C-TEC AlarmSense CFP702-2 Instruction Manual

LPCB APPROVED
CFP 2/4/8 ZONE
FIRE ALARM
CONTROL PANEL
CFP702-2 (2 Zone)CFP702-2 (2 Zone)
CFP704-2 (4 Zone)
CFP708-2 (8 Zone)
installation &
maintenance
manual
Approved Document No. DFU7002020 Rev 4

CONTENTS
EN54 Compliance Statement.............................................................................................................. 3
Basic Overview & Key Features ......................................................................................................... 3
Important Notes .................................................................................................................................. 4
The Fire Panel Enclosure .................................................................................................................... 5
First Fix.......... .......................................................................................................................................6
Cable types and limitations............................................................................................................................. 6
Mains wiring..................................................................................................................................................... 6
Planning the cable layout in the panel.......................................................................................................... 6
Fixing the base onto a wall ............................................................................................................................ 7
AlarmSense™ zone circuit wiring .................................................................................................................. 7
Typical conventional sounder circuit wiring ................................................................................................. 8
Important sounder loading and distribution information .......................................................................... 8
Typical auxiliary input wiring ......................................................................................................................... 8
Typical auxiliary output wiring ...................................................................................................................... 9
Second Fix ......................................................................................................................................... 10
Connecting the panel .................................................................................................................................... 10
Installing the Power Supply PCB................................................................................................................... 10
Connecting the Mains.................................................................................................................................... 10
Connecting the standby batteries ................................................................................................................ 10
Installing the Main Control PCB.................................................................................................................... 12
Connecting the zone circuits and conventional sounder circuits............................................................... 13
Connecting the auxiliary inputs, auxiliary outputs and relay outputs....................................................... 13
Programming the Panel ................................................................................................................... 14
An overview of the panel’s controls ............................................................................................................ 14
Engineer functions......................................................................................................................................... 14
Accessing the engineer controls ................................................................................................................... 16
Programming coincidence, non-latching zones, delays, test, sounder status ...................................... 16-17
Fault Diagnosis ................................................................................................................................. 18
Fault indications ............................................................................................................................................ 18
Zone faults...................................................................................................................................................... 19
Power supply faults........................................................................................................................................ 19
System faults .................................................................................................................................................. 21
Repeater faults............................................................................................................................................... 22
Conventional sounder faults......................................................................................................................... 22
Remote output faults .................................................................................................................................... 22
Maintenance ..................................................................................................................................... 22
Standby Battery Calculation Guide ................................................................................................. 23
Technical Specification ...................................................................................................................... 24
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 2 of 24
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
Errors & Omissions Excepted. The manufacturer of this product operates a policy of continuous improvement and reserves the right to alter product
specifications at its discretion and without prior notice. All of the instructions covered in this manual have been carefully checked prior to publication.
However, no responsibility can be accepted by the manufacturer for any inaccuracies or for any misinterpretation of an instruction or guidance note.
Manufacturer: Computionics Limited (C-TEC), Challenge Way, Martland Park, Wigan, Lancashire WN5 0LD. www.c-tec.com
Niederlassung Deutschland: C-TEC Germany Limited, Virchowstr. 32, D-33332 Gϋtersloh. www.c-tec-germany.de

BASIC OVERVIEW & KEY FEATURES
The fire alarm panel is designed for use with fire and security systems and includes the following features:
•Two, four or eight AlarmSense™ zone circuits (dependent on the model purchased);
The design of the panel’s zone circuits allows AlarmSense™ detectors, manual call points and sounders to be
fitted across the same two zone wires (conventional panels typically use four wires, two for the detectors/
call points and two for the sounders). In many installations it is more cost-effective to install a two wire
system rather than a conventional four wire system due to savings in cabling and installation labour.
It should be noted that no other type of device is compatible with the zone circuits except AlarmSense™
detectors, AlarmSense™ manual call points and AlarmSense™ sounders.
•Four conventional sounder circuits (designed for use with non-AlarmSense™ sounders);
•A flush or surface mountable plastic lid and enclosure;
•A wide range of secure user functions (as detailed in the separate User Manual/Log Book) including the
ability to disable/enable a large number of system functions, as specified in EN54;
•Keypad and keyswitch entry to authorised user controls (access level 2);
•A wide range of engineering functions, including:
Selectable zone delay facility
Non-latching zones facility. Note: This function is non-compliant with EN54-2.
Coincidence (double-knock) facility. Note: This function is non-compliant with EN54-2.
Zone test facility
Programming silenced sounders to resound, or not resound, when a new zone is in alarm
Programming zone circuits to have sounders fitted or not fitted
Comprehensive fault diagnostic facilities
•The following optional EN54 Part 2 features:
Output(s) to fire alarm devices {Clause 7.8}. Four conventional sounder circuits are provided to drive
external alarm sounders.
Delays to outputs {Clause 7.11}. A delay facility (selectable on a zone by zone basis) is provided to delay
the alarm sounders, remote fire and/or auxiliary outputs.
Test condition {Clause 10.0}. A zone test facility is provided.
•The following features that are not required by EN54 Part 2:
Reset output (RESET) open collector output which provides a signal to reset any part of the fire alarm
system (if required) whilst the panel is being reset.
Remote output (REM) open collector output and Auxiliary fire relay output (AUX) which provide a signal
to any part of the fire alarm system that needs to be activated during a fire alarm condition.
Two (non-latching) auxiliary input connections; ‘class change’ and ‘alert’.
•A Fault relay output (FAULT).
Important Note: It is possible for the panel to determine if an AlarmSense™ manual call point, or an
AlarmSense™ detector has triggered a zone into alarm. This allows the system to be optionally set up so
that, if required, the activation of a manual call point will override delays and coincidence.
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 3 of 24
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
EN54 COMPLIANCE STATEMENT
This fire alarm panel is fully compliant with the requirements of EN54 Part 2 (Fire
detection and fire alarm systems, control and indicating equipment) and EN54 Part 4 (Fire
detection and fire alarm systems, power supply equipment) and is certified as meeting
these standards by the Loss Prevention Certification Board (LPCB) - unless stated.
Please note, some of the engineering functions provided on the panel go
beyond the scope of EN54 Part 2. A caution symbol (left) is used to indicate
where such a function is non-compliant with EN54-2.
DO NOT affix the LPCB approval label (supplied) to the front of the panel if it
has been configured to operate in a way that would make it non-compliant
with the requirements of EN54-2.
Read these instructions thoroughly before installation and operation
General Warning Sign Danger Electrical Hazard
Symbols
176b
2831
13
2831-CPR-F0386

