SELF-DIAGNOSTICS TESTING:
1. NORMAL OPERATION
When unit is functioning properly with A.C. power supplied, the status indicator will be green.
2. TESTING
The exit performs two types of test, Contingency and Non-Contingency.
The contingency testing includes “Battery Disconnected Mode” and “Lamp Failure Mode”. When the Battery is
disconnected, the indicator would indicate as Red (Steady). When the Lamp fails, the indicator would indicate as Red
(Blinking - three times). The Non-Contingency test is for testing the Battery for its “discharging” and “recharging”
capacity. A 1minute battery discharge test is performed every 30 days to check for the normal operation of the battery
and the unit. Also a full 90 minute discharge this is performed once a year to confirm the same. When the battery is in
discharging mode, the LED indicator would be a flashing Green (Three/Four Pulses). Upon completion of the test and
after 24 hours battery charging (Indicator on Red and Green flashing), the status indicator will return to either Green
(Steady) indicating a properly functioning unit or Red (Double Pulse) to show a battery failure. The following table
shows the status indication.
MANUAL TESTING:
Battery and Lamp test may be manually
initiated by pressing the manual test switch.
Once the test switch is pressed, the unit
would be reset and the date of battery
self-testing would start counting again.
OPERATION:
During and electrical power failure, the
lamps will automatically come on for a
minimum of 90 minutes. To test this unit, the
battery needs to be charged initially for 2
hours before depressing the test switch.
On pressing the test switch, the emergency
lamps will illuminate. When the switch is
released, the lamps will turn off.
LL30 SERIES
INSTALLATION INSTRUCTIONS
800.533.3948 •www.barronltg.com
10070057 Rev 4 - 02/14
CAUTION This equipment is furnished with a low voltage
disconnect circuit to protect the battery from fully
discharging after its useful output has been used. Allow 24
hours recharge time after installation or power failure for
full load testing.
1. Lamp Cover
2. Cover Housing
3. Lamp
4. Base Housing
5. Mounting Bracket
6. Cover Hold Plug
7. Cover Housing Screw
8. Setting Screw
9. Battery
10. Circuit Board
11. Wire Nuts
12. Purple & Yellow
67
8
9
11
10
5
4
12
3
2
1
REACTION AND LED INDICATION
Press test button once (Within 2 seconds) 30-second test: Green light – Single blinking
Press test button 2 times (Within 2 seconds)
15-minute test: Green light – Double blinking
Press test button 3 times (Within 2 seconds)
90-minute test: Green light – Triple blinking
Exit is in Emergency Mode
Lamp Failure Red (Flashing 4 times)
Red and Green (Flashing Alternately)
30 Second Battery Discharging Mode
15 Minute Battery Discharging Mode**
90 Minute Battery Discharging Mode***
* = Happens only after battery discharges once in every 30 days or 1 year.
** = Occurs once in every 30 days.
*** = Occurs once in a year.