manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Evco
  6. •
  7. Controllers
  8. •
  9. Evco EV3143 User manual

Evco EV3143 User manual

EVCOS.p.A.|EV3143|Instructionsheetver.1.1|Code1043143E113|Page1of3|PT28/22
EV3143 Controller with two independent regulators for refrigerated milk storage
units and ice cream batch freezers
EN ENGLISH
- 230 VAC or 115 VAC power supply (according to the model)
- 2 analogue inputs (PTC/NTC)
- door switch/multi-purpose input
- main relay 16 A res. @ 250 VAC
- alarm buzzer
- TTL MODBUS slave port for EVconnect app, EPoCA remote monitoring system or for BMS
- hot or cold mode regulation.
1 MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
- the thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
- ensure that the working conditions are within the limits stated in the TECHNICAL SPEC-
IFICATIONS section
- do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations or
shocks
- in compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be fixed
in such a way as to need the aid of a tool to remove them.
2 ELECTRICAL CONNECTION
N.B.
- use cables of an adequate section for the current running through them
- to reduce any electromagnetic interference, locate the power cables as far away as
possible from the signal cables.
The controller is operated mainly by P10 (default "controller with two independent regulators").
P10 OPERATION PROBE 1 PROBE 2 LOAD 1 LOAD 2 LOAD 3
0
controller with two inde-
pendent regulators regulator
1 regulator
2 regulator
1 regulator
2 alarm
1
controller for refrigerated
milk storage units tank
auxiliary
compres-
sor auxiliary
beater
2
controller for ice cream
batch freezers tank
plate
compres-
sor plate
heaters beater
PRECAUTIONS FOR ELECTRICAL CONNECTION
- if using an electrical or pneumatic screwdriver, adjust the tightening torque
- if the device is moved from a cold to a warm place, humidity may cause condensation
to form inside. Wait for about an hour before switching on the power
- make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS
- disconnect the power supply before carrying out any type of maintenance
- do not use the device as a safety device
- for repairs and for further information, contact the EVCO sales network.
3 FIRST-TIME USE
1. Carry out the installation following the instructions given in the section MEASUREMENTS
AND INSTALLATION.
2. Power up the device as set out in the section ELECTRICAL CONNECTION: an internal test
will start up.
The test normally takes a few seconds; when it is finished the display will switch off.
3. Configure the device as shown in the section Setting configuration parameters.
Recommended configuration parameters for first-time use:
PAR. DEF. PARAMETER MIN... MAX.
SP1 0.0 load 1 setpoint r1... r2
SP2 0.0 load 2 setpoint r12... r13
SP3 0.0 beater setpoint r16... r17
P0 1 type of probe 0 = PTC 1 = NTC
P2 0 temperature measurement unit 0 = °C 1 = °F
P10
0
operating logic
0 = controller with two independent
regulators
1 = controller for refrigerated milk
storage units
2 = controller for ice cream batch
freezers
Then check that the remaining settings are appropriate; see the section CONFIGURATION
PARAMETERS.
4. Disconnect the device from the mains.
5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION, with-
out powering up the device.
6. For the connection in an RS-485 network connect the interface EVIF22TSX or
EVIF23TSX, to use the device with the EPoCA remote monitoring system, connect the
EVIF25TWX module, to use the device with the APP EVconnect connect the interface
EVIF25TBX; see the relevant instruction sheets. If EVIF22TSX or EVIF23TSX is used,
set parameter bLE to 0.
7. Power up the device again.
4 USER INTERFACE AND MAIN FUNCTIONS
4.1 Switching the device on/off
1. If POF = 1 (default), touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("probe 1 temperature" default);
if the display shows an alarm code, see the section ALARMS.
LED ON OFF FLASHING
compressor on
compressor off
- compressor protection in pro-
gress
