Bradley S19-324D1 User manual

Installation
P.O. Box 309
Menomonee Falls, WI 53052 USA
800 BRADLEY (800 272 3539)
+1 262 251 6000
bradleycorp.com
215-1848 Rev. G: ECO 20-05-028
© 2020 Bradley
Page 1 of 10 6/11/2020
S19-324D1
Class I, Division 1, Groups C & D
Explosion Proof
Emergency Signaling System
Table of Contents
Pre-Installation Information.................................... 2-3
Assembly of Components..........................................4
Install the Flow Switch and Mount Signaling Assembly
...5
Connect Signaling Assembly to Flow Switch.............6
Attach Beacon and Area Lights.................................6
Complete Electrical Supply Connections...................6
Conduit Seals ............................................................6
Test the Signaling System .........................................7
Maintenance ..............................................................7
Remote Sensing Option.............................................7
Servicing of Lights .....................................................8
Troubleshooting..........................................................8
Service Parts ....................................................... 9-10

2
S19-324D1 Installation
6/11/2020 Bradley • 215-1848 Rev. G: ECO 20-05-028
WARNING
Power supplied to the unit should be between 90-264VAC, 50-60 Hz, 15 amp branch circuit with a
dedicated circuit breaker or fuse and should not supply power to any other device. Compliance
and conformity to local codes and ordinances is the responsibility of the installer.
Do not use this safety equipment in a location that does not match its hazardous location rating.
Verify the appropriate ratings prior to installation.
When making electrical connections be sure to follow all lockout–tagout safety procedures.
Flush the water supply lines before beginning installation and after installation is complete. Test
the unit for leaks and adequate water flow. Main water supply should be “ON” at all times unless
system is being serviced. Provisions shall be made to prevent unauthorized shutoff.
CAUTION
Supply the unit with clean, potable water.
NOTICE
Before installing this product, ensure that there are adequate clearances around the product and
activation of the product does not interfere with other products or obstructions.
It is recommended that all water supply and electrical connections be made at temperatures above
freezing. Failure to do so may result in major product and/or property damage.
Constant power supply to safety equipment is necessary for it to function.
Avoid cleaners containing organic solvents, alcohols and hydrocarbons. Rinse with potable water
after cleaning.

3
Installation S19-324D1
Bradley • 215-1848 Rev. G: ECO 20-05-028 6/11/2020
IMPORTANT
The installation and location of all safety drench showers, eye and eye/face washes must comply
with the requirements of ANSI/ISEA Z358.1.
Read this installation manual completely to ensure proper installation, then file it with the owner
or maintenance department. Compliance and conformity to local codes and ordinances is the
responsibility of the installer.
Separate parts from packaging and make sure all parts are accounted for before discarding any
packaging material. If any parts are missing, do not begin installation until you obtain the missing
parts.
Installation and maintenance of this system must be completed by a qualified plumber and
electrician according to the information contained in this installation manual and in compliance
with all national and local codes.
The ANSI/ISEA Z358.1 standard requires an uninterrupted supply of flushing fluid. Bradley
plumbed emergency fixtures require a minimum of 30 PSI (0.21MPa) flowing pressure.
Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable
flushing fluid supply is present and any sediment build up in the supply line is cleared. Inspect
safety equipment monthly to address any maintenance issues ensuring the equipment is in good
operating condition and that there are no signs of wear.
Perform functional test upon relocation of safety equipment.
Workers who may come in contact with potentially hazardous materials should be trained
regarding the placement and proper operation of emergency equipment per ANSI/ISEA Z358.1.
For questions regarding the operation or installation of this product, visit www.bradleycorp.com or
call 800-BRADLEY (272.3539).
Product warranties and parts information may also be found under ”Products” on our web site at
bradleycorp.com.
Supplies Required
• Teflon tape or pipe sealant
• Black, white and green AWG 18 minimum (14 AWG maximum) wire to connect signaling system to electric
power supply, use copper wire only
• 3/4" hubs and fittings for electrical wiring (all customer supplied hubs and fittings must match the electrical
rating of the enclosures)