IMPORTANT NOTES
THIS EQUIPMENT MUST BE INSTALLED AND MAINTAINED BY A SUITABLY SKILLED AND
TECHNICALLY COMPETENT PERSON. THIS EQUIPMENT IS A PIECE OF CLASS 1 PERMANENTLY
CONNECTED EQUIPMENT AND MUST BE EARTHED.
Items supplied with this panel
•Installation & Maintenance Manual (i.e. this manual).
Explains how to install, commission and maintain the fire alarm control panel.
This manual MUST NOT be left accessible to the user.
•User Manual / Log Book.
Gives detailed operational information, some of which will need to be referenced by the
installation engineer when setting up the panel. Sections of the user manual must be completed
by the engineer before system handover.
•Torx key, for unfastening / securing the panel lid.
•Electrical accessory pack, containing the following items:
8 x 0.47μF 50V capacitors
4 x 6K8 0.25W resistors
1 x Mains fuse
1 x battery connection kit
2 x nylon cable ties (for securing the batteries into the panel enclosure)
1 x LPCB approval label (see EN54 Compliance Statement, page 3 for details).
System design
Fire alarm system design is beyond the scope of this document. A basic understanding of fire alarm system
components and their use is assumed.
We strongly recommend that a suitably qualified and competent person is consulted in connection with the
design of the fire alarm system and that the system is commissioned and serviced in accordance with the laid
down specification and national standards. The fire officer concerned with the property should be contacted
at an early stage in case he/she has any special requirements.
We recommend you read BS 5839 Part 1: Fire detection and fire alarm systems for buildings - code of
practice for system design, installation, commissioning and maintenance, available at your local reference
library or from the BSI. Other national standards of installation should be referenced and adhered to where
applicable.
Equipment guarantee
This equipment is not guaranteed unless the complete system is installed and commissioned in accordance
with the laid down national standards by an approved and competent person or organisation.
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 4 of 24
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
This product has been manufactured in conformance with the requirements of all
applicable EU Council Directives.

THE FIRE PANEL ENCLOSURE
The panel is supplied with a plastic detachable lid, a plastic back box and a minimum of two separate PCBs.
The relative location of these PCBs is indicated in figure 1 below.
The panel can be surface or semi-flush mounted. It must be installed indoors, positioned to avoid accidental
damage, and not subject to conditions likely to affect its performance, e.g. dust, conductive or corrosive
gases or liquids, nor subject to temperatures, input voltages and electrical loads outside the stated operating
range. It should be sited at a height where it is easily accessible and in a prominent position within the
building. Ideally, the indicators on the front of the enclosure should be at eye level and the ambient light
level should allow the status of the indicators to be clearly seen.
Typical locations for the panel are in the entrance foyer/hallway of a building at ground floor level (the first
and most obvious point of contact for emergency services) or a security office that is likely to be permanently
manned.
Removing the lid and base PCBs
To protect the electronics from damage and to expose the base mounting holes, the panel’s lid and PCBs
should be removed prior to first fix installation.
Anti-static handling guidelines
Please ensure that the following electro-static handling precautions are taken immediately
prior to handling the panel’s PCBs or any other static-sensitive components:
Before handling any static-sensitive items, operators should rid themselves of any personal electro-static
charge by momentarily touching any sound connection to safety earth, e.g. a radiator.
Always handle PCBs by their sides and avoid touching the legs of any components.
PCBs should be stored in a clean, dry place which is free from vibration, dust and excessive heat. Retaining
the PCBs in a suitable cardboard box will also guard them against mechanical damage.
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 5 of 24
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
Figure 1 : Location of the panel’s base PCBs and removal details
1. Take the fire alarm panel out of its box and undo the two lid screws using the Torx key provided.
Remove the lid to expose the Main Control PCB (the Power supply PCB is located underneath).
2. Carefully remove the five retaining screws on the Main Control PCB and slide the PCB up and over the
mounting pillars, taking care not to damage any of the components.
3. Disconnect the telecoms-style connecting cable at PL1 on the Power Supply PCB, making sure that the
cable remains connected to the reverse of the Main Control PCB to prevent it being misplaced. Care
should be taken when detaching this connector to depress the locking tab to prevent damage.
4. Pull the Power Supply’s earth distribution strap off the spade connector at the base earth distribution post.
5. Carefully remove the three retaining screws on the Power Supply PCB and slide the PCB up and over
the mounting pillars, again taking care not to damage any of the components.
MAIN CONTROL PCB
POWER SUPPLY PCB
Leave this end of the connector cable connected
to SK2 on the reverse of the Main Control PCB
push tab
and gently
lift cable
PL1
PL1

FIRST FIX
All system wiring should be installed to meet BS 5839 Part 1 and BS 7671 (Wiring Regulations).
Other national standards of installation should be used where applicable.
Cable types and limitations
Consult Clause 26 of BS 5839 Part 1: Fire detection and fire alarm systems for buildings - code of practice
for system design, installation, commissioning and maintenance, for detailed information on cables,
wiring and other interconnections.
To comply with EMC (Electro Magnetic Compatibility) regulations and to reduce the risk of electrical
interference in the system wiring, we recommend the use of fire-resistant screened cables throughout
the installation. Cables such as FP200, Firetuff™, Firecel™ and MICC may be acceptable provided they are
properly terminated at the fire panel and meet national standards/the system specification as applicable.
Correct cable glanding is essential and due regard should be made to any system specifications which
demand a certain cable type.
Mains wiring
All wiring should be installed in accordance with the current edition of the IEE Wiring Regs. (BS 7671),
or relevant national standards. The requirement for the Mains supply to the panel is fixed wiring (no
less than 1mm2and no greater than 2.5mm2), either using 3-core cable, or a suitable three conductor
system fed from an isolating switched fused spur at 3 A, or a 6 A Type B circuit breaker to IEC/EN 60898-1.
The Mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post.
Hint! As an alternative to a switched
fused spur, a double-pole isolating
switch (S), with 3mm air gaps on
the contacts & switching L & N
only, may be used in the Mains feed from
the Main Distribution Board (A) to the
Panel (C), providing it meets the appropriate
wiring regulations (see drawing right).
Do not drill any additional holes
for cable entry in this shaded area.
This is where the PCBs and
backup batteries will be located.
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 6 of 24
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
Planning the cable layout in the panel
The zone circuit and conventional sounder circuit cabling is classed as extra low voltage and should be
segregated away from Mains voltages. Careful planning is needed to ensure this, see figure 2 (below) for
guidance. Drill centre points are provided in the panel base to aid drilling tools. Cut out suitable holes in the
panel using a hole saw directed by a pilot bit in the centre of the hole saw. Always ensure that if a hole is
cut out it is filled with a good quality strain relief, cable gland. Any unused holes must be securely blanked off.
Figure 2 : Location of centre points for hole removal
A
S
C
≥1.0 mm2<2.5 mm2
These four drill centre
points are for incoming
Mains cable only
Holes should be cut
out using a hole saw
with a pilot bit.