- setpoint being set
plate heaters on
plate heaters off
setpoint being set
OUT1
regulator 1 on
regulator 1 off
- load 1 protection in progress
- setpoint being set
defrost active
-
-
beater on
beater off
setpoint being set
alarm active and si-
lenced -
alarm active and not silenced
°C/°F
temperature displayed
-
-
OUT2
regulator 2 on
regulator 2 off
- load 2 protection in progress
- setpoint being set
device off
device on
device being switched on/off
When 30 s have elapsed without the keys being pressed, the display will show the “Loc” label
and the keypad will automatically lock.
4.2 Unlocking the keypad
Touch a key for 1 s: the display will show the label “UnL”.
4.3 Quick setting:
- of setpoints (if P9 = 1 or 3)
- beater switch on/off times (if P9 = 2 or 3)
Check that the keypad is not locked.
1. Touch the SET key: the display will show the label “SP1”.
2. Touch the UP or DOWN key within 15 s to set the load 1 setpoint
value within the limits r1 and r2 (default “-50... 50”).
3. Touch the SET key: the display will show the label “SP2”.
4. Touch the UP or DOWN key within 15 s to set the load 2 setpoint
value within the limits r12 and r13 (default “-50... 50”).
5. Touch the SET key: the display will show the label “SP3”.
6. Touch the UP or DOWN key within 15 s to set the beater setpoint
value within the limits r16 and r17 (default “-50... 50”).
7. Touch the SET key: the display will show the label “t0”.
8. Touch the UP or DOWN key within 15 s to set the time the beater
is switched off within the limits 0... 240 min.
9. Touch the SET key: the display will show the label “t1”.
10. Touch the UP or DOWN key within 15 s to set the time the beater
is switched on within the limits 0... 240 min.
11. Touch the SET key (or take no action for 15 s).
Settings are temporary: when the device is switched back on (and after a power failure), it resets
the values SP1, SP2, SP3, t0 and t1.
4.4 Starting up/interrupting batch freezing (if P10 = 2)
Check that the keypad is not locked.
1. Touch the ON/STAND-BY key.
4.5 Manually switching on the beater (if P10 = 1)
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
The beater is switched on for time t1.
4.6 Activating manual defrost (if r5 and/or r19 = 0, default)
Check that the keypad is not locked.
1. Touch the UP key for 4 s.
4.7 Silencing the buzzer (if Pbu = 2 or 3)
Touch a key.
If u4 = 1, the alarm output is also deactivated.
5 OPERATION
5.1 Controller with two independent regulators (P10 = 0, default)
Cold mode regulation regulator 1 (r5 = 0).
Hot mode regulation regulator 1 (r5 = 1).
Cold mode regulation regulator 2 (r10 = 0).
Hot mode regulation regulator 2 (r10 = 1).
5.2 Controller for refrigerated milk storage units (P10 = 1)
Compressor operation.
Beater operation set to t0 and t1 (r14 = 0).
Beater operation set to r19, t0 and t1 if beater setpoint is not reached (r14 = 1).
Cold mode regulation beater (r19 = 0)
Beater operation set to r19, t0 and t1 if beater setpoint is not reached (r14 = 1).
Hot mode regulation (r19 = 1).
5.3 Controller for ice cream batch freezers (P10 = 2)
The batch freezing cycle consists of 4 phases:
- heating
- cooking
- cooling
- conservation.
5.3.1 Heating
The compressor remains off.
Plate heaters operation.
Beater operation.
End of phase.
At the end of the phase the buzzer emits 10 beeps 1 s long.
If there is a power failure during the phase, it starts back up again from the beginning.
5.3.2 Cooking
The compressor remains off.
Plate heaters operation.
EVCOS.p.A.|EV3143|Instructionsheetver.1.1|Code1043143E113|Page2of3|PT28/22
Beater operation.
End of phase.
At the end of the phase the buzzer emits 10 beeps 1 s long.
If there is a power failure during the phase, it starts back up again from the beginning.
5.3.3 Cooling
Compressor operation.
The plate heaters remain off.
Beater operation.
End of phase.
At the end of the phase the buzzer emits 10 beeps 1 s long.
If there is a power failure during the phase:
- the phase starts back up again from the beginning if (tank temperature after the power
