BRIDEX Rudolf R-DPA96 A User manual

BRIDEX Singapore Pte., Ltd
R-DPA96 A/AN
DDIIGGIITTAALL PPOOWWEERR AAAALLYYSSEERR
R-DPA96A
Instruction Manual

2RUDOLF - Ref. : 876 583 A
DANGER AND WARNING ____________________________________________________4
PRELIMINARY OPERATIONS _________________________________________________4
PRESENTATION _____________________________________________________________5
INSTALLATION ______________________________________________________________5
PROGRAMMING ____________________________________________________________9
OPERATION _______________________________________________________________24
CONNECTION TEST FUNCTION ____________________________________________29
ASSISTANCE ______________________________________________________________32
TEC NICAL C ARACTERISTICS ____________________________________________33
GLOSSARY OF ABBREVIATIONS ____________________________________________35
Main Module
MAI CO TE TS
PRELIMINARY OPERATIONS ________________________________________________ 36
PRESENTATION ___________________________________________________________ 36
INSTALLATION_____________________________________________________________ 37
PROGRAMMING___________________________________________________________ 38
TEC NICAL C ARACTERISTICS ____________________________________________ 42
GLOSSARY OF ABBREVIATIONS_____________________________________________42
Module 1
kWh - kvarh - kVAh
PRELIMINARY OPERATIONS ________________________________________________55
GENERAL INFORMATION______________________________________________56
INSTALLATION_____________________________________________________________57
CONNECTION ________________________________________________________57
PROGRAMMING ___________________________________________________________58
COMMUNICATION ADDRESS __________________________________________59
COMMUNICATION SPEED _____________________________________________59
COMMUNICATION PARITY ____________________________________________60
COMMUNICATION STOP BIT __________________________________________60
COMMUNICATION _________________________________________________________61
T E STANDARD COMMUNICATIONS FRAME____________________________61
LIST OF PARAMETERS TO BE DISPLAYED ______________________________62
Table of values with allocated current and voltage winf-ding ratios on 2 words____________62
Address available with the Monitoring or Control/Command option______________________63
Instant value display _______________________________________________________________64
Table of values without allocated current and voltage winding ratios on 1 word ___________65
Alarm event log ___________________________________________________________________81
Table of current and voltage harmonics ______________________________________________82
Option recognition table____________________________________________________________85
Module 2
kWh - kvarh - kVAh
Harmonics
Module 3
RS485 - JBUS/MODBUS
PRELIMINARY OPERATIONS ________________________________________________ 45
PRESENTATION ___________________________________________________________ 45
INSTALLATION _____________________________________________________________46
PROGRAMMING___________________________________________________________ 47
OPERATION _______________________________________________________________ 51
TEC NICAL C ARACTERISTICS ____________________________________________ 52
GLOSSARY OF ABBREVIATIONS_____________________________________________52

3
RUDOLF - Ref. : 876 583 A
LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED_________________86
RESET TO ZERO: ENERGY METERS AND MAX. VALUES _________________95
SAVED COMMAND ___________________________________________________96
PULSE METERS VALUES ______________________________________________96
DATE AND OUR SETTINGS___________________________________________97
LAST 10 ALARMS EVENT LOG _________________________________________97
LAST 10 VOLTAGE DIPS EVENT LOG / SAG ____________________________111
LAST 10 VOLTAGE SURGE EVENT LOG / SWELL _______________________116
MINIMUM AND MAXIMUM INSTANTANEOUS VALUES___________________121
LAST 10 VOLTAGE CUT-OFFS EVENT LOG / SAG _______________________125
MEAN POWER EVENT LOG___________________________________________127
MEAN VOLTAGE EVENT LOG _________________________________________127
MEAN FREQUENCY EVENT LOG ______________________________________127
TEC NICAL C ARACTERISTICS ___________________________________________128
GLOSSARY OF ABBREVIATIONS ___________________________________________128
Module 3
RS485 - JBUS/MODBUS
Module 4
Outputs 0/4 - 20mA
Module 5
2Inputs / 2 outputs
Module 3+6
Profibus
Module 7
Memory
PRELIMINARY OPERATIONS _______________________________________________ 131
PRESENTATION __________________________________________________________ 131
INSTALLATION ___________________________________________________________ 132
PROGRAMMING__________________________________________________________ 133
TEC NICAL C ARACTERISTICS ___________________________________________ 138
GLOSSARY OF ABBREVIATIONS____________________________________________138
PRELIMINARY OPERATIONS _______________________________________________ 141
PRESENTATION __________________________________________________________ 141
INSTALLATION ___________________________________________________________ 142
PROGRAMMING__________________________________________________________ 144
OPERATION ______________________________________________________________ 150
TEC NICAL C ARACTERISTICS ___________________________________________ 151
GLOSSARY OF ABBREVIATIONS____________________________________________151
PLEASE CONSULT US
PRELIMINARY OPERATIONS _______________________________________________ 153
PRESENTATION __________________________________________________________ 154
INSTALLATION ___________________________________________________________ 155
PROGRAMMING__________________________________________________________ 156
OPERATION ______________________________________________________________ 168
TEC NICAL C ARACTERISTICS ___________________________________________ 169
GLOSSARY OF ABBREVIATIONS____________________________________________168