4
S19-324D1 Installation
6/11/2020 Bradley • 215-1848 Rev. G: ECO 20-05-028
S19-324D1 Components
Signal Light
Area Light
56-3/4"
(1439mm)
8-3/4"
(224mm) 20-1/2"
(519mm)
Beacon Light
14-1/2"
(369mm)
¾" NPT Hub,
Plugged
Brass
Sensor
Body
Brass
Adapter
and Tee
2-7/8"
(73mm)
1-5/8"
(41mm)
NEMA 4X
Junction Box
and Cover
Electrical Quick
Disconnect Male
3-13/16"
(97mm)
5-5/16"
(135mm)
Red
Blue
Black
Remote
Sensing
13-1/8"
(334mm)
System is prewired. Installer
connects ONLY ground black
and white wires.
Horn
Pendant
Mount
Pendant
Mount
1/2" (eyewash)
or 1¼" (drench
shower) NPT Inlet
and Outlet
2-3/8" (60mm) for
eyewash or
3-9/16" (91mm) for
drench shower

5
Installation S19-324D1
Bradley • 215-1848 Rev. G: ECO 20-05-028 6/11/2020
1Install the Flow Switch and Mount Signaling Assembly
The flow switch will attach to the mounted alarm via a 6, 12 or 50 foot waterproof cable.
Keep the location for mounting the alarm in mind when choosing the flow switch location.
AChoose a location for mounting the
flow switch in a horizontal run of the
water supply line.
B
Mount the flow switch assembly in
the water supply line.
• The switch body must be in the
vertical position with the water
pipe horizontal.
• The water flow must be in the
direction marked by the arrow on
the flow switch body.
• Use teflon tape or pipe sealant
(supplied by installer) on all water
pipe connections.
C
Choose a location for mounting the
alarm. For best visibility, the signaling
system should be mounted at least 7'
above ground level.
• The signaling system may be
mounted directly to the drench
shower piping using the supplied
U-bolts and nuts.
• The signaling system can also be
bolted to a flat surface such as
a wall (hardware for this type of
installation is NOT supplied). NOTICE! If the water supply line will be exposed to
temperatures at or below freezing, the inlet supply
must be freeze-protected 6 inches above the flow
switch tee (freeze protection by others).
16" (406mm)
min. ceiling
clearance
To 1" Water
Supply
Flow Switch
1¼" to 1"
Reducing
Bushing
required
Piping supplied by
installer (must be
minimum 6 inches
from any fittings)
Flow Switch
optional location
(recommended
location for brass
flow switch is
inside of wall)
To 1¼" Water
Supply
Recommended Location
for Flow Switch
Piping supplied
by installer
(must be
minimum 6
inches from any
fittings)
Flow Switch
Clearances Needed
1/2" Piping
supplied by
installer (must be a
minimum 3 inches
from any fittings)
If multi-tone horn option is selected, it must be mounted
separately following horn manufacturer's instructions.
Mounting hardware is supplied by installer.

6
S19-324D1 Installation
6/11/2020 Bradley • 215-1848 Rev. G: ECO 20-05-028
2Connect Signaling Assembly to Flow Switch
4Complete electrical supply connections
WARNING To prevent personal injury and damage to the components, follow all manufacturer's
warnings and instructions when performing any maintenance or installation of
components used in this emergency signaling system.
ARemove the access cover by rotating
the cover counterclockwise.
B
Run provided electric power conduit
and hubs into an unused 3/4" conduit
port of the control box. Connect the
provided wires in the conduit to the
floating terminal block per the wiring
schematic. Compliance and conformity to local codes and
ordinances is the responsibility of the installer.
D
Once the connections are made,
close the access cover by rotating
clockwise and sealing the control
box.
The cable may be cut to any length required.
A
Wire the flow switch to the control
box with one of the provided cables
and conduit hubs supplied per
the wiring schematic. Refer to the
instruction manual supplied with the
conduit hubs for proper installation.
5Conduit Seals
A
Unit is provided with sealing
compound and conduit seals.
Seals must be filled by installer
prior to powering the unit per seal
manufacturer's instructions.
To prevent water condensation from dripping onto
the flow switch, make sure the cable is not taut.
See wiring diagram and schematic
included in documentation packet.
Seal
Seal
Seal
Seal
3Attach Beacon and Area Lights (if applicable)
AIf unit is ordered with optional area
and beacon lights, remove lights
from their individual boxes. B
Screw beacon and/or area light
onto pendant mount in appropriate
location. Make sure light is securely
screwed to pendant mount.
CPlug any remaining holes with plugs
provided.
Do not exceed 14 AWG wire.