failure - tank temperature before the power failure) < PFd
- the cycle starts back up again from the beginning of the heating phase if (tank tempera-
ture after the power failure - tank temperature before the power failure) > PFd.
5.3.4 Conservation
Compressor operation.
The plate heaters remain off.
Beater operation.
End of phase.
If there is a power failure during the phase:
- the phase starts back up again from the beginning if (tank temperature after the power
failure - tank temperature before the power failure) < PFd
- the cycle starts back up again from the beginning of the heating phase if (tank tempera-
ture after the power failure - tank temperature before the power failure) > PFd.
6 ADDITIONAL FUNCTIONS
6.1 Viewing the temperatures detected by the probes
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
Pb1 probe 1 temperature
Pb2 probe 2 temperature
3. Touch the SET key.
4. Touch the ON/STAND-BY key (or take no action for 60 s) to exit
the procedure.
7 SETTINGS
7.1 Setting configuration parameters
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the PAS value (de-
fault “-19”).
4. Touch the SET key (or take no action for 15 s): the display will
show the label “SP1”.
5. Touch the UP or DOWN key to select a parameter.
6. Touch the SET key.
7. Touch the UP or DOWN key within 15 s to set the value.
8. Touch the SET key (or take no action for 15 s).
9. Touch the SET key for 4 s (or take no action for 60 s) to exit the
procedure.
7.2 Restoring factory (default) settings and saving customised settings
N.B.
- check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- saving customised settings overwrites the factory settings.
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the value.
VAL. MEANING
149 value for restoring the factory information (default)
161 value for saving customised settings
4.
Touch the SET key (or take no action for 15 s): the display will
show the label “dEF” (for setting the “149” value) or the label
“MAP” (for setting the “161” value).
5. Touch the SET key.
6. Touch the UP or DOWN key within 15 s to set the value.
VAL. MEANING
1 controller with two independent regulators
2 controller for refrigerated milk storage units
3 controller for ice cream batch freezers
7.
Touch the SET key (or take no action for 15 s): the display will
show “- - -” flashing for 4 s, after which the device will exit the
procedure.
8. Disconnect the device from the power supply.
9. Touch the SET key for 2 s before action 6 to exit the procedure
beforehand.
8 CONFIGURATION PARAMETERS
N.B.
- DEF. 1: default values for P10 = 0
- DEF. 2: default values for P10 = 1
- DEF. 3: default values for P10 = 2
Access to parameter P10 causes the restoration of the default values.
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
SETPOINT MIN... MAX.
1 SP1 0.0 0.0 - - - load 1 setpoint r1... r2
2 SP2 0.0 0.0 - - - load 2 setpoint r7... r8
3 SP3 - - - 0.0 - - - beater setpoint r16... r17
NO.
PAR.
DEF. 1
DEF. 2
DEF. 3
ANALOGUE IN-
PUTS MIN... MAX.
4 CA1 0.0 0.0 0.0 probe 1 offset -25... 25 °C/°F
5 CA2 0.0 0.0 0.0 probe 2 offset -25... 25 °C/°F
6 P0 1 1 1 type of probe 0 = PTC 1 = NTC
7
P1
1
1
1
enable decimal
point °C 0 = no 1 = yes
8
P2
0
0
0
temperature
measurement unit
0 = °C 1 = °F
9
P3
2
2
- - -
probe 1 function
not visible if P10 =
2
0 = disabled
1 = tank probe
2 = regulator 1
3 = condenser probe
10
P4
2
2
- - -
probe 2 function
not visible if P10 =
2
0 = disabled
1 = plate probe
2 = regulator 2
3 = condenser probe
11
P5
0
0
0
value displayed
0 = probe 1 temperature
1 = probe 2 temperature
2 = load 1 setpoint
3 = load 2 setpoint
12
P8
5
5
5
display refresh
time 0... 250 s: 10
13
P9
0
0
0
enable quick set-
tings block
0 = disabled
1 = setpoint
2 = beater on/off times
3 = beater on/off setpoint +
times
14
P10
0
1
2
operating logic
0 = controller with two inde-
pendent regulators
1 = controller for refrigerated
milk storage units
2 = controller for ice cream
batch freezers
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
REGULATION MIN... MAX.