4RUDOLF - Ref. : 876 583 A
R-DPA96 A/AN
PREMI ARY OPERATIO SDA GER A D WAR I G
This equipment must be mounted only by professionals.
The manufacturer shall not be held responsible for
failure to comply with the instructions in this manual.
Risk of electrocution,
burns or explosion
• the device must be installed and serviced only by
qualied personnel
• prior to any work on or in the device, isolate the
voltage inputs and auxiliary power supplies and
short-circuit the secondary winding of all current
transfromers (PTI RUDOLF)
• always use an appropriate voltage detection device
to conrm the absence of voltage
• put all mechanisms, door and covers back in
place before energising the device
• always supply the device with the correct rated
voltage
Failure to take these precautions could cause
serious injuries.
Risk of damaging device
Chek the following :
• the voltage of the auxiliary power
• the frequency of the distribution system (50 or
60 z)
• the maximum voltage across the voltage-input
terminals, (V1, V2, V3 and VN) 700 V AC phase-to-
phase or 400 V AC phase-to-neutral
• a maximum current of 20 A on the current-input
terminals (I1, I2 and I3)
For personnel and product safety please read the
contents of these operating instructions carefully
before connecting.
Check the following points as soon as you receive
the R-DPA96 A/AN package:
• the packing is in good condition,
• the product has not been damaged during tran-
sit,
• the product reference number conforms to your
order,
• the package contains the product tted with a
pull-out terminal block,
• operating instructions.

5
RUDOLF - Ref. : 876 583 A
I STALLATIO
RECOMMA DATIO S
• avoid proximity to systems which generate electroma-
gnetic interference,
• avoid vibrations with accelerations in excess of 1 g for
frequencies below 60 z.
92
+ 0,8
-
0,0
92
+ 0,8
-
0,0
96
96
60 20
40
40
R-DPA96 A/AN 586 A
CUT-OUT DIAGRAMM
MOU TI G
R-DPA96 A/AN 584 A
8
1
10
9
3
4
2
5
6
7
R-DPA96A
1. Key-pad with 6 dual-function keys (display or pro-
gramming)
2. Backlit LCD display
3. Phase
4. Values
5. Unit
6. Activity indicator on the communication bus
7. Energy metering indication
8. our meter and energy display
9. Alarm relay 1
10. Alarm relay 2
PRESE TATIO
R-DPA96 A/AN 587 A
R-DPA96 A/AN

6RUDOLF - Ref. : 876 583 A
R-DPA96 A/AN
I STALLATIO
The maximum coupling torque for each screw is 0.4
Nm.
Each CT’s secondary winding must be short-circuited
when disconnecting the R-DPA96 A/AN is can be
done automatically using one of Socomec’s cata-
logue products: the PTI. Please contact us for further
information.
S2 S1 S2 S1 S2S1
I2 I3I1
V1 V2 V3 VN
1
2
S2 S1 S2 S1 S2S1
I2 I3I1
In
V1V2V3VN
1
S1 S2
2
R-DPA96 A/AN 286 CR-DPA96 A/AN 453 B
CO ECTIO
R-DPA96 A
R-DPA96 AN
Aux.: 110 … 400 V AC
120 … 350 V DC
12 … 48 V DC
Fus.: 0.5 A gG / BS 88 2A gG / 0.5 A class CC
OPTIO AL MODULES
The R-DPA96 A/AN can be tted with optional
modules:
- JBUS/MODBUS communication;
ref: R-MODULE 3:
RS485 JBUS/MODBUS serial port in RTU mode with
a speed from 2400 to 38400 baud. (User manual ref:
CDR 27 028)
- PROFIBUS-DP Communication;
ref: R-MODULE 3+6:
RS485 PROFIBUS-DP serial port with a speed from
9,600 baud to 1.5 Mbaud. (User manual ref: CDR 18
021)
- Pulse outputs; ref: R-MODULE 1:
2 pulse outputs connected to the metering of energy
in kWh, kvarh and KVAh (User manual ref: 876 584)
- Harmonic and pulse outputs; ref: R-MODULE 2:
2 pulse outputs connected to the metering of energy
in kWh, kvarh and KVAh. Analysis of the harmonic
spectrum in current and voltage in rows and in
phases up to row 25 (User manual ref: 876 585
- Analogue outputs; ref: R-MODULE 4:
2 analogue outputs 4/20 mA or 0/20 mA congurable
for current, voltage, power and power factor. 2
modules can be installed, a maximum of 4 outputs
(User manual ref: 876 586)
- Inputs/Outputs; ref: R-MODULE 5:
2 outputs allocated for alarms, for voltage, current,
power, power factor and T D, or remote control.
2 inputs for the metering of pulses or controlling posi-
tion (User manual ref: 876 587).
- Storage capability; ref: R-MODULE 7:
Storage capability for storing mean active and reacti-
ve power, minimum and maximum instantaneous
values, the last 10 alarms, troughs/overvoltages and
power cuts according to EN50160 (User manual ref:
876 588).
R-DPA96 A/AN 343 A
1
2

