOW
Relay 1
NC COM NO
KEY RESET
RED
RED
YEL
YEL
Chan 1 Alarm LEDs Chan 2 Alm LEDs (Opt.)
GRN
Low Alarm
Relay
(Volt Free)
Mains
Power
RED
RED
RED
RED
RED
RED
Chan 1
Alarm LED
Chan 2
Alarm LED
Chan 3
Alarm LED
Chan 4
Alarm LED
Chan 5
Alarm LED
Chan 6
Alarm LED
GRN
SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 SENSOR 5 SENSOR 6
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
NC COM NO
High Relay
+ 12V -
- SIREN +
PSU KEY
FAIL SAFE
ON
OFF
RV1
To Lid
Ground
Connecon
Base Ground
Connecon
Repeat for sensor
channels 3 through
6 as required.
Relay
Output
Fail Safe
Jumper Seng:
OFF
ON
OFF: High Relay Is
Energized On Alarm
(Energized on High
Alarm Condion)
ON: High Relay Is
Normally Energized
(De-energized on
High Alarm or Mains
Failure Condion)
Sensor Enable
Jumper Sengs:
OFF
ON
OFF: Sensor is
disabled for this
channel
ON: Sensor is
enabled for this
channel
Ensure that connecons 1 to 4
on each sensor connect to their
corresponding numbers on the
terminal block in the main
alarm unit, otherwise the
system will not funcon
correctly and could be
damaged.
Fuse
MAINS
12V
50/60Hz
Fuse
REPLACE FUSE
WITH M205
T2AL250V
Mains
Power
Horn
(12 VDC, 200 mA Max)
Key
Switch
Fuse
MAINS
12V
50/60Hz
Fuse
REPLACE FUSE
WITH M205
T2AL250V
RED
RED
RED
RED
RED
RED
Chan 1
Alarm LEDs
Chan 2
Alarm LEDs
Chan 3
Alarm LEDs
Chan 4
Alarm LEDs
Chan 5
Alarm LEDs
Chan 6
Alarm LEDs
YEL
YEL
YEL
YEL
YEL
YEL
GRN
SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 SENSOR 5 SENSOR 6
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
NC COM NO
High Relay Low Relay Fault Relay
NC COM NO NO COM NC
+ 12V -
- SIREN +
PSU KEY RESET
RV1
To Lid
Ground
Connecon
Base Ground
Connecon
Mains
Power
Horn
(12 VDC, 200 mA Max)
Key
Switch
Push
Buon
Switch
Repeat for sensor
channels 3 through
6 as required.
Ensure that connecons 1 to 4
on each sensor connect to their
corresponding numbers on the
terminal block in the main
alarm unit, otherwise the
system will not funcon
correctly and could be
damaged.
Relay
Outputs
Fail Safe
Jumper Seng:
OFF
ON
OFF: High Relay Is
Energized On Alarm
(Energized on High
Alarm Condion)
ON: High Relay Is
Normally Energized
(De-energized on
High Alarm or Mains
Failure Condion)
Sensor Enable
Jumper Sengs:
OFF
ON
OFF: Sensor is
disabled for this
channel
ON: Sensor is
enabled for this
channel
FAIL SAFE
ON
OFF
2 Channel 1 Alarm 2 Channel 2 Alarm
6 Channel 1 Alarm 6 Channel 2 Alarm
Refer to the User Manual (part number 6109-
9000) at www.MyBacharach.com for detailed
instrucons on accessing the internal components
for wiring.
SC Gas Sensor PCB
IR Gas Sensor PCB
SC
SENSOR
IR Gas Sensor PCB
4-conductor cable (stranded);
500 (152 m) max;
22 AWG; Max 8.8Ω/wire
4-conductor cable (stranded);
500 (152 m) max;
22 AWG; Max 8.8Ω/wire
4-conductor cable (stranded) (6 places max);
500 (152 m) max; 22 AWG; Max 8.8Ω/wire
4-conductor cable (stranded) (6 places max);
500 (152 m) max; 22 AWG; Max 8.8Ω/wire