
7
Flow Diagram Component Identification
Component Purpose
Solenoid valve Opens to allow water to enter the RO. Closes when the unit is turned
off. It ensures that the disinfectant used in disinfecting the unit remains
inside the instrument until it is turned on again.
Water pressure
gauges
Located before and after the water filter. When the difference between
the two gauge readings is greater than 10 psi, the filter should be
changed.
Filter Contains both a fiber material (5-10 micron) and activated carbon. The
carbon is sufficient for 13 treatments (for the home, about one month) if
the incoming water contains less than 3 ppm chloride ions. For higher
chloride levels and chloramines, additional activated carbon may
be needed.
Heat exchanger Tubing around the pump motor to cool the motor and warm the water.
This is done so the motor can be enclosed in insulation without
overheating and warmer water assists the membrane in producing
quality water.
Water pressure
regulator (20 psi)
Regulates the water pressure to the Procon pump at 20 psi.
Sanitize Luer port Used to inject disinfectant into the RO for sanitizing the machine.
Sanitize check valve Prevents back up of water or disinfectant through the sanitize Luer port.
Water pressure
switch
Set at about 6 psi. Should the incoming pressure drop below this
amount, the Procon pump will be shut off and an alarm will sound.
Thermistor Used to monitor the water temperature. This information is used in
conjunction with the two conductivity cells to determine the total ion
concentration of the recirculating and product water.
Conductivity cells Used to measure the conductance of the recirculating and product
water. This information is combined to yield the display of percent
rejection on the front panel.
Procon pump Pump used in RO to push the water across the membrane. The pump
can produce pressures much higher than the 200 psi which is
necessary in the RO.
RO module Contains the thin film composite (TFC) membrane, which is the heart of
the system.
Test points Plugged holes in the system's flow block, which can be used by service
personnel to test pressures and set the pressure regulators.
Pressure regulator
(200 psi)
Provides the backpressure necessary for the Procon pump to create
the 200 psi required to push water across the membrane.
Flow regulator A restrictor used to limit the flow of water to the drain during normal
function. The drain flow is about 1000mL/min.
Fast rinse valve Opened to create a high flow to drain when rinsing disinfectant from the
system. This reduces the waiting time before the unit can be used.
Check valve
(product line)
Used to prevent incoming or recirculating water from entering the
product line. Because this valve is 1 psi, the output water pressure will
be 21 psi to the dialysis machine.