7
R-DPA96 A/AN
RUDOLF - Ref. : 876 583 A
L1
(
R)
L2
(
S)
L3
(
T)
S2 S1 S2 S1 S2S1
I2 I3I1
V1V2V3 VN AUX
P1
S1
P1
S1
2
1
2
R-DPA96 A/AN 278
U BALA CED THREE-PHASE ETWORK (3NBL)
The solution with 2 CTs with the 2nd and 3rd phase
current calculated via vectoral summation, results in
an 0.5% reduction in phase accuracy.
P1
S1
P1
S1
L1
(
R)
L2
(
S)
L3
(
T)
P1
S1
S2 S1 S2 S1 S2S1
I2 I3I1
V1V2V3 VN AUX
2
1
2
R-DPA96 A/AN
L1
(
R)
L2
(
S)
L3
(
T)
S2 S1 S2 S1 S2S1
I2 I3I1
V1V2V3 VN AUX
P1
S1
P1
S1
2
2
1
R-DPA96 A/AN
N
P1
S1
P1
S1
L1
(
R)
L2
(
S)
L3
(
T)
P1
S1
S2 S1 S2 S1 S2S1
I2 I3I1
V1V2V3 VN AUXS1S2
In
2
1
2
R-DPA96 A/AN 272
U BALA CED THREE-PHASE ETWORK (4NBL)
N
P1
S1
P1
S1
L1 (R)
L2 (S)
L3 (T)
P1
S1
S2 S1 S2 S1 S2S1
I2 I3I1
V1V2V3 VN AUX
2
1
2
R-DPA96 A/AN
Aux.: 110 … 400 V AC
120 … 350 V DC
12 … 48 V DC
Fus.: 0.5 A gG / BS 88 2A gG / 0.5 A class CC
1
2
Aux.: 110 … 400 V AC
120 … 350 V DC
12 … 48 V DC
Fus.: 0.5 A gG / BS 88 2A gG / 0.5 A class CC
1
2
I STALLATIO

8RUDOLF - Ref. : 876 583 A
R-DPA96 A/AN
I STALLATIO
BALA CED THREE-PHASE ETWORK (3BL/4BL)
The solution using one CT, with the 3rd phase current
calculated via vectoral summation, results in an 0.5%
reduction in phase accuracy.
P1
S1
L1
(
R)
L2
(
S)
L3
(
T)
S2 S1 S2 S1 S2S1
I2 I3I1
V1V2V3 VN AUX
2
1
2
R-DPA96 A/AN
P1
S1
L1 (R)
L2 (S)
L3 (T)
N
S2 S1 S2 S1 S2S1
I2 I3I1
V1V2V3 VN AUX
2
1
2
R-DPA96 A/AN
P1
S1
L1
(
R)
L2
(
S)
S2 S1 S2 S1 S2S1
I2 I3I1
V1V2V3 VN AUX
2
1
2
N
P1
S1
L1
(
R)
S2 S1 S2 S1 S2S1
I2 I3I1
V1V2V3 VN AUX
2
1
2
R-DPA96 A/AN
R-DPA96 A/AN 284 D
TWO-PHASE ETWORK (2BL)
SI GLE-PHASE ETWORK (1BL)
AAA
aaa
L1 (R)
L2 (S)
L3 (T)
V1 V2 V3 VN AUX
1
2
R-DPA96 A/AN
VOLTAGE TRA SFORMER
Aux.: 110 … 400 V AC
120 … 350 V DC
12 … 48 V DC
Fus.: 0.5 A gG / BS 88 2A gG / 0.5 A class CC
1
2
Aux.: 110 … 400 V AC
120 … 350 V DC
12 … 48 V DC
Fus.: 0.5 A gG / BS 88 2A gG / 0.5 A class CC
1
2
Aux.: 110 … 400 V AC
120 … 350 V DC
12 … 48 V DC
Fus.: 0.5 A gG / BS 88 2A gG / 0.5 A class CC
1
2
Aux.: 110 … 400 V AC
120 … 350 V DC
12 … 48 V DC
1