Fixing the base onto a wall
Using the five mounting holes provided (see figure 3 below), fix the base securely onto a vertical wall, ≤2m
mounting height. The mounting holes are suitable for use with No.8-10, or 4-5mm countersunk screws.
Assess the condition and construction of the wall and use suitable screw fixings for the in-service weight of
the product. Any dust or swarf created during the fixing process must be kept out of the fire alarm panel
and care must be taken not to damage any wiring or components.
Figure 3 : Internal view of the back box with PCBs removed / side view for flush mounting
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 7 of 24
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
AlarmSense™zone circuit wiring
Depending on the model purchased, two, four or eight AlarmSense™ zone circuit connections are available
on the fire alarm panel. A recommended maximum of 25 devices can be fitted on each circuit which may
include AlarmSense™ detectors, AlarmSense™ manual call points or AlarmSense™ sounders. These can be
mixed in any order. Only AlarmSense™ devices can be used on the zone circuits.
Note: Any AlarmSense™ sounders fitted must be locked to their base or non-removable. If AlarmSense™
sounders are not fitted on a populated zone circuit then this must be programmed into the panel using the
Sounder Status function (see Page 17 for details).
Also, there are limitations on the number of sounders which can be used (please refer to page 8 for
important advice on sounder loading and distribution).
Figure 4 : Typical zone circuit wiring
Connect an end-of-line (EOL) capacitor (provided in the panel ’s accessory pack) across the terminals of the
last device on each circuit to allow the wiring to be monitored. Unused zone circuits must also have an EOL
capacitor fitted at the panel terminals.
Note that an open circuit fault on zone circuit wiring will stop some or all of the detectors, manual call
points and sounders operating, and a short circuit will stop all devices operating.
For more specific device wiring information, refer to the instructions provided with the AlarmSense™
devices used.
The wiring for each zone circuit should be connected to the relevant 5mm connector block on the Main
Control PCB and their screens terminated at the panel’s base earth distribution post (see page 13 for
detailed second fix connection details).
ALARMSENSE™
MANUAL CALL
POINT
+
PANEL ZONE
CIRCUIT
TERMINALS
–
+ +
ALARMSENSE™
OPTICAL/HEAT
DETECTOR
ALARMSENSE™
SOUNDER, OR
SOUNDER BASE
ALARMSENSE™
MANUAL CALL
POINT
ALARMSENSE™
SOUNDER
BEACON BASE
ALARMSENSE™
OPTICAL/HEAT
DETECTOR
END OF LINE
CAPACITOR
DO NOT SPUR
(wiring not
monitored)
75mm
WALL
339mm
170mm
Ensure no
fixing devices
are located
underneath the
Power Supply
PCB to avoid
compromising
electrical
safety
Fixing centres
Fixing centres

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 8 of 24
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
Typical conventional sounder circuit wiring
Four conventional sounder circuits are available on the fire alarm panel. These are designed for use with
conventional sounders and bells only. AlarmSense™ sounders should not be used on the conventional sounder
circuits.
Figure 5 : Typical conventional sounder circuit wiring
All sounders must be polarised as unpolarised sounders will show a sounder fault.
Connect a 6k8 end-of-line (EOL) resistor (provided in the panel’s accessory pack) at the end of each sounder
circuit to allow the wiring to be monitored. Unused sounder circuits must also have an EOL resistor fitted at
the panel terminals.
Note: Any sounders fitted must be locked to their base or non-removable.
The wiring for each conventional sounder circuit should be connected to the relevant 5mm connector block on
the Main Control PCB and their screens terminated at the panel’s base earth distribution post (see page 13 for
detailed second fix connection details).
Important sounder loading and distribution information
The panel’s power supply is designed to give a maximum output current of 1.5A. In addition to powering the
sounders, this current is also used for handling short circuit faults and supplying the panel’s battery charging
circuit and any output relays which may be fitted. As a safe margin and to allow for these other loads, the total
sounder loading for the panel should not exceed a maximum of 1.25A.
Each zone circuit and each conventional sounder circuit will support a maximum sounder alarm current of
200mA. Currents in excess of this value will cause the circuit’s fuse to trip.
The sounders should be distributed throughout the building according to the sound levels required, but the
load should be distributed as equally as possible across each circuit.
Note that faults on zone circuits affect the detectors, manual call points and sounders, so plan accordingly for
the effect of possible wiring faults.
Typical auxiliary input wiring
Two non-latching auxiliary input connections are available on the panel, as detailed below:
Alert Input (ALERT): Operates the sounders intermittently when connected to 0V.
Class Change Input (CC): Operates the sounders continuously when connected to 0V.
If either of the above are triggered, they WILL NOT operate the panel’s remote or auxiliary fire outputs.
Figure 6 : Typical auxiliary input wiring
Connect the wiring for each
input to the relevant 5mm
connector block on the Main
Control PCB and terminate
their screens at the panel’s base
earth distribution post (see
page 13 for more details).
END OF LINE
RESISTOR
(6k8 Ohm)
POLARISED
SOUNDER
POLARISED
SOUNDER
+++
–
+
POLARISED
SOUNDER
+
✗
DO NOT SPUR
(wiring not
monitored)
PANEL
SOUNDER
CIRCUIT
TERMINALS
ALERT
CC
0V
CLASS
CHANGE
INPUT
ALERT
INPUT

