4
EXCLUSIVE
b Under  the  safety  valve,  install  a  water  collecting  funnel  with  the 
corresponding discharge in the event of leaks due to the overpressure 
of the heating system. The domestic hot water circuit does not need a 
safety valve, but make sure that the pressure of waterworks does not 
exceed 6 bar. In case of doubts, install a pressure reducer.
b Prior  to  ignition,  make  sure  that  the  boiler  is  designed  to  operate 
with the gas available; this can be checked by the wording on the 
packaging and by the adhesive label indicating the gas type.
b It is very important to highlight that in some cases the ues are under 
pressure, so the joints of the various elements must be airtight.
3.2 Installation regulations
The installation must be carried out by qualied personnel, in compliance 
with the following reference standards:
- UNI 7129-7131
- CEI 64-8.
Always comply with local standards of the Fire Department, the Gas 
Company and with possible municipal dispositions.
POSITION
EXCLUSIVE is a wall-hung boiler for heating and for the production of hot 
water. There are two categories, depending on the type of installation:
- B23P-B53P boiler type - forced open installation, with ue gas discharge 
pipe and pick-up of combustion air from the installation area. If the 
boiler is not installed outdoors, the air intake in the installation area is 
compulsory;
- C13,C13x; C33,C33x; C43,C43x; C53,C53x; C63,C63x; C83,C83x, 
C93,C93x  type  boiler:  appliance  with  airtight  chamber,  with  ue  gas 
discharge pipe and pick-up of combustion air from outside.
 It does not require an air intake point in the installation area.
 This  type  MUST  be  installed using  concentric  pipes,  or  other types  of 
discharge designed for condensing boilers with an airtight chamber.
MINIMUM DISTANCES (g. 6-6a)
To ensure access to the boiler for normal maintenance operations, respect 
the minimum installation clearances envisaged.
For correct appliance positioning, bear in mind that:
- it must not be placed above a cooker or other cooking device
- it is forbidden to leave inammable products in the room where the boiler 
is installed
- heat-sensitive walls (e.g. wooden walls) must be protected with proper 
insulation.
b In case of installation it is ESSENTIAL to provide the necessary 
space for the introduction of the instrument for the combustion 
analysis  check.  In  g.  6a  is  shown  a  sample  drawing  where  the 
distances between boiler and cabinet/niche were obtained using a 
300mm length tool.
 Longer lengths of tools require more space.
3.3 Elimination of air from the heating circuit and 
from the boiler - g. 7
During the initial installation phase, or in the event of extraordinary 
maintenance, you are advised to perform the following sequence of 
operations:
1. Open by two or three turns the automatic relief valve cap (A) and leave 
it open.
2.  Open the system lling tap located on the water unit.
3. Switch on the electricity supply to the boiler, leaving the gas tap turned 
off.
4. Activate a heat request via the room thermostat or the remote control 
panel, so that the 3-way valve goes into heating mode.
5. Activate a request for DHW as follows: open a tap for 30” per minute so 
that the three-way valve cycles from heating to DHW and vice versa for 
about ten times (in this situation, the boiler will go into alarm due to lack 
of gas, therefore reset it whenever this is proposed).
6. Continue the sequence until no more air is felt coming from the air vent 
valve. 
7. Check the system pressure level is correct (the ideal level is 1 bar). 
8. Turn off the system lling tap.
9. Turn on the gas tap and ignite the boiler.
3.4 Positioning the wall-mounted boiler and hydraulic 
connections - g. 8-9 
The boiler comes as standard with a boiler support plate. The position and 
dimension of hydraulic ttings are shown in the detail drawing.
For the assembly, proceed as follows:
- fasten the boiler support plate (F) to the wall and use a spirit level to 
make sure it is perfectly horizontal
- mark the 4 holes (ø 6 mm) envisaged for securing the boiler support 
plate (F)
- make sure that all measurements are exact, then drill the wall using drill 
tips with the diameters indicated above
- x the plate with the built-in template to the wall
- carry out the hydraulic connections.
3.5 Electrical wiring - g. 10-11
Low voltage connections
Carry out the low voltage connections as follows:
- use the external cable box supplied as standard
- unscrew the xing screws of the cover (V)
- carry out the connections as shown in g. 11
b It is recommended to use wires with section not exceeding 
0,5mm2.
b In case of TA or TBT connection, remove the respective shunts 
(g. 12).
- close the box with the screws that were previously removed
- press the two tabs on the sides of the box to place it correctly in its 
housing in the boiler sliding upward within the guide rails
- tighten the safety screw (V1).
b If the low voltage electrical connection box is not connected the 
boiler does not ignite.
High voltage connections
The connection to the mains supply must be made via a separation device 
with an omnipolar opening of at least 3.5 mm (EN 60335/1 - category 3). 
The appliance  works with alternating  current at 230  Volt/50 Hz, and  is in 
compliance with Standard EN 60335-1.
It is obligatory to make the connection with a safe ground/earth, in 
compliance with current directives.
b It is the responsibility of the installer to provide suitable grounding 
for the appliance; the manufacturer will not be liable for any damage 
resulting from an incorrect or absent earth connection.
b It is also recommended to uphold the phase-neutral connection (L-N).
b The earth conductor must be a couple of cm longer than the others.
The boiler can operate with a phase-neutral or phase-phase supply.
For power supplies that are not earthed, it is necessary to use an isolating 
transformer with earth-anchored secondary.
It is forbidden to use gas and/or water pipes to earth electrical appliances. 
Use  the  power  cable  supplied  to  connect  the  boiler  to  the  mains  power 
supply.
If the power cable has to be replaced, use a HAR H05V2V2-F cable, 3 x 
0.75mm2, Ø max external 7 mm.
3.6  Gas connection
The connection of the gas supply must be carried out in compliance with 
current installation standards.
Before carrying out the connection, check that the type of gas is that for 
which the appliance is set up.
3.7  Removing the casing
To access the components inside, remove the casing as indicated below:
- locate and unscrew the 2 screws (A - g. 13) that x the casing to the 
boiler
- by leveraging the xing clips (C - g. 13), unhook the lower part of the 
casing
- lift the casing upwards to release it from the top tabs (B - g. 13), then 
remove it.
WARNING
b The possible damage of the frontal panel involves the replacement 
of the same.
b The noise absorbing panels inside the front and side walls ensure 
the airtight seal for the air supply duct in the installation environment.
b It is therefore ESSENTIAL after the dismantling operations to 
correctly reposition the components so as not to compromise the 
boiler’s operation.
3.8  Flue gas exhaust and combustion air suction
To  evacuate  the  combustion  products,  refer  to  UNI  7129-7131.  Always 
comply with local standards of the Fire Department, the Gas Company and 
with possible municipal dispositions.
The release of combustion products is assured by a centrifugal fan and the 
control board constantly checks that it is operating correctly. It is essential 
for evacuating fumes and adduction boiler combustion air that only original 
pipes are used and that the connection is made correctly as shown in the 
instructions provided with the ue gas accessories.
A single ue can be connected to several appliances provided that every 
appliance is the condensing type.