9
RUDOLF - Ref. : 876 583 A
x 1
x 1
x 1
confirm
x 1
3 sec
ACCES TO PROGRAMMI G MODE
COde 100
R-DPA96 A/AN
PROGRAMMI G

10 RUDOLF - Ref. : 876 583 A
R-DPA96 A/AN
PROGRAMMI G
ETWORK (Example : NET = 3NBL)
x 1
x 1(1BL)
x 2 (2BL)
x 3 (3BL)
x 4 (3NBL)
x 5 (4BL)
x 6 (4 NBL)
x 1
confirm

11
R-DPA96 A/AN
RUDOLF - Ref. : 876 583 A
CURRE T TRA SFORMERS (Example : CT = 1500/ 5A)
x 2
x 1
x 1
confirm
PROGRAMMI G

12 RUDOLF - Ref. : 876 583 A
R-DPA96 A/AN
PROGRAMMI G
x 2
x 1
x 1
confirm
EUTRAL CURRE T TRA SFORMER DPA96 AN (Example : Ct In = 1500 / 5A)

13
R-DPA96 A/AN
RUDOLF - Ref. : 876 583 A
VOLTAGE TRA SFOMERS (Example : Vt = YES)
x 1
x 1
x 1
confirm
PROGRAMMI G

14 RUDOLF - Ref. : 876 583 A
R-DPA96 A/AN
PROGRAMMI G
VOLTAGE TRA SFORMER PRIMARY (Example: PR = 20 000 V)
x 2
x 2
x 2
x 1
x 1
confirm

15
R-DPA96 A/AN
RUDOLF - Ref. : 876 583 A
VOLTAGE TRA SFORMER SECO DARY (Example : SE = 110 V)
x 1
x 1 (110)
x 2 (115)
x 3 (120)
x 4 (173)
x 5 (190)
x 6 (60)
x 7 (100)
x 1
confirm
PROGRAMMI G

16 RUDOLF - Ref. : 876 583 A
R-DPA96 A/AN
PROGRAMMI G
I TEGRATIO TIME (Example : tIME 4I = 20 min)
x 1
x 1 (20 min)
x 2 (30 min)
x 3 (60 min)
x 4 (2 sec)
x 5 (10 sec)
x 6 (5 min)
x 7 (8 min)
x 8 (10 min)
x 9 (15 min)
x 1
confirm

17
R-DPA96 A/AN
RUDOLF - Ref. : 876 583 A
VOLTAGE I TEGRATIO (Example : tIME U/V = 20 min)
x 1
x 1 (20 min)
x 2 (30 min)
x 3 (60 min)
x 4 (10 sec)
x 5 (5 min)
x 6 (8 min)
x 7 (10 min)
x 8 (15 min)
x 1
confirm
PROGRAMMI G

18 RUDOLF - Ref. : 876 583 A
R-DPA96 A/AN
PROGRAMMI G
FREQUE CY I TEGRATIO (Example : tIME F = 20 min)
x 1
x 1 (20 min)
x 2 (30 min)
x 3 (60 min)
x 4 (10 sec)
x 5 (5 min)
x 6 (8 min)
x 7 (10 min)
x 8 (15 min)
x 1
confirm

19
R-DPA96 A/AN
RUDOLF - Ref. : 876 583 A
I TEGRATIO ACTIVE TIME POWERS (Example : tIME P/Q/S = 20 min)
x 1
x 1 (20 min)
x 2 (30 min)
x 3 (60 min)
x 4 (10 sec)
x 5 (5 min)
x 6 (8 min)
x 7 (10 min)
x 8 (15 min)
x 1
confirm
PROGRAMMI G

20 RUDOLF - Ref. : 876 583 A
R-DPA96 A/AN
PROGRAMMI G
x 1
x 1 (MAX P+)
x 2 (MAX P-)
x 3 (MAX Q+)
x 4 (MAX Q-)
x 5 (MAX S)
x 6 (HOUR)
x 7 (EA+)
x 8 (ER+)
x 9 (ES)
x 10 (EA-)
x 11 (ER-)
x 12 (MAX 4I)
x 13 (MAX U)
x 14 (MAX V)
x 15 (MAX F)
x 1
x 1
x 1
confirm
RESET TO ZERO (Example : rSET = Ea)
This manual suits for next models
1
Table of contents
Popular Measuring Instrument manuals by other brands

National Instruments
National Instruments NI 5102 Getting started guide

LIMIT
LIMIT CDN-BT operating manual

jacarta
jacarta interSeptor Quick installation guide

PCB Piezotronics
PCB Piezotronics IMI SENSORS 66103PPZ1 Installation and operating manual

Baltech
Baltech VP-3410 Operation manual

LaserLiner
LaserLiner SensoLite 410 quick start guide