Typical auxiliary output wiring
Two auxiliary open collector outputs and one auxiliary output connections are available on the panel, as detailed below:
Figure 7 : Typical auxiliary output wiring for open collector outputs
Two relay outputs are available on the panel, as detailed below:
Connect each output to the relevant 5mm connector block on the Main Control PCB and terminate their screens
at the panel’s base earth distribution post (see page 13 for more details).
Reset Output
(RESET)
Turns on during the panel’s reset cycle. Can be used for resetting fire alarm system devices
such as roller-shutter doors or beam detectors. This output remains active for approximately
one second after all other outputs have returned to normal.
Remote Output
(REM)
Turns on during any new fire alarm condition or when the panel’s Silence/Resound Sounders
button is pressed to manually evacuate the building. The output turns off when the panel
is silenced. This output does not turn on when the Class Change or Alert inputs are asserted
(unless there are other fire alarm conditions present on the system). Note: It is possible to
delay the activation of the Remote Output to correspond with any zone delay(s) that have
been programmed into the panel at access level 3. If required, the remote output can be
disabled by the user. When the Remote output is activated the Remote Output light will be
lit. This output will not operate from a non-latching zone.
Auxiliary 24V
Output
(AUX 24V)
This output provides a positive voltage supply for peripheral loads (such as relays) which are
controlled from the above outputs. It is protected by a current limiting fuse which trips if
one or more of the loads are shorted. This affects all loads and results in appropriate faults
being reported at the panel. The current consumed by this output must be considered when
calculating battery standby times. DO NOT CONNECT DOOR HOLDER CIRCUITS TO THIS
OUTPUT AS THEY WILL REDUCE BATTERY STANDBY TIME - USE A SEPARATE POWER SUPPLY.
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 9 of 24
REM
RESET
AUX 24V
+
–
+
–
REMOTE
OUTPUT
RELAY
RESET
RELAY
To protect the output stage, only
24V polarised relays with back EMF
diodes should be used. If any of
the relays are to be used to switch
Mains potentials, then suitable
relays should be chosen and
installed and wired accordingly, so
as not to compromise the electrical
safety of the fire alarm system.
Auxiliary Fire
Output
(AUX)
Turns on during any fire alarm condition and off when the panel is reset. This output does
not turn on if the Class Change or Alert inputs are asserted or if the panel’s Silence/Resound
Sounders button is pressed to manually evacuate the building (unless there are other fire
alarm conditions present on the system). Note: It is possible to delay the activation of the
Auxiliary Output to correspond with any zone delay(s) that have been programmed into the
panel at access level 3. If required, the Auxiliary Output can be disabled by the user. This
output will not operate from a non-latching zone.
Fault Output
(FAULT)
This output is normally energised. When a fault occurs, the output turns off to ensure failsafe
operation even in the event of total power loss. It is important that the peripheral part of the
system this output drives is able to handle the output’s ‘normally on’ condition. If required,
this output can be disabled by the user.

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 10 of 24
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
SECOND FIX
Connecting the panel
Connecting the panel’s internal connections and PCBs should be undertaken immediately before commissioning.
Before you begin, we recommend you check all devices on the zone circuits and conventional sounder circuits are
correctly connected (see pages 7 and 8) and that cable integrity is verified throughout the installation.
Important: DO NOT use a high voltage insulation tester with any electronic devices connected.
Installing the Power Supply PCB
The panel’s Power Supply PCB combines the functions of a Mains input to regulated DC power supply unit, battery
charging unit and battery monitoring unit.
WHEN CONNECTED, THE POWER SUPPLY PCB STORES VOLTAGES AT UP TO 400Vdc AND MAY BE
LETHAL IF TOUCHED. DO NOT TOUCH THE PCB WHILST THE RED ‘HAZARDOUS VOLTAGES PRESENT’
INDICATOR IS LIT.
Under no circumstances should the fire alarm panel be operated without the Power Supply PCB correctly mounted
in the panel’s enclosure and the three retaining screws securely tightened.
The PCB should be positioned in the panel as shown in figure 8 on page 11.
Connecting the Mains
The general requirement for the Mains supply to this equipment is described on page 6.
DO NOT attempt to connect Mains to the panel until you are fully conversant with the layout and features of the
Power Supply PCB, as described above and in figure 8 on page 11.
The incoming Mains cable should be brought into the panel at the top right hand side of the enclosure and
terminated at the connector block (CONN1) on the Power Supply PCB.
Make sure the Mains earth wire is connected directly to this connector block and NOT to the base earth distribution
post which is provided for making off zone circuit and conventional sounder circuit screens.
The Power Supply PCB’s earth distribution strap MUST be connected to the spade on the base earth distribution
post before operation. The spade is compressed against a shoulder on the post via the lowest nut. The base earth
distribution post may appear loose, this is intended by design.
Connecting the standby batteries
There is a risk of explosion if incorrect battery types or sizes are used. Always replace both batteries
and always dispose of used batteries in accordance with the battery manufacturers instructions and
local regulations. Batteries are heavy and can produce dangerously high currents if shorted. Take
care when handling and routing battery leads to avoid damage.
Note: LPCB approved systems must use 3.2Ah batteries (YUCEL Y3.2-12).
Two new, good quality and fully charged 12V valve regulated lead acid (VRLA) batteries are required as the
emergency standby power supply for the panel.
The batteries should be connected in series and located in the panel’s enclosure as shown in figure 9 on page 11.
The battery leads, link wire and nylon cable ties are supplied in the panel’s accessory pack. Run the battery leads
through the slits in the panel’s lower plastic ribs and secure the batteries into position using the nylon cable ties.
The panel’s sophisticated battery monitoring unit protects the batteries against deep discharge by activating a cut
off circuit when the standby supply voltage reaches 21V approx. If batteries are not fitted, are discharged or in
poor condition, a PSU fault will show at the fire alarm panel.
The capacity of the batteries used will depend upon the required standby time. To calculate the batteries required
for any given standby period, please refer to the calculation guide on page 23.