15
r0
2.0
2.0
- - -
load 1 setpoint
differential 1... 15 °C/°F
16
r1
-50
-50
- - -
load 1 minimum
setpoint -99 °C/°F... r2
17
r2
50.0
50.0
- - -
load 1 maximum
setpoint r1... 150 °C/°F
18
r5
0
0
- - -
hot or cold mode
regulation regula-
tor 1
0 = cold mode
1 = hot mode
19
r6
2.0
2.0
- - -
load 2 setpoint
differential 1... 15 °C/°F
20
r7
-50
-50
- - -
load 2 minimum
setpoint -99 °C/°F... r8
21
r8
50.0
50.0
- - -
load 2 maximum
setpoint r7... 150 °C/°F
22
r9
1
1
- - -
enable regulator 2
0 = no 1 = yes
if P10 = 1
23
r10
0
0
- - -
hot or cold mode
regulation regula-
tor 2
0 = cold mode
1 = hot mode
24
r14
- - -
0
- - -
beater mode in
normal operation
0 = parameter set to t0 and
t1
1 = parameter set to r19, t0,
t1 if the beater setpoint
is not reached
25
r15
- - -
0.5
- - -
beater setpoint
differential 1... 15 °C/°F
26
r16
- - -
-50
- - -
beater minimum
setpoint -99 °C/°F... r17
27
r17
- - -
50
- - -
beater maximum
setpoint r16... 150 °C/°F
28
r19
- - -
0
- - -
hot or cold mode
regulation beater 0 = cold mode
1 = hot mode
29
r20
- - -
0
- - -
beater mode in
beater probe
alarm
0 = off
1 = set to t0 and t1
30
r21
- - -
0
- - -
constraint be-
tween beater and
compressor
0 = disabled
1 = on if compressor on and
parameter set to r14
2 = on if compressor off and
parameter set to r14
3 = on if compressor on
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
BEATER MIN... MAX.
31
t0 - - - 3 - - - beater off time 0... 240 min
32
t1 - - - 2 - - - beater on time 0... 240 min
33
t2
- - -
0
- - -
beater off delay
from compressor
off
0... 240 min
34
t3
- - -
10
- - -
minimum beater
on and off time 0... 240 s
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
LOADS MIN... MAX.
35
C0
3
3
3
load 1 on delay
from power-on 0... 240 min
36
C1
5
5
5
delay between
two load 1 switch-
ons
0... 240 min
37
C2
3
3
3
load 1 minimum
off time 0... 240 min
38
C3
0
0
0
load 1 minimum
on time 0... 240 s
39
C4
10
10
- - - load 1 off time in
probe 1 alarm 0... 240 min
if C6 = 2
40
C5
10
10
- - -
load 1 on time in
probe 1 alarm
0... 240 min
if C6 = 2
41
C6
3
3
- - -
load 2 on delay
from power-on
and load 2 mini-
mum off time
0... 240 min
42
C7
0
0
- - -
load 2 minimum
on time 0... 240 s
43
C8
5
5
- - -
delay between
two load 2 switch-
ons
0... 240 min
44
C10
0
0
- - -
load 2 off time in
probe 2 alarm 0... 240 min
if C6 = 2
45
C11
0
0
- - -
load 2 on time in
probe 2 alarm 0... 240 min
if C6 = 2
46
C13
80.0
80.0
- - -
high condensation
signal threshold
not visible if P10 =
2
0... 199 °C/°F
differential = 2 °C/4 °F
47
C14
90.0
90.0
- - -
high condensation
alarm threshold 0... 150 °C/°F
48
C15
60
60
- - -
high condensation
alarm delay 0... 240 s
NO.
PAR.
DEF. 1
DEF. 2
DEF. 3
DEFROSTING (if
r5 = 0) MIN... MAX.
49
d0
8
8
- - -
automatic defrost
interval regulator
1 and regulator 2
0... 99 h
0 = manual only
50
d3
30
30
- - -
defrost duration
regulator 1 0... 99 min
51
d4
0
0
- - -
enable defrost at
power-on 0 = no 1 = yes
52
d5
0
0
- - -
defrost delay from
power-on 0... 99 min
53
d6
2
2
- - -
value displayed
when defrosting
0 = value P5 (if P5 = 0 or 1)
1 = value P5 (if P5 = 0 or 1)
at defrost activation
2 = label dEF
54
d10
30
- - -
- - -
defrost duration
regulator 2 0... 99 min
55
d12
0
- - -
- - -
constraint be-
tween defrost reg-
ulator 1 and de-
frost regulator 2
0 = disabled
1 = regulator defrost is acti-
vated only if defrost of
the other regulator is not
in progress. If it is, it
waits for this to end.
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
ALARMS MIN... MAX.
56
A1
-10.0
-10.0
-10.0
low temperature
alarm threshold
probe 1
-99... 150 °C/°F
57
A2
0
0
0
type of low tem-
perature alarm
probe 1
0 = disabled
1 = relative to load 1 setpoint
2 = absolute
58
A4
10.0
10.0
10.0
high temperature
alarm threshold
probe 1
-99... 150 °C/°F
59
A5
0
0
0
type of high tem-
perature alarm
probe 1
0 = disabled
1 = relative to load 1 setpoint
2 = absolute
60
A6
12
12
12
high temperature
alarm delay probe
1 from power-on
0... 99 minx10
61
A7
15
15
15
high/low tempera-
ture alarm delay
