Technical data sheet PRCA-S2-T
Rotary actuator for butterfly valves
• Nominal torque 160 Nm
• Nominal voltage AC 24...240 V /
DC 24...125 V
• Control Open-close, 3-point
• with 2 integrated auxiliary switches
Technical data
Electrical data Nominal voltage AC 24...240 V / DC 24...125 V
Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 19.2...264 V / DC 19.2...137.5 V
Power consumption in operation 20 W
Power consumption in rest position 6 W
Power consumption for wire sizing with 24 V 20 VA / with 230 V 52 VA
Auxiliary switch 2 x SPDT, 1 x 10° / 1 x 0...90° (ex works 85°)
Switching capacity auxiliary switch 1 mA...3 (0.5 inductive) A, AC 250 V
Connection supply / control Terminals 2.5 mm²
Connection auxiliary switch Terminals 2.5 mm²
Parallel operation Yes (note the performance data)
Functional data Torque motor 160 Nm
Manual override with hand crank, can be fixed in any position
Running time motor 35 s / 90°
Motor running time variable 30...120 s
Sound power level motor 68 dB(A)
Position indication Mechanically (integrated)
Safety Protection class IEC/EN II reinforced insulation
Protection class UL II reinforced insulation
Protection class auxiliary switch IEC/EN II reinforced insulation
Degree of protection IEC/EN IP66 + IP67
EMC CE according to 2014/30/EU
Low voltage directive CE according to 2014/35/EU
Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14
Certification UL cULus according to UL 60730-1A, UL 60730-2-
14 and CAN/CSA E60730-1:02
Mode of operation Type 1
Rated impulse voltage supply 4 kV
Rated impulse voltage auxiliary switch 2.5 kV
Control pollution degree 3
Ambient temperature -30...50 °C
Non-operating temperature -40...80 °C
Ambient humidity 95% r.h., non-condensing
Maintenance Maintenance-free
Mechanical data Connection flange F07
Weight Weight 5.8 kg
Safety notes
• This device has been designed for use in stationary heating, ventilation and air
conditioning systems and must not be used outside the specified field of application,
especially in aircraft or in any other airborne means of transport.
• Caution: Power supply voltage!
• Only authorised specialists may carry out installation. All applicable legal or
institutional installation regulations must be complied during installation.
• Apart from the connection box, the device may only be opened at the manufacturer’s
site. It does not contain any parts that can be replaced or repaired by the user.
www.belimo.eu PRCA-S2-T • en-gb • 2016-10-06 • subject to changes 1