SA021,SA022
SA041 SA042,Check P372 (rated speed), P375 (rated frequency).
SA0 1 The machine data for star connection is entered, but the motor is connected in delta. For star
connection change the motor cable connection. For delta connection check the entered rated
motor values. Repeat Setup.
SA0 2 The machine data for delta connection is entered, but the motor is connected in star. For delta
connection change the motor cable connection. For star connection check the entered rated
motor values. Repeat Setup.
SA0 3 Check motor connection and frequency inverter connections.
Display
SF001 SF022... Check rated motor values in parameters 370...376. Repeat Setup. Check motor cable
connections and frequency inverter connections.
Error messages and w during Setuparnings
!
!
Press ESC to correct a parameter value after an error message or after a warning message.
Press ENT to ignore a warning message. Setup is coninued. It is recommended to check the entered data.
SA001 SA004... Check rated motor values in parameters 370...376. Repeat Setup.
The following causes are possible: The motor cable cross-section is not sufficient. The motor
cable is too long. The motor cable is not connected correctly.
Error messages and warnings during operation
Fault clearance
Display
F0102 F0103,Frequency inverter overloaded. Check load behavior. Check motor parameter settings.
Overtemperature. Check cooling, fan, sensor and ambient temperature.
Low temperature. Check ambient temperature and electrical cabinet heating.
F0400 F0403,Motor temperature too high or sensor defective. Check connection on X12.4. Phase failure. Check
motor and wiring.
F0 00 F0 07... Overloaded, s heck load behavior and
ramps (P420...P423). C
hort circuit or earth fault, motor current or phase failure. C
heck motor and wiring.
F0700 F0706... DC link voltage too high or too low. Check deceleration ramps (P421, P423) and the connected
brake resistor. Check mains voltage.
Power failure or phase failure, voltage break-chopper or motor-chopper too high. Check mains
voltage, mains fuses and circuit.
F0801 F0804,Electronics voltage (24 V) too high or too low. Check wiring of control terminals.
F1100 F1110... Maximum frequency achieved. Check control signals and settings. Check deceleration ramps
(P421, P423) and the connected brake resistor.
F1310 Minimum output current. Check motor and wiring.
F1401 Reference value signal on input X12.3 faulty, check signal.
F1407 Overcurrent on input X12.3, check signal.
Overtemperature. Check cooling, fan and ambient temperature.
A0008 A0010,
A0080 Max. motor temperature reached, check motor and sensor.
A0001 A0004... Frequency inverter overloaded. Check load behavior. Check motor parameters and application
parameters.
A0100 Mains phase failure, check mains fuses and supply cable.
A0400 Limit frequency reached; output frequency is limited.
A0800 Input signal at X12.3 is too low. Increase the value.
F1408 Overcurrent on input X12.4, check signal.
A1000 Input signal at X12.4 is too low. Increase the value.
A4000 DC link voltage has reached the type-specific minimum.
!Press ESC to hide an error message. It it displayed again after 10 seconds.
Press STOP to acknowledge an error message or a warning message. Remove the fault.!
F0200 F0300...
10
Fault clearance
Error messages
Warnings
Error messages
Warnings
GB