probe 1
0... 240 min
62
A8
15
15
15
high temperature
alarm delay probe
1 after defrosting
regulator 1
0... 240 min
63 A10 - - - - - - - - - unused -
64
A11
-10.0
-10.0
-10.0
low temperature
alarm threshold
probe 2
-99... 150 °C/°F
65
A12
0
0
0
type of low tem-
perature alarm
probe 2
0 = disabled
1 = relative to load 2 setpoint
2 = absolute
66
A14
10.0
10.0
10.0
high temperature
alarm threshold
probe 2
-99... 150 °C/°F
67
A15
0
0
0
type of high tem-
perature alarm
probe 2
0 = disabled
1 = relative to load 2 setpoint
2 = absolute
68
A16
12
12
12
high temperature
alarm delay probe
2 from power-on
0... 99 minx10
69
A17
15
15
15
high/low tempera-
ture alarm delay
probe 2
0... 240 min
70
A18
15
15
15
high temperature
alarm delay probe
2 after defrosting
regulator 2
0... 240 min
71
A19
2.0
2.0
2.0
high/low tempera-
ture alarm reset
differential
1... 15 °C/°F
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
DIGITAL INPUTS MIN... MAX.
72
i2
30
30
30
door switch/multi-
purpose input
alarm signal delay
0... 120 min
73
i3
15
15
15
maximum com-
pressor and
beater off time
with door
switch/multi-pur-
pose input active
0... 120 min
74
i5
3
3
3
door switch/multi-
purpose input
function
0 = disabled
1 = compressor off
2 = beater off
3 = multi-purpose input
alarm
4 = switches device on/off
5 = thermal switch alarm
6 = door open alarm
EVCOS.p.A.|EV3143|Instructionsheetver.1.1|Code1043143E113|Page3of3|PT28/22
75
i6
0
0
0
activation door
switch/multi-pur-
pose input
0 = with contact closed
1 = with contact open
76
i7
0
0
0
door switch/multi-
purpose input
alarm activation
delay
0... 120 min
NO.
PAR.
DEF. 1
DEF. 2
DEF. 3
DIGITAL OUT-
PUTS MIN... MAX.
77
u1
3
0
0
K1 relay configu-
ration
0 = compressor
1 = plate heaters
2 = beater
3 = load 1
4 = load 2
5 = alarm
78
u2
4
4
1
K2 relay configu-
ration as u1
79
u3
5
2
2
K3 relay configu-
ration as u1
80
u4
1
1
1
enable silencing
alarm output 0 = no 1 = yes
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
BATCH FREEZER MIN... MAX.
81
Snd
- - -
- - -
30
threshold for neu-
tral zone regula-
tion during cook-
ing
99... 150 °C/°F
82
d2n - - - - - - 1.0 neutral zone value
0... 99.0 °C/°F
83
r23
- - -
- - -
0.0
minimum plate
setpoint during
batch freezing
heating and cook-
ing
0 °C/°F... r24
84
r24
- - -
- - -
130
maximum plate
setpoint during
batch freezing
heating and cook-
ing
r23... 150 °C/°F
85
r25
- - -
- - -
0.0
minimum tank
setpoint at end of
batch freezing
heating and batch
freezing cooking
setpoint
0 °C/°F... r26
86
r26
- - -
- - -
90.0
maximum tank
setpoint at end of
batch freezing
heating and batch
freezing cooking
setpoint
r25... 150 °C/°F
87
r27
- - -
- - -
0.0
minimum tank
setpoint at end of
batch freezing
cooling and tank
setpoint during
conservation
-2 °C/°F... r28
88
r28
- - -
- - -
130
maximum tank
setpoint at end of
batch freezing
cooling and tank
setpoint during
conservation
r27... 60 °C/°F
89
SA1
- - -
- - -
50.0
tank setpoint for
beater on or
on/off during
batch freezing
-99... 150 °C/°F
differential = 5 °C/10 °F
90
PFd
- - -
- - -
5.0
difference in tank
temperature after
power failure dur-
ing batch freezing
cooling or conser-
vation due to re-
activating heating
1... 25 °C/°F
1
NO.
PAR.
DEF. 1
DEF. 2
DEF. 3
BATCH FREEZING
HEATING MIN... MAX.
91
r1H
- - -
- - -
2.0
plate differential
setpoint during
batch freezing
heating and plate
setpoint during
batch freezing
cooking
1... 25 °C/°F
92
n1H
- - -
- - -
0
hours beater on
during batch
freezing heating
0... 23 h
93
n1n
- - -
- - -
2
minutes beater on
during batch
freezing heating
0... 59 min
94
n1S
- - -
- - -
0
seconds beater on
during batch
freezing heating
0... 59 s
95
F1H
- - -
- - -
0
hours beater off
during batch
freezing heating
0... 23 h
96
F1n
- - -
- - -
2
minutes beater off
during batch
freezing heating
0... 59 min
97
F1S
- - -
- - -
0
seconds beater off
during batch
freezing heating
0... 59 s
2
NO.
PAR.
DEF. 1
DEF. 2
DEF. 3
BATCH FREEZING
COOKING MIN... MAX.
98
SPC
- - -
- - -
30.0
plate setpoint dur-
ing batch freezing
cooking and plate