7
Installation S19-324D1
Bradley • 215-1848 Rev. G: ECO 20-05-028 6/11/2020
4Test the Signaling System
Testing the signaling assembly for the first time using the drench shower may expose the flow switch to
an unnecessary water hammer since the downstream piping may be empty of water. The flow switch is
designed to withstand such a water hammer, but using the smaller eyewash flow is recommended.
A
Apply power to the alarm branch
circuit. The alarm should remain in
the OFF position and the beacon and
area light illuminate (if applicable).
The signal light will not illuminate.
B
Open the eyewash valve. The horn
should sound and the signal light
flash shortly after water flows from
the system. If there is the optional
beacon light, this beacon light will
turn off once the fixture is activated
(the signal light will stay on, flashing).
The area light will always stay on.
C
If present, use the auto reset on/
off switch to silence the horn during
a flow event. Toggling the switch to
silence mode will shut off the horn
but allow the signal light to keep
flashing. All units can be silenced by
deactivating the flow.
D
Shut off the eyewash flow valve. The
signal light should stop flashing and
the beacon light (if applicable) will
turn back on at a steady state.
ERepeat steps A through D, this time
using the drench shower only.
Discontinuing the flow will automatically
reset the silence feature.
The signaling system is designed to work properly
even if both the eyewash and drench shower are
used simultaneously. The signaling system will
continue to operate so long as either the eyewash
or drench shower is still in use.
Signaling System Maintenance
The Bradley Emergency Signaling System is designed to be virtually maintenance free. An occasional damp cloth
wiping of the clear dust cover is all that is needed to ensure maximum visual attention-getting ability.
Remote Sensing Option
Flow Switch Capability (see supplied wiring diagram)
If remote sensing is wanted, remove the pipe plug from the back of the junction box. Connect the extra black
wire (common to both switch arrangements) and the blue wire (normally open switch arrangement) or red wire
(normally closed switch arrangement) to your application per local electrical codes. The switch is rated at 5 amps
at 125/250VAC and is isolated from the contacts used by the signaling station. The customer supplied connections
should be of a type equal to or greater than the junction box's rating to maintain the integrity of the system.
Control Box Capability (see supplied wiring diagram)
The control box is supplied with 2 sets of double pole double throw relay contacts which change state with flow.
These contacts can be externally powered or powered by the 24VDC un-switched outputs; combined load cannot
exceed 770mA when internal DC power is used. If contacts are externally powered, the contacts are rated for a
maximum 160 volts at 5 amps.

8
S19-324D1 Installation
6/11/2020 Bradley • 215-1848 Rev. G: ECO 20-05-028
Servicing of Lights
S19-324D1 LED Arrays (Type 4X)
ADe-power the control box by
observing standard lock-out tag-out
practices.
B
Unscrew the light needing
replacement from the pendant
mount. Refer to light manufacturer's
instructions for servicing. Replace
with appropriate LED array color light
fixture.
COnce light is replaced, re-attach
repaired light to pendant mount.
D
Check that the signaling station is
functioning properly once the power
is restored by activating the fixture
attached to the signaling station.
Troubleshooting
Problem Cause Solution
The signal light and horn (if
applicable) does not operate
when water flows.
No power to the signal station. Check that the circuit breaker or fuse is supplying power to the
signal station
Component failure. Check the two 3 Amp 24VDC fuses on the print circuit board in
the signal station enclosure.
No input power. Check that there is 24VDC being supplied from the power supply
mounted on the print circuit board in the signal station enclosure.
Water flowing in wrong
direction for flow switch body.
Verify that the direction of the water flow corresponds to the arrow
on the flow switch body.
Insufficient water flow. Check that water flow is sufficient (2.4 gallons per minute is
required).
Installation error. Check all electrical connections, including power supply at the
quick-connect cable, from the signal station to the flow switch.
Horn sounds and signal light
does not light.
Component failure. Check light connections and filament in the light.
Area light does not operate. No power to the signal station. Check that the circuit breaker or fuse is supplying power to the
signal station
Component failure. Check the two 3 Amp 24VDC fuses on the print circuit board in the
signal station enclosure.
No input power. Check that there is 24VDC being supplied from the power supply
mounted on the print circuit board in the signal station enclosure.
Component failure. Check light connections and filament in the light.
Beacon light does not
operate. (This light should
turn off when the signal light
turns on and back on when
the signal light turns off.)
Fixture in use. Make sure that the flow switch contacts are open (horn and/or
signal light are not ON).
Power disconnected in error. Check that the circuit breaker or fuse is supplying power to the
signal station.
Component failure. Check the 3 Amp 24VDC fuses on the print circuit board in the
signal station enclosure.
No input power. Check that there is 24VDC being supplied from the power supply
mounted on the print circuit board in the signal station enclosure.
Component failure. Check light connections and filament in the light.