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 11 of 24
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
Figure 9 : Battery location and connection details
+–+–
+
I
+
+
I
–
+–
Location of small
sized batteries
typically 1.2 Ah
Location of medium
sized batteries
typically 2.1 Ah
++
–
–
+
Take care to arrange
batteries so terminals
do not touch
Location of large
sized batteries
typically 3.0 Ah
Connection of leads
to Power Supply PCB
Run the battery leads
(supplied) through slits
in the plastic ribs
R E D
BLACK
Nylon
tie wraps
Link wire
Figure 3 : Power Supply PCB layout and Mains connection (Full Protective Cover & Cable Cover shown fitted)
C
C
C
C
C
C
C
C
C
C
C
C
C
C
ON
O
ON
ON
ON
ON
ON
ON
N1
N1
N1
N1
N1
N1
N1
N
N
N
N
N
N
N
N
L
L
L
L
L
L
CONN2
BLK-RED+
VR1
F2
F1.6A
PL2
PL1
F
F
F1
F
F
1A
1A
2
2
2
50V
50V
0V
50V
50V
50V
50V
H
H
H
RC
RC
C
RC
C
C
RC
F1
F
F
F
V
V
V
HRC
F
F1 1A
2
0
50
250
0
0V
V
0V
V
V
V
V
HRC
V
0
V
V
0
HR
R
V
V
0V
1
A 250
R
1A
R
Incoming Mains Cable
This cable MUST be segregated from
other cables. Good quality cable
glands MUST always be fitted.
Battery Connector
(CONN2)
(Leads supplied in
the panel’s accessory
pack.) See below for
connection details.
Mains Input (CONN1)
L = Live (BROWN)
N = Neutral (BLUE)
= Earth (GREEN/YELLOW)
The incoming Mains earth wire MUST
be connected to the terminal marked
and NOT to the base earth distribution post.
CONN1
NL
Cable cover
removed
PSU Earth Distribution Strap
DO NOT operate the panel
without first connecting
this strap to the base earth
distribution post.
Battery Fuse (F2) Connector Cable Socket (PL1)
Connect other end of lead to
the rear of Main Control PCB.
Hazardous Voltages Present LED
When lit red, hazardous
voltages are present under the
two covers. Allow to discharge
for at least 5 minutes before
removal & handling.
Mains Fuse (F1)
Exposed Live
parts under fuse
cover. Isolate
before removal.
Exposed live parts under cable
cover. Isolate first, then remove
the small cable cover by loosening
its single retaining screw which is
retained in the cover. Only operate the
PSU with this cover securely fitted.

Installing the Main Control PCB
The panel’s Main Control PCB provides all the 5mm connector blocks for the system’s zone circuits, conventional
sounder circuits, auxiliary inputs and auxiliary outputs. It also provides the engineer with access to a wide range of
engineering functions, details of which appear later in this manual.
Before any connections can be made, the Main Control PCB must first be securely positioned inside the fire alarm
panel (see figure 10 below) using the five retaining screws. As the PCB is presented to the panel, remember to
attach the telecoms-style connecting cable to SKT2 on the reverse of the Main Control PCB and to PL1 on the Power
Supply PCB.
Important: SKT1 on the reverse of the Main Control PCB is for the connection of optional system expansion devices
such as Network Driver Cards (for repeater panels) and Relay Output Boards. If any of these devices are to be used,
refer to the individual installation instructions supplied with them as they will need to be fitted to the panel before
the Main Control PCB.
Take care when reconnecting the 5mm connector blocks that you do so the correct way round. We recommend
that you clearly label all system wiring to reduce the likelihood of incorrect connection.
Figure 10 : Main Control PCB layout
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 12 of 24
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
SW4
SW3
SW8
SW1
SW2
CONN2
SW7
SW6
SW5
ACCESS
LEVEL THREE
FUNCTIONS
OPEN
CIRCUIT
DELAYS TEST
ACCESSEDTEST
PSU
FAULT
Z2 Z3
GENERAL
FAULT
DELAY MINUTES
0
1
2
3
CAUTION - RISK OF EXPLOSION IF
INCORRECT TYPE OF BATTERIES FITTED.
DISPOSE OF USED BATTERIES ACCORDING
TO THE MANUFACTURERS INSTRUCTIONS.
4
NONLATCHING
56
7
FAULT
OUTPUT
STATUS
SUPPLY
OK
REMOTE
OUTPUT
AUX
OUTPUT
STATUS
FOR OPERATIONAL DETAILS PLEASE
CONSULT THE MAINTENANCE MANUAL
Z4
COINCIDENCE
Z5 Z6 Z7
8
REPEATER
FAULT
SHORT
CIRCUIT
SILENCE
INTERNAL
SOUNDER
OUTPUTS
DELAYED
SOUNDER
STATUS
REMOTE
OUTPUT
STATUS
GENERAL
DISABLEMENT
GENERAL
FIRE
9
10
SYSTEM
FAULT
NEXT OPTION
CODE ENTRY(3)
ENABLE/DISABLE
LAMP TEST
CODE ENTRY(4)
CODE ENTRY(1)
CODE ENTRY(2)
ESCAPE ACCESS
SILENCE/
RESOUND
SOUNDERS
RESET
FAULT
ZONE1 ZONE4ZONE2 ZONE3 ZONE8ZONE7ZONE6ZONE5
FIRE
VR1
–
+
–
+–
+
–
+–
+
–
+ +
4CS3CS2CS8Z
CC
STUPNI
TIUCRICREDNUOSOUTPUTS AUX
AUX
24V
0V
ALT
REM
CONN5
CONN6
CONN7
CONN8
CONN9
–
+
– –
+–
+
–
+
Z1
DETECTOR CIRCUITS
REMOVING THIS CIRCUIT
BOARD EXPOSES HAZARDOUS
VOLTAGES - PLEASE REFER TO
INSTALLATION INSTRUCTIONS
WARNING
SENSITIVE TO STATIC
ELECTRICITY - OBSERVE
PRECAUTIONS BEFORE
HANDLING
I
O
ACCESS LEVEL 2
RST
FAULT
NO
NC
C
NO
NC
C
1CS
+–
CONN10

