2
®
WIRING DIAGRAMS
QUICK MOUNT VISUAL INSTRUCTION MANUAL
SGVL/G2/G3 Linkage with LV and SV Series Actuators
BLK
Black
Negro
Noir
Preto
RED
Red
Rojo
Rouge
Vermelho
WHT
White
Blanco
Blanc
Branco
PNK
Pink
Rosado
Rosa
Cor-de ros
ORG
Orange
Anaranjado
Orange
Alaranjado
BLU
Blue
Azul
Bleu
Azul
BRN
Brown
Marron
Brun
Marrom
Non-Spring Return Actuator with -3 Non-Spring Return Actuator with -SR
24 VAC Transformer
Blk (1) Common
Red (2) +
Wht (3) +
Line
Volts
2 3 18
Blk (1) Common
Red (2) +
Wht (3) +
Line
Volts
24 VAC Transformer
2 3 18
Blk (1) Common
Red (2) + Hot
Wht (3) Y1Input, 2 to 10 V
Org (5) U Output, 2 to 10 V
(–)
(+)
Line
Volts
24 VAC Transformer
Control Signal
VDC/mA
318
7
Ω500Ω
1/4 W
On/Off Floating Point VDC / 4 to 20 mA
100 to 240 VAC
Blu (1) Common
Brn (2) +
Wht (3) +
N L1
H L2
Line
Hot
A
2
Blk (1) Common
Brn (2) +
Wht (3) +
A
2
Line N L1
Hot H L2
100 to 240 VAC
Signal
Direction
On/Off Floating Point Selector Switch
Com
Line
Volts
Hot
Controller
24 VAC Transformer (AC only)
Blk (1) Common
Red (2) + Hot
Wht (3)
Y
1
Input
2
24 VAC Transformer (AC only)
Line
Volts
Hot
Controller
Com
Blk (1) Common
Red (2) + Hot
Wht (3)
Y
1
Input
2
Triac Sink Triac Source
Non-Spring Return Actuator with MFT
Blk (1) Common
Red (2) Hot
Wht (3) Y Input
Org (5) U Output
Line
Volts
24 VAC Transformer
2 to 10 VDC
Feedback Signal (+)
(–)
318
Line
Volts
(–)
(+)
24 VAC Transformer
Blk (1) – Common
Red (2) + Hot
Wht (3) Y1Input
Org (5) U Output 2 to 10 V
AB AB
Direction of rotation switch
A
B
Feedback Signal
2 to 10 VDC
210 18
1818
8
912
Notes:
On/Off Floating Point
Blk (1) Common
Red (2) + Hot
Wht (3) Y1Input, 2 to 10 V
Org (5) U Output, 2 to 10 V
(–)
(+)
Line
Volts
24 VAC Transformer
Control Signal
VDC/mA
318
7
Ω500Ω
1/4 W
Functions
0%
50%
100%
Control mode acc. to Y
Min
Mid
Max
Normal
abc
500
Blk (1) Common
Red (2) + Hot
Org (5)
Wht (3) Y1Input, 2 to 10 V
(–)
(+)
Line
Volts
24 VAC Transformer (AC Only)
B
C
A
1/4 W
VDC/mA
Control Signal
18
7
Ω
Ω
VDC / 4 to 20 mA Override Control Min, Mid, Max Postions
Meets cULus requirements without the need of an
electrical ground connection
AActuators with appliance cables are numbered.
2Actuators may be connected in parallel. Power
consumption and input impedance must be observed.
3Actuators may also be powered by 24 VDC.
5Only connect common to neg. (-) leg of control circuits.
7A 500 resistor converts the 4 to 20 mA control signal
to 2 to 10 VDC.
8Control signal may be pulsed from either the Hot
(Source) or Common (Sink) 24 VAC line.
9
Contact closures A & B also can be triacs. A & B
should both be closed for the triac source and open
for triac sink.
10
For triac sink the Common connection from the actuator
must be connected to the Hot connection of the
controller. Position feedback cannot be used with a triac
sink controller. The actuator internal common reference
is not compatible.
12
IN4004 or IN4007 diode. (IN4007 supplied, Belimo Part
number 40155)
18 Actuators with plenum rated cable do not have numbers
on wires; use color codes instead.