9
Installation S19-324D1
Bradley • 215-1848 Rev. G: ECO 20-05-028 6/11/2020
S19-324D1 Service Parts
30
32
31
32
33
34
37
34
3876
84 62
34
33
34
20 38 77 63
61
41
43
32
33
34
39 36
34
37
34
36
33
34
2
1
60 64 65
38
84
36 81
80
61
62
3
84

10
S19-324D1 Installation
6/11/2020 Bradley • 215-1848 Rev. G: ECO 20-05-028
Item Part No. Qty. Description
1 S90-568 1 Sub Assy, Signaling Station
2
269-1593A24
1
Signal Light, Exp. Div1, 24VDC, Amber
2
269-1593R24
1
Signal Light, Exp. Div1, 24VDC, Red
3 269-1306B 1 Horn, Exp. C1D1, 24VDC
20
269-1593C24
1Area Light, C1D1, White**
20
269-1593R24
1Area Light, C1D1, Red**
30
269-1593G24
1Beacon Light, C1D1, Green**
30
269-1593B24
1Beacon Light, C1D1, Blue**
31 269-1780 1 Conduit Coupling
32 269-1316 3 Condiut Nipple, 3/4 x 6
33
269-1596
1-4 Fitting, Seal*
34 269-1582 8 Conduit Nipple, 3/4 x 2
36 269-1294 4 Plug, Conduit, 3/4
37 269-1549 2 Elbow-Street 3/4"
38 269-1308 4 Conduit Connector
39 269-2142 1 Elbow, 90, 3/4, Conduit
41 261-144 1 Selector Switch, Class 1 Div 1 & 2
42 114-310 1 Nameplate
43 255-070 1 Enclosure, Class 1 Div 1 & 2
60 140-1159 1 Plate MN, Surface Mount
60 140-1157 1 Plate PM, Pipe Mount
60 S70-176 1 Mounting Plate, Heat Trace
Item Part No. Qty. Description
61 160-514 5 Screw, 3/8-16 x 1.0 BTNCA
62 161-157 5 Nut, 3/8-16 Hex Jam
63 140-1158 1 Bracket, Alarm, J-Box
64 269-594 2 U-Bolt, SST
65 161-065 4 Nut, 3/8-16 SST
76 269-1588 1 Conduit, Flexible, 3 ft.
77 S90-643 1 Conduit, Flexible, 6 ft.
77 S90-644 1 Conduit, Flexible, 12 ft.
77 S90-645 1 Conduit, Flexible, 50 ft.
80 269-1421 1 Flowswitch, 1-1/4" T-DPDT, Brass
Tee and Body
80
269-1421SS
1Flowswitch, 1-1/4" T-DPDT, SS
Tee and Body, CSA Listed
80 269-1522 1 Flowswitch, 1/2", T-DPDT
80
269-1522SS
1Flowswitch, 1/2" T-DPDT, SS Tee
and Body, CSA Listed
81 269-1312 1 NEMA 4X Box, Conduit Outlet
81 255-078 1 NEMA 4X Stainless Steel,
Conduit Outlet
84
269-518
3Reducing Bushing
97
269-1935
1Sealing Compound-A 3-3
Item 97 ships lose.
*Requires sealing compound if replaced. One sealing compound will fill two seal fittings.
**Re-program per manufacturer's instructions to be steady state light if ordered for
service.
S19-324D1 Service Parts
This manual suits for next models
2
Table of contents
Other Bradley Security System manuals