Connecting the zone circuits and conventional sounder circuits
Incoming zone circuits and conventional sounder circuits (if used) should be connected to the relevant connector
block on the Main Control PCB as shown in figure 11 below.
For typical zone circuit and conventional sounder circuit wiring diagrams, please refer to pages 7 and 8.
Figure 11 : Zone circuit and conventional sounder circuit connections
Connecting the auxiliary inputs, auxiliary outputs and relay outputs
Incoming auxiliary inputs, auxiliary outputs and relay outputs cables should be connected to the relevant connector
block terminals on the Main Control PCB. If screened cables have been used, all screens should be adequately
insulated and connected between the nut and washers on the base earth distribution post (see below) using eyed
crimp connectors (as per the zone circuit and conventional sounder circuit examples shown in figure 11).
For a full description of the inputs and outputs available on the panel, including typical wiring diagrams, please
refer to pages 8 & 9.
Important notes regarding the earthing of screens
All screens should be adequately insulated and
connected between the nut and washers on the
base earth distribution post (see right) using suitable
eyed crimp connectors. Do not disturb the lower nut,
this must be secure to ensure earth continuity. The base earth
distribution post is provided for terminating earth screens or
drains and not as the main earthing point. The system designer
or installer must review the external earth bonding (if required)
with respect to the national wiring rules. That is, if the type of
installation requires protective earth bonding, then this must be
applied externally and in conjunction with the type of earthing
system employed on that particular site. This must always be
done with regard to the appropriate national wiring rules.
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 13 of 24
Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 SC1SC2 SC3SC4
SOUNDER CIRCUITSDETECTOR CIRCUITS
CONN5
CONN6
CONN7
–
+
–
+–
+
–
+–
+
–
+–
+
–
+–
+
–
+–
+
–
+
insulated
screens
insulated
conductors
See ‘Important notes
regarding the earthing
of screens’ section below
CC
STUPNI
OUTPUTS AUX
AUX
24V
0V
ALT
RST
CONN8
CONN9
REM
FAULT
NO
NC
C
NO
NC
C
CONN10
CONN2
nut
plain
washers
crimped
connections
Do not untighten lower nut
spring
washer
screens

PROGRAMMING THE PANEL
An overview of the panel’s controls
Three control levels are available on the panel - general user (access level 1), authorised user (access level 2) and
engineer (access level 3), as detailed below:
General user controls (access level 1)
When the panel is in its normal state, the indicator lights on the panel front give a comprehensive overview of the
system’s current status. Any fire and fault conditions are clearly displayed, disablements highlighted and the status
of all outputs reported. The only functions that can be performed when the panel is in this state are:
•Muting the panel’s internal sounder.
•Overriding any delays which may have been programmed into the panel.
•Putting the panel into access level 2 to access the authorised user controls (see below).
Authorised user controls (access level 2)
To avoid unauthorised changes to critical parts of the fire alarm system, certain fire alarm panel controls are only
available to authorised users. These include:
•Silencing the sounders.
•Resetting an alarm condition.
•Manually activating the alarm sounders (to evacuate a building)
•Testing the indicator lights.
•Disabling or enabling any (or all) of the following: zones, sounders, the fault output, the remote output, the
auxiliary fire output and delays.
The authorised user controls can be accessed by entering the code 2 1 4 3 using the keypad or, by turning the
keyswitch to the ‘I’ position.
For detailed information on how to use the general and authorised user controls, please refer to the User Manual
/ Log Book.
Engineer controls (access level 3)
It is possible to read or interrogate the site specific data at this level. The following controls are available to
competent service personnel only:
•The programming of coincidence / double knock. Note: This function is non-compliant with EN54-2.
•The setting-up zones for non-latching operation. Note: This function is non-compliant with EN54-2.
•The programming of delays.
•The invoking of test procedures.
•Programming silenced sounders to resound, or not resound, when new zone in alarm.
•Fault diagnosis.
A brief overview of these functions appears below. Details of how to gain access to the engineer controls and how
to use them appears on pages 16 and 17. We recommend, however, that you carefully read the sections below
before attempting to implement any changes to the factory defaults or existing system set-up.
Engineer functions
Coincidence (Note: This function is non-compliant with EN54-2)
The programming of coincidence (also referred to as ‘double knock’) is a feature often used on sites where
the consequence of a false alarm can be onerous, e.g. where the panel is used to trigger a sprinkler, or gas
extinguishant system.
Coincidence is programmed into the panel in pairs of zones, the pairs being zones 1 and 2; zones 3 and 4 (if fitted),
zones 5 and 6 (if fitted); and zones 7 and 8 (if fitted).
When any of these pairs are programmed to operate in coincidence mode, there must be alarms on both zones
before the sounders and outputs are turned on. If only one of the pair goes into alarm, the panel will indicate the
alarm condition by illuminating the relevant indicator on the front panel and sounding its internal sounder, thus
prompting a responsible person to investigate.
If found to be false, the alarm can be reset by the user. If found to be a true fire condition, the user can manually
activate the alarm sounders and outputs by entering access level 2 and pressing the SILENCE/RESOUND SOUNDERS
button.
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 14 of 24