setpoint during
batch freezing
cooking
r23... r24
99
SU2
- - -
- - -
30.0
tank setpoint at
end of batch
freezing heating
and tank setpoint
during batch
freezing cooking
r25... r26
100
r2H
- - -
- - -
2.0
tank differential
setpoint during
batch freezing
cooking
1... 25 °C/°F
101
C2H
- - -
- - -
1
duration in hours
of batch freezing
cooking
0... 23 h
102
C2n
- - -
- - -
0
duration in
minutes of batch
freezing cooking
0... 59 min
103
C2S
- - -
- - -
0
duration in sec-
onds of batch
freezing cooking
0... 59 s
104
n2H
- - -
- - -
0
hours beater on
during batch
freezing cooking
0... 23 h
105
n2n
- - -
- - -
2
minutes beater on
during batch
freezing cooking
0... 59 min
106
n2S
- - -
- - -
0
seconds beater on
during batch
freezing cooking
0... 59 s
107
F2H
- - -
- - -
0
hours beater off
during batch
freezing cooking
0... 23 h
108
F2n
- - -
- - -
2
minutes beater off
during batch
freezing cooking
0... 59 min
109
F2S
- - -
- - -
0
seconds beater off
during batch
freezing cooking
0... 59 s
3
NO.
PAR.
DEF. 1
DEF. 2
DEF. 3
BATCH FREEZING
COOLING MIN... MAX.
110
SU3
- - -
- - -
30.0
tank setpoint at
end of batch
freezing cooling
and tank setpoint
during batch
freezing conserva-
tion
r27... r28
111
SA3
- - -
- - -
10.0
tank setpoint for
beater on at end
of batch freezing
cooking
0... 25 °C/°F
112
n3H
- - -
- - -
0
hours beater on
during batch
freezing cooling
0... 23 h
113
n3n
- - -
- - -
2
minutes beater on
during batch
freezing cooling
0... 59 min
114
n3S
- - -
- - -
0
seconds beater on
during batch
freezing cooling
0... 59 s
115
F3H
- - -
- - -
0
hours beater off
during batch
freezing cooling
0... 23 h
116
F3n
- - -
- - -
2
minutes beater off
during batch
freezing cooling
0... 59 min
117
F3S
- - -
- - -
0
seconds beater off
during batch
freezing cooling
0... 59 s
4
NO.
PAR.
DEF. 1
DEF. 2
DEF. 3
BATCH FREEZING
CONSERVATION MIN... MAX.
118
r4H
- - -
- - -
2.0
tank differential
setpoint during
batch freezing
conservation
1... 25 °C/°F
119
n4H
- - -
- - -
0
hours beater on
during batch
freezing conserva-
tion
0... 23 h
120
n4n
- - -
- - -
2
minutes beater on
during batch
freezing conserva-
tion
0... 59 min
121
n4S
- - -
- - -
0
seconds beater on
during batch
freezing conserva-
tion
0... 59 s
122
F4H
- - -
- - -
0
hours beater off
during batch
freezing conserva-
tion
0... 23 h
123
F4n
- - -
- - -
2
minutes beater off
during batch
freezing conserva-
tion
0... 59 min
124
F4S
- - -
- - -
0
seconds beater off
during batch
freezing conserva-
tion
0... 59 s
125
F4C
- - -
- - -
0
beater mode dur-
ing batch freezing
conservation
0 = independent on the com-
pressor
1 = on if compressor on, ac-
cording to n4... and F4...
if compressor off
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
SECURITY MIN... MAX.
126
HE4
60
0
0
timeout for lock-
ing the keypad 0... 240 s
127
POF
1
1
1
enable
ON/STAND-BY
key
0 = no 1 = yes
128
PAS -19 -19 -19 password -99... 999
129
PA1 - - - - - - - - - unused -
130
PA2 - - - - - - - - - unused -
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
UNUSED MIN... MAX.
131
Hr0 - - - - - - - - - unused -
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
UNUSED MIN... MAX.
132
rE0
15
15
15
data-logger sam-
pling interval 0... 240 min
133
rE1
1
1
1
recorded temper-
ature
0 = none 1 = probe 1
2 = probe 2
3 = all
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
MODBUS MIN... MAX.
134
LA 247 247 247 MODBUS address 1... 247
135
Lb
2
2
2
MODBUS baud
rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
136
bLE
1
1
1
serial port config-
uration for con-
nectivity
0 = free
1 = forced for EVconnect or
EPoCA
2-99= EPoCA local network
address
NO.
PAR. DEF. 1
DEF. 2
DEF. 3
SECURITY MIN... MAX.
137
bu1
- - -
0
- - -
duration of buzzer
activation when
setpoint reached
0... 240 s
138
Pbu
3
3
2
enable buzzer
0 = disabled
1 = keys only
2 = alarms only
3 = keys and alarms
9 ALARMS
CODE
DE8CRIPTION RESET TO CORRECT
Pr1 probe 1 alarm automatic - check P0
Pr2 probe 2 alarm automatic - check integrity of the probe
- check electrical connection
rtc unused unused unused
