71930-00001.H
QUICK MOUNT VISUAL INSTRUCTION MANUAL
PR and PKR Actuators
with 3-Way Butterfly Valves
7
2
1
3
4
№
2
NEMA 4X
12 in-lb
Power
Wire separator
4
WIRING DIAGRAMS
Floating Point
PR and PKR Actuators
End Switches
Temp Sensor
VDC / 4 to 20 mA
BACnet
24 to 240 VAC
or
24 to 125 VDC
N
L
Y1
Y2
N
Com
D +
D -
Com
Bacnet D +
D -
Notes:
0˚ to 90˚
default 85˚
41!
of anMeets cULus requirements without the need
electrical ground connection.
5
Only connect common to neg. (-) leg of control circuits.
1
Provide overload protection and disconnect as required.
46
Actuators may be controlled in parallel. Current draw
and input impedance must be observed.
4
Two built-in auxiliary switches (2x SPDT), for end
position indication, interlock control, fan startup, etc.
Universal Power Supply (UP) models can be supplied
with 24 VAC up to 240 VAC, or 24 VDC up to 125 VDC.
Optional: end switch adjustment
On/Off
N
L + Hot
Y1
Y2
1
46
UP
!
Common
Input CCW (open)
Input CW (close)
24 to 240 VAC
or
24 to 125 VDC
N
L
Y
1
Y
2
Common
+ Hot
Input CCW (open)
Input CW (close)
24 to 240 VAC
or
24 to 125 VDC
46
11
UP
!
Disconnect power.
1 Gear disengagement
Open the manual override cover and insert the hand crank.
Manual override is possible.
2Manual override
3Auxiliary switch
4Terminals
indicates the desired switching
position and then remove the crank.
Turn the hand crank until
A
Open the auxiliary switch adjustment cover and properly seat
the hand crank into the actuator. Turn the crank until
B
the arrow points to the vertical line.
Connect continuity tester to S4 + S5 or to S4 + S6.
If the auxiliary switch should switch in the opposite direction,
rotate the hand crank by 180˚.
5LED Display Green
6LED Display Yellow
Off: No power supply or malfunction, On: In operation
Press button: Triggers test run, followed by standard mode.
Off: Standard mode, On: Test run active.
On/Off
N
L
Y1
Y2
N
5
UP
46
24 to 240 VAC
or
24 to 125 VDC
-
+
Y3
U5
Com -
24 VDC Out
Y3 0 - 10 VDC**
U5/MP 0 - 10 VDC
1
**Control type, Direction and Fail position changes can
be made via Belimo Assistant App, i.e. Floating or
4-20mA.