Important note: If link PLK1 is fitted on the Main Control PCB (see right) triggering a manual call
point on any zones programmed for coincidence will activate the alarm sounders and outputs
immediately. Alarms from detectors will still be processed as described previously in this section.
From an installation point of view, detectors on zones assigned for coincidence should be installed in close
proximity to each other. This ensures if the user is not around to investigate the cause of the alarm, that a detector
in alarm on one zone is quickly confirmed by its neighbour on the corresponding zone in the event of a real fire.
Alarms raised in zones not set up for coincidence will be processed as normal.
Non-Latching Zones (Note: This function is non-compliant with EN54-2)
Any or all of the zones on the fire alarm panel can be set up for non-latching operation.
Alarms raised from non-latching zones are indicated as normal but when the alarm stimulus that triggered the zone
is cleared, the alarm condition at the panel automatically clears too (i.e. a manual panel reset is not required).
Note: Alarms raised on non-latching zones will not trigger the panel’s auxiliary fire and remote outputs.
Non-latching zones may be used to interconnect fire panels to prevent a ‘deadly embrace’ situation. This is a permanent
unresettable alarm condition arising from multiple fire panels simultaneously flagging latching alarm conditions.
Delays
A delay of 1 to 10 minutes can be set between the fire alarm panel being triggered to its alarm sounders and
outputs being activated. This is a particularly useful feature in public places where the nuisance and panic caused
by a false alarm must be avoided
The delay period is set by adjusting the VR1 control on the Main Control
PCB (see right) using a terminal screwdriver. Note: The same delay
period will apply to all pre-programmed delayed zones and outputs.
When an alarm occurs on a delayed zone, it is processed as normal.
However, the activation of any pre-programmed sounders and outputs is postponed until
the delay period has expired, thus allowing the cause of the alarm to be investigated by a responsible person.
During the delay period, the Output Delays light on the panel front pulses to indicate the delay is operative.
Pressing the SILENCE/RESOUND SOUNDERS button will override the delay at any time and result in any delayed
sounders and outputs being activated. Alternatively, in the event of a false alarm, pressing the CONTROL PANEL
RESET button (at access level 2) during the delay period will return the system to normal.
Important note: If link PLK1 is fitted on the Main Control PCB (see right), triggering a manual call
point during the delay period will activate any delayed alarm sounders and outputs immediately.
If link PLK1 is not fitted, triggering a manual call point will have no effect on the delayed alarm
sounders and outputs.
Test
To aid commissioning and routine maintenance checks, a non-latching ‘one man walk test’ facility is available.
When a detector or manual call point is triggered on any zone(s) in test, the alarm sounders operate for
approximately one second on and eight seconds off. This cycle continues until the cause of the alarm is removed
(either by the test smoke clearing from the detector or the manual call point being reset), at which point the zone
circuit also automatically resets. As the engineer walks around the site, additional devices on the zone(s) in test can
be checked with the momentary activation of the alarm sounders confirming correct operation.
Zones programmed for test, will be indicated at the panel by their Fault lights pulsing quickly in synchronisation
with the General Test light. Should an alarm occur on a zone that is not programmed for test, the alarm will be
processed in the normal way. All zones that are in test will have their tests temporarily suspended until the alarm(s)
from the other zones are reset. At this point zone testing may resume. In other words, the alarm will operate
correctly despite being in test mode.
Program sounders to resound or not resound
Once the sounders (AlarmSense™ and conventional) have been activated after an alarm and then silenced, it is
possible to set up the panel so that a new alarm raised from another zone resounds, or does NOT resound, the
sounders in accordance with EN54-2 {Clause 7.8d}.
Program sounders on zone circuits to be fitted or not fitted
By default, zone circuits have AlarmSense™ sounders fitted. However, it is possible to programme a zone circuit
to have sounders not fitted.
Fault diagnosis
A wide range of fault diagnosis features are available at access level 3. These are described in detail on pages 18
to 22 of this manual.
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 15 of 24
DELAY MINUTES
0
1
2
3
4
5
6
7
8
9
10
VR1
Use a small terminal
screwdriver to adjust the
delay time period.
For information on how to
assign individual zones so
the delay period applies to
them, see pages 16 and 17.
PLK1
FUNCTION
MCP/SOUNDER
PLK1
FUNCTION
MCP/SOUNDER

Accessing the engineer controls
Before programming the panel, please refer to pages 14 and 15 for an overview of the various engineering
functions available and the effect their implementation will have on the way the system operates.
To gain access to the panel’s engineer functions, remove the panel lid using the Torx key provided and press the
ACCESS LEVEL THREE FUNCTIONS button on the Main Control PCB (see figure 12 below).
Figure 12 : Location of the panel’s programming tools on the Main Control PCB
When the ACCESS LEVEL THREE FUNCTIONS button is pressed for
the first time, the Accessed light will be lit steady and the first
engineer function (COINCIDENCE) will be selected and indicated
by its yellow light flashing (see right).
Every time the ACCESS LEVEL THREE FUNCTIONS button is pressed
the next engineer function is selected.
Note: The engineer functions are graphically linked on the Main
Control PCB by an ‘S’ shaped line (see right). Pressing the ACCESS
LEVEL THREE FUNCTIONS button after the last selection (SOUNDER
STATUS) returns to the first function (COINCIDENCE).
To exit access level 3 at any time, press the ESCAPE ACCESS button.
Notes:
1. Access level 3 functions that are relevant to zones temporarily use the Zone Fault lights to show which zones
have been programmed for that function. This means any fault or disablement indication is suppressed until
the programming of the relevant function is complete.
2. When the panel’s lid is removed, it is still possible to access the panel’s authorised user control, i.e. access
level 2. This is done by entering the 2 1 4 3 entry code or, by turning the keyswitch to the ‘I’ position).
For detailed information on the authorised user controls, please refer to the separate User Manual / Log Book.
3. ‘SYSTEM FAULT’, ‘REPEATER FAULT’, ‘HEAD OUT’, ‘OPEN CIRCUIT’ and ‘SHORT CIRCUIT’ options are for fault
diagnosis purposes, as detailed on pages 18 to 22.
To program coincidence (Note: This function is non-compliant with EN54-2)
1. Press the ACCESS LEVEL THREE FUNCTIONS button until the COINCIDENCE light flashes (any pairs of zones that are already
programmed for coincidence will have their Zone Fault lights lit steady).
2. To change the coincidence configuration press the NEXT OPTION button (Fault lights for zones 1 and 2 will flash slower
than COINCIDENCE light if NOT programmed for coincidence, or at the same rate if they are).
3. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4. Confirm your selection by pressing the NEXT OPTION button. This will move to the next pair of zones (if available).
5. Repeat steps 3 and 4 until the process is complete.
6. To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the
ACCESS LEVEL THREE FUNCTIONS button.
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 16 of 24
SW4
SW3
SW8
SW1
SW2
SW7
SW6
SW5
ACCESS
LEVEL THREE
FUNCTIONS
OPEN
CIRCUIT
DELAYS TEST
ACCESSEDTEST
PSU
FAULT
GENERAL
FAULT
DELAY MINUTES
0
1
2
3
CAUTION - RISK OF EXPLOSION IF
INCORRECT TYPE OF BATTERIES FITTED.
DISPOSE OF USED BATTERIES ACCORDING
TO THE MANUFACTURERS INSTRUCTIONS.
4
NONLATCHING
56
7
FAULT
OUTPUT
STATUS
SUPPLY
OK
REMOTE
OUTPUT
AUX
OUTPUT
STATUS
COINCIDENCE
8
REPEATER
FAULT
SHORT
CIRCUIT
SILENCE
INTERNAL
SOUNDER
OUTPUTS
DELAYED
SOUNDER
STATUS
REMOTE
OUTPUT
STATUS
GENERAL
DISABLEMENT
GENERAL
FIRE
9
10
SYSTEM
FAULT
NEXT OPTION
CODE ENTRY(3)
ENABLE/DISABLE
LAMP TEST
CODE ENTRY(4)
CODE ENTRY(1)
CODE ENTRY(2)
ESCAPE ACCESS
SILENCE/
RESOUND
SOUNDERS
RESET
FAULT
ZONE1 ZONE4ZONE2 ZONE3 ZONE8ZONE7ZONE6ZONE5
FIRE
VR1
REMOVING THIS CIRCUIT
BOARD EXPOSES HAZARDOUS
VOLTAGES - PLEASE REFER TO
INSTALLATION INSTRUCTIONS
WARNING
SENSITIVE TO STATIC
ELECTRICITY - OBSERVE
PRECAUTIONS BEFORE
HANDLING
I
O
ACCESS LEVEL 2
HEAD
OUT
DELAYS TEST
NONLATCHING
COINCIDENCE
ACCESS
LEVEL THREE
FUNCTIONS
OPEN
CIRCUIT
SHORT
CIRCUIT
REPEATER
FAULT
SYSTEM
FAULT
SW8
CFP ALARMSENSE PANEL CONTROLS
HEAD
OUT
SOUNDER
STATUS
ACCESS LEVEL THREE FUNCTIONS button