AL1
low temperature alarm
probe 1 automatic
check A1 and A2
AH1
high temperature alarm
probe 1 automatic
check A4 and A5
AL2
low temperature alarm
probe 2 automatic
check A11 and A12
AH2
high temperature alarm
probe 2 automatic
check A14 and A15
id door open alarm automatic check i5 and i6
PF
power failure alarm
manual
- touch a key
- check electrical connection
COH high condensation signal automatic check C13
CSd
high condensation alarm
manual
- switch the device off and on
- check C14
iA multi-purpose input alarm automatic check i5 and i6
it
thermal switch alarm
automatic
- switch the device off and on
- check i5 and i6
10 TECHNICAL SPECIFICATIONS
Purpose of the control device: function controller.
Construction of the control device: built-in electronic device.
Housing: black, self-extinguishing.
Category of heat and fire resistance: D.
Measurements:
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x
2 5/16 in) with fixed screw terminal blocks 75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x
3 3/16 in) with plug-in screw terminal blocks
Mounting methods for the control device:
to be fitted to a panel, snap-in brackets pro-
vided
Degree of protection provided by the casing: IP65 (front).
Connection method:
fixed screw terminal blocks for
wires up to 2.5 mm²
plug-in screw terminal blocks
for wires up to 2.5 mm² (on
request)
Micro-MaTch connector
Maximum permitted length for connection cables:
power supply: 10 m (32.8 ft) analogue inputs: 10 m (32.8 ft)
digital inputs: 10 m (32.8 ft) digital outputs: 10 m (32.8 ft).
Operating temperature: from 0 to 55 °C (from 32 to 131 °F).
Storage temperature: from -25 to 70 °C (from -13 to 158 °F).
Operating humidity:
relative humidity without condensate from 10
to 90%.
Pollution status of the control device: 2.
Compliance:
RoHS 2011/65/EC
WEEE 2012/19/EU
REACH (EC) Regulation
no. 1907/2006
EMC 2014/30/EU LVD 2014/35/EU.
Power supply:
230 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 2 VA insulated in EV3143N7
115 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 2 VA insulated in EV3143N5.
Earthing methods for the control device: none.
Rated impulse-withstand voltage: 4 KV.
Over-voltage category: III.
Software class and structure: A.
Analogue inputs:
2 for PTC or NTC probes (probe 1 and probe
2).
PTC probes: Type of sensor: KTY 81-121 (990 @ 25 °C, 77 °F)
Measurement field: from -50 to 150 °C (from -58 to 302 °F)
Resolution: 0.1 °C (1 °F).
NTC probes: Type of sensor: ß3435 (10 K@ 25 °C, 77 °F)
Measurement field: from -40 to 105 °C (from -40 to 221 °F)
Resolution: 0.1 °C (1 °F).
Digital inputs: 1 dry contact (door switch/multi-purpose).
Dry contact: Type of contact: 5 VDC, 1.5 mA
Power supply: none
Protection: none.
Digital outputs: 3 electro-mechanical relays.
K1 relay: SPST, 16 A res. @ 250 VAC
K2 relay: SPDT, 8 A res. @ 250 VAC.
K3 relay: SPST, 5 A res. @ 250 VAC.
Type 1 or Type 2 actions: type 1.
Additional features of Type 1 or Type2 actions:
C.
Displays: custom display, 3 digit, with function icons.
Alarm buzzer: built-in.
Communications ports:
1 TTL MODBUS slave port for EVconnect app,
EPoCA remote monitoring system or for BMS.
N.B.
The device must be disposed of according to local regulations governing the collection
of electrical and electronic equipment.
This document and the solutions contained therein are the intellectual property of EVCO and thus protected
by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the full or partial
reproduction and disclosure of the content other than with the express approval of EVCO. The customer
(manufacturer, installer or end user) assumes all responsibility for the configuration of the device.
EVCO accepts no liability for any possible errors in this document and reserves the right to make any
changes at any time without prejudice to the essential functional and safety features of the equipment.
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
Tel. +39 0437/8422 | Fax +39 0437/83648
email [email protected] | web www.evco.it

