
3
ATICS-2-ISO_D00046_02_Q_XXEN/09.2016
ATICS-2…-ISO Quick start
1. Alarm/meas. values
Displays current status messages, alarm messages and measured values
2. Changeover Displays information on the changeover function (number, test)
3. History/Logger Displays logger information 1. History Alarm messages of this device and tests which have been
performed: value and time
2. Data logger Displays the history of measured values: Line 1, Line 2, posi-
tion, load current in the TN system I(3), insulation, trans-
former load
3. Config. Logger Shows the history of the "Settings" menu: value and time
4. Test logger Displays the history of the tests of the changeover switch
carried out
5. Service logger Displays the history of the service activities carried out
4. Settings Various settings for this device 1. Changeover Setting the date and time, system, switching back interlock-
ing function, preferred supply, generator, test and service
interval
2. Voltage Delay times, voltage ranges, hysteresis
3. Current Short-circuit detection
4. IT system Response values insulation, transformer load, temperature,
fault location
5. Relay Mode of operation and relay mode
6. Digital input Mode of operation, function, delay
7. Data logger Modify, overwrite, delete
8. Language Deutsch, English, Francais
9. Interface Setting the BMS bus address of this device.
Allow the settings to be changed via the interface.
Allow a test to be run via interface.
10. Clock Set date format and date and time
11. Password Enable resp. set password for settings and test
12. Service Reserved for settings to be made by authorised Bender
Service personnel.
5. Control Run TEST and RESET for this device 1. TEST
Isometer, changeover, last changeover saved as a test, generator
2. RESET Reset alarm messages, cancel the switching back
interlocking function, change the alarm value for the max.
permissible number of changeover operations performed
and the max. permissible number of operating hours
6. Digital input Display voltage level of the digital input
7. Info Display information on device type and firmware versions
11. Troubleshooting
If a fault occurs,
proceed as follows:
1. Activate manual mode, if necessary.
2. Make a note of what happened prior to the fault: operator
inputs, device error messages, ambient conditions, etc.
3. Keep the device type and device serial number to hand.
4. Speak to Bender Service, describe the type of fault
and quote the three-digit error code.
Fault/message Description Remedy
Failure Line xx
(xx stands for: 1, 2, AV, SV, UPS,
BSV), undervoltage or overvoltage
Voltage is no longer available on Line 1 or Line 2
(Channel 1 = Line 1,
Channel 2 = Line 2)
→Measure voltage on Line xx.
→Check cause.
→Eliminate fault on the system.
→Check the setting for voltage and hysteresis.
Failure line 2 Generator deliveres no voltage within the set time t(GenMax)
Insulation fault IT system has insulation fault →Look for insulation fault.
→Eliminate fault on the system.
Overload Current consumption too high →Check setting for transformer load current.
→Switch off any loads which are not urgently needed.
Overtemperature Temperature on the IT system transformer is too high →
Switch off any loads which are not urgently needed.
CT connection
CT short-circuit
Generator delivers no voltage within the set time. Short circuit or
interruption of the connection cable was detected: Measuring
current transformer STW2 (T4), isolating transformer load, channel 10.
→Check connecting wire of measuring current trans-
former
Main menu Meaning Submenu: Meaning/Setting