INSTALLATION
Procedures for installing Recordall Turbo Series meters are essentially the same for all meter sizes. Any special instructions
required for the installation or connection of accessory devices such as AMR/AMI technologies or strainers is provided in the
literature for those devices. Figure 1 shows a recommended meter installation.
Badger Meter Plate Strainer
and Turbo Series Meters
Coupling
Adaptor
Service
Saddle
Shuto
Valve
Test Tee
Minimum of 5 Diameters
of Straight Pipe
Upstream
Valve
(open)
By-pass
(Permanent or
Temporary)
Do
Minimum of 5 Pipe Diameters
Downstream of Turbo Meter
Figure 1: Recommended meter installation
Preinstallation Considerations
Before proceeding any further with the installation, first read the instructions in the paragraphs immediately following to
become familiar with the requirements and procedures involved.
MPORTANTI
The meter must be installed horizontally in the line with the register upright.
• Be sure that the meter flow range and size of the meter coincide with the intended service and demand for water.
THE LIFE OF THE TURBO METER WILL BE CURTAILED IF OPERATED AT FLOW RATES HIGHER THAN SPECIFIED.
• The meters are designed for use in cold water service (up to 120° F or 49° C) within the applicable flow requirements for
Turbo meters. For use with water at higher temperatures, consult Badger Meter Tech Support.
• If solid material is present in the water to be metered, a strainer must be installed in the service piping upstream of the
meter. The strainer, in addition to protecting the meter from debris in the line, minimizes the effect of velocity profile
distortions or turbulence caused by changes in pipe direction or valving resulting in more accurate registration.
• Avoid locating the meter in close quarters. Allow sufficient space to permit access for meter reading, testing,
and maintenance.
• Because of the need to test large meters periodically to verify their performance, it is recommended that a bypass system
be incorporated into the piping arrangement. This will also provide a means of performing periodic clean out and routine
maintenance without interrupting service to the customer. An optional test port is incorporated in the meter housing and
can be used for field accuracy testing.
• The Recordall Turbo Series meter is accuracy and pressure tested prior to shipment, therefore no field adjustments
are required. As turbine performance is directly related to the flow conditions of the water stream entering the
meter, upstream fittings and piping changes can adversely affect flow registration. For valid registration and proper
performance, consider the following installation considerations:
• When installing the meter with a separate plate strainer or integral strainer, a minimum of 5 pipe diameters of
straight, unobstructed pipe is recommended upstream of the meter. For optimum protection and accuracy, this
straight pipe spool piece should be installed between the separate strainer and meter (see Figure 1). A minimum of
10 pipe diameters (minimum of 25 pipe diameters for smallest size) of straight unobstructed pipe is recommended
upstream of a meter installed without a plate strainer. The deletion of a strainer, however, is not recommended.
This allows for dampening of velocity profile distortions caused by elbows, pumps and dirt traps upstream of the
meter. Where spiral flows are created by three dimensional elbows or rotary pumps, additional distance to dampen
the effect is beneficial. If a basket or Y-type strainer is used, place it 5 to 10 pipe diameters upstream of the meter to
dampen velocity profile distortions created by this design.
Installation