Other Evco Controllers manuals

Evco c-pro 3 nano CHIL Instructions for use

Evco

Evco c-pro 3 nano CHIL Instructions for use

Evco EV9300 Series User manual

Evco

Evco EV9300 Series User manual

Evco Vcolor 338 L User guide

Evco

Evco Vcolor 338 L User guide

Evco EV3 Mix User manual

Evco

Evco EV3 Mix User manual

Evco EV3 CHIL User manual

Evco

Evco EV3 CHIL User manual

Evco EVJ 700 User guide

Evco

Evco EVJ 700 User guide

Evco Vcolor 318 M User guide

Evco

Evco Vcolor 318 M User guide

Evco EV3 HP User guide

Evco

Evco EV3 HP User guide

Evco C-pro 3 giga User manual

Evco

Evco C-pro 3 giga User manual

Evco EV3 200 WEB User manual

Evco

Evco EV3 200 WEB User manual

Evco EVK904 User manual

Evco

Evco EVK904 User manual

Evco Vcolor 379 User guide

Evco

Evco Vcolor 379 User guide

Evco EVF User manual

Evco

Evco EVF User manual

Evco EVD MVC Series User manual

Evco

Evco EVD MVC Series User manual

Evco EV3B33N7VXRX04 User manual

Evco

Evco EV3B33N7VXRX04 User manual

Evco EVJ 200 User manual

Evco

Evco EVJ 200 User manual

Evco EVX225 User manual

Evco

Evco EVX225 User manual

Evco EV3S204 User manual

Evco

Evco EV3S204 User manual

Evco EV3 200 WEB User manual

Evco

Evco EV3 200 WEB User manual

Evco c-pro 3 micro AHU User manual

Evco

Evco c-pro 3 micro AHU User manual

Evco EV3143 User manual

Evco

Evco EV3143 User manual

Evco EVJS 800 Series User guide

Evco

Evco EVJS 800 Series User guide

Evco Vcolor 318 M User guide

Evco

Evco Vcolor 318 M User guide

Evco c-pro 3 OEM HRV User guide

Evco

Evco c-pro 3 OEM HRV User guide

Popular Controllers manuals by other brands

PowMr M1210P user manual

PowMr

PowMr M1210P user manual

Intel 845PE Thermal Design Guide

Intel

Intel 845PE Thermal Design Guide

Kübler 573 Series operating instructions

Kübler

Kübler 573 Series operating instructions

Honeywell HR 40 Installation and operating instructions

Honeywell

Honeywell HR 40 Installation and operating instructions

Liscarroll Engineering LE-200 Installation and operating instructions

Liscarroll Engineering

Liscarroll Engineering LE-200 Installation and operating instructions

RYTEC System 4 Installation & owner's manual

RYTEC

RYTEC System 4 Installation & owner's manual

FETtec FC G4 manual

FETtec

FETtec FC G4 manual

K-Tech ET901 Programming guide

K-Tech

K-Tech ET901 Programming guide

TREND IQ422 installation instructions

TREND

TREND IQ422 installation instructions

Smartgen HGM8100A user manual

Smartgen

Smartgen HGM8100A user manual

Siemens RMU7*B series operating instructions

Siemens

Siemens RMU7*B series operating instructions

Veldhuis Digital Engineering NV4C2H Operator's manual

Veldhuis Digital Engineering

Veldhuis Digital Engineering NV4C2H Operator's manual

Carel pCO1 series manual

Carel

Carel pCO1 series manual

Superior Electric POWERSTAT FRM2000 Series instructions

Superior Electric

Superior Electric POWERSTAT FRM2000 Series instructions

Robur Direct Digital Controller Installation, use and programming manual

Robur

Robur Direct Digital Controller Installation, use and programming manual

i2Systems Lightlink LL-105-R Setup guide

i2Systems

i2Systems Lightlink LL-105-R Setup guide

Datapath VSNMicro N600 quick start guide

Datapath

Datapath VSNMicro N600 quick start guide

Kitz ESR Series Operation manual

Kitz

Kitz ESR Series Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.