SAFETY INFORMATION
Before installing the VRF-2000R Remote model, please
read these instructions and familiarize yourself with the
requirements and functions. If any questions or problems
arise during the installation, please contact Bindicator®
Applications at 1-800-778-9242.
The VRF-2000R Remote model must only be installed and
operated as described in this operating instruction. Please
note that other action can cause damage for which
Bindicator®does not take responsibility. If the model is not
installed correctly or used in approved applications,
dangers may arise such as product overflow.
Ensure that all personnel installing, wiring, and calibrating this device are
suitably qualified.
Observe all local and national electrical codes for the wiring of this device.
IMPORTANT!
Either AC or DC power is to be connected to the power input depending on
the model. Consult the nameplate of the unit. Models beginning with
VRF2RE are AC powered units and accept any voltage between 85 VAC
and 265 VAC. Models beginning with VRF2RE are DC powered units and
accept any voltage between 9 VDC and 36 VDC.
IMPORTANT!
An electrical earth ground connection must be made to the housing input
ground screw. See Figure 1 for location. This connection is needed for both
electrical safety and proper operation of the unit. This is required for both
AC and DC units.
External ground wire must be connected to tank wall or top of tank.
VRF-2000R Series
of Variable Radio Frequency
Point Level Sensors
Remote Electronics with Opti-SenseTM
Quick-Start Guide
150 Venture Boulevard
Spartanburg, SC 29306
Phone: (864) 574-8060, Fax: (864) 574-8063
Customer Care: (800) 778-9242
Internet: http://www.bindicator.com
email: sales@bindicator.com
© 2006 All rights reserved.
All data subject to change without notice. VRF 180403 Rev. C 12/06
Please see VRF180003 for complete installation guidelines.
Dimensional and electrical drawings of the VRF-2000R models are available in
various formats from Bindicator's website; www.Bindicator.com
From the home page, click on the link Installation Manuals/VRF180003 to obtain
the applicable drawing.
If access to the internet is not available, please contact Bindicator®Customer
Care Department at 1-800-778-9242 for assistance in obtaining these drawings.
Start-up & Operation
The VRF-2000R Remote model will automatically begin operation when
powered up. It should be initially powered after it is installed in the application
and with material below the probe. When initially powered up, the VRF-2000R
Remote model will automatically begin a 3 second calibration operation. If the
unit is powered on the bench prior to installation, or moved from one installation
to another, recalibration is required. Momentarily press the recalibration
pushbutton. The green calibration indication LED will go off, and after 3 seconds
illuminate to indicate calibration is complete. The VRF-2000R Remote model is
shipped from the manufacturer with the automatic calibration/recalibration fea-
ture enabled. If only manual pushbutton calibration/recalibration is desired, set
SW5 DIP switch position 4 to off.
SW3
Position
Sensitivity
0 .5 pF, Very High
1 1 pF, High
22pF
33pF
4 5 pf, Medium
58pF
6 10 pF, Low
7 15 pF, Very Low
SW5
Position 2
Time Delay Mode
On The delay set on SW4 is applied when material touches the probe
Off There is no delay when material touches the probe
SW5
Position 3
Time Delay Mode
On The delay set on SW4 is applied when material leaves the probe
Off There is no delay when material leaves the probe
Figure 3. Sensitivity Settings
Figure 5. Time Delay Mode Settings
(See Fig. 2)
Figure 1. VRF-2000 Electronics
Failsafe Selection
High Level Failsafe Operation
· DIP Switch SW5 position 1 is on.
· If the electrical power fails, the relay turns off. This indicates material as if the
tank were full.
Low Level Failsafe Operation
· DIP Switch SW5 position 1 is off.
· If the electrical power fails, the relay turns off. This indicates material as if the
tank were empty.
SW4
Position
Time Delay
0 200 mSec
11Sec
22Sec
35Sec
4 10 Sec
5 20 Sec
6 30 Sec
7 60 Sec
Figure 4. Time Delay Settings
(See Fig. 5)
(See Fig. 4) (See Fig. 3)
The output relay contacts are labeled in the un-powered alarm state. The relay is energized
when the VRF-2000R is not alarmed. This status may be opposite that of other Bindicator®
brand units. If the VRF-2000R is replacing an older Model RF unit, connections will need to
be opposite. If a connection was made to NC1 terminal of the RF, connect now to the NO1
terminal of the VRF-2000R. C1 and C2 connections would remain the same.

Other Bindicator Measuring Instrument manuals

Bindicator Pulse Point LP-500ST User manual

Bindicator

Bindicator Pulse Point LP-500ST User manual

Bindicator PRD1000 User manual

Bindicator

Bindicator PRD1000 User manual

Bindicator MP Series User manual

Bindicator

Bindicator MP Series User manual

Bindicator Roto-Bin-Dicator User manual

Bindicator

Bindicator Roto-Bin-Dicator User manual

Bindicator SonoTracker Ultrasonic Liquid Level User manual

Bindicator

Bindicator SonoTracker Ultrasonic Liquid Level User manual

Bindicator Pulse Point II Series User manual

Bindicator

Bindicator Pulse Point II Series User manual

Popular Measuring Instrument manuals by other brands

Kaise SK-7810 instruction manual

Kaise

Kaise SK-7810 instruction manual

HP 3458A Technical manual

HP

HP 3458A Technical manual

PCE Instruments PCE-FM 50N user manual

PCE Instruments

PCE Instruments PCE-FM 50N user manual

Primes PocketMonitor operating manual

Primes

Primes PocketMonitor operating manual

PTX SPM-622 user guide

PTX

PTX SPM-622 user guide

REED R9920 instruction manual

REED

REED R9920 instruction manual

BANTE WXG-4 instruction manual

BANTE

BANTE WXG-4 instruction manual

QED MicroPurge MP25 Operation manual

QED

QED MicroPurge MP25 Operation manual

Kistler 2519A Series instruction manual

Kistler

Kistler 2519A Series instruction manual

Rohde & Schwarz SMBV100B user manual

Rohde & Schwarz

Rohde & Schwarz SMBV100B user manual

Kipp & Zonen PAR lite instruction manual

Kipp & Zonen

Kipp & Zonen PAR lite instruction manual

AOIP THERMYS 150 instruction manual

AOIP

AOIP THERMYS 150 instruction manual

Sekonic FLASH MASTER L-358 quick guide

Sekonic

Sekonic FLASH MASTER L-358 quick guide

HP 1660CS-Series user guide

HP

HP 1660CS-Series user guide

Fluke 971 CAL user manual

Fluke

Fluke 971 CAL user manual

Sper scientific 840006 instruction manual

Sper scientific

Sper scientific 840006 instruction manual

Keeler D-KAT Z Instructions for use

Keeler

Keeler D-KAT Z Instructions for use

TechnipFMC Smith Meter AccuLoad IV Series Installation and maintenance manual

TechnipFMC

TechnipFMC Smith Meter AccuLoad IV Series Installation and maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.