To program non-latching zones (Note: This function is non-compliant with EN54-2)
1. Press the ACCESS LEVEL THREE FUNCTIONS button until the NONLATCHING light flashes (any zones that are already
programmed for non-latching operation will have their Zone Fault lights lit steady).
2. To change the non-latching configuration press the NEXT OPTION button (Zone 1’s Fault light will flash slower than the
NONLATCHING light if NOT programmed, or at the same rate if it is).
3. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4. To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5. Repeat steps 3 and 4 until the process is complete.
6. To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the
ACCESS LEVEL THREE FUNCTIONS button.
To program delays
1. Press the ACCESS LEVEL THREE FUNCTIONS button until the DELAYS light flashes (any zones that are already programmed
for delays will have their Zone Fault lights lit steady, and similarly, if the Remote Output or Auxiliary Output are delayed,
then their relevant status lights will be lit steady. Note: Any existing fault indications will be temporarily suppressed during
this programming function. On exiting the function, the previous indications will be restored).
2. To change the delays configuration press the NEXT OPTION button (Zone 1’s Fault light will flash slower than the DELAYS
light if NOT programmed, or at the same rate if it is).
3. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4. To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5. Repeat steps 3 and 4 until the zone selection process is complete.
6. Pressing the NEXT OPTION button when on the last zone will select the Remote Output for editing. The output’s current
status will be shown by the Remote Output Status light, in the same way as for the zones.
7. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
8. Pressing the NEXT OPTION button will select the Auxiliary Output for editing. The output’s current status will be shown by
the Auxiliary Output Status light, in the same way as for the zones.
9. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
10. Pressing the NEXT OPTION button will return the selection to zone 1.
11. Set the delay period which will apply to all delayed zones or outputs by adjusting the VR1 control on the Main Control PCB
with a terminal screwdriver (this can be anything from 1 to 10 minutes), then press the ESCAPE ACCESS button or move
onto the next programming function by pressing the ACCESS LEVEL THREE FUNCTIONS button.
To program zones into test
1. Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes (any zones that are already programmed for
test will have their Zone Fault lights lit steady).
2. To change the test configuration press the NEXT OPTION button (Zone 1’s Fault light will flash slower than the TEST light if
NOT programmed, or at the same rate if it is).
3. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4. To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5. Repeat steps 3 and 4 until the process is complete.
Important: Before testing any of the zones you have programmed for test, you must first press the ESCAPE ACCESS button.
Any zone(s) in test will be flashing and the General Test light will also be flashing. Testing can now commence. Remember
to take the relevant zones out of test when testing is complete.
To program the sounder status (new zone in alarm resounds, or does not resound, the sounders)
1. Press the ACCESS LEVEL THREE FUNCTIONS button until the SOUNDER STATUS light flashes.
If the SOUNDER STATUS light flashes three times quickly with a longer off period, then an alarm in a new zone will
resound the sounders. If the SOUNDER STATUS light flashes with equal on-off periods, then an alarm in a new zone will
NOT resound the sounders.
2. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
3. To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the
ACCESS LEVEL THREE FUNCTIONS button.
To program the sounder status (sounders fitted or not fitted)
1. Press the ACCESS LEVEL THREE FUNCTIONS button until the SOUNDER STATUS light flashes. Then press the ACCESS LEVEL
THREE FUNCTIONS button a second time.
Any zone circuits that are programmed (by default) to have sounders fitted will have their Zone Fault lights lit steady.
2. To change the configuration press the NEXT OPTION button (Zone 1’s Fault light will flash at the same rate as the
SOUNDER STATUS light if sounders are programmed as fitted, or flash slower if programmed as NOT fitted).
3. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4. To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5. Repeat steps 3 and 4 until the process is complete.
6. To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the
ACCESS LEVEL THREE FUNCTIONS button.
The relevant part of the System Set-Up Data chart in the User Manual / Log Book must be updated if you
implement or make any changes to the coincidence, non-latching zones, delays, or sounder status functions.
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 17 of 24

FAULT DIAGNOSIS
Fault indications
When a fault occurs on a critical part of the fire alarm system, the panel responds by activating its internal sounder
and illuminating the General Fault light and any other Fault light(s) relating to the fault. The panel’s fault output
will also activate (provided it has not been disabled).
The type of faults typically indicated at the fire alarm panel are highlighted below. A more precise diagnosis of
fault conditions is available at access level 3 (the summaries below refer to the sections you should read later
in this manual for further information). Unless otherwise stated, repairing any particular fault condition will
automatically clear the fault from the panel. If the panel is reset whilst faults still exist, the faults will reappear
after a short period of time.
Note: It is possible to mute the panel’s internal sounder at any time by momentarily pressing the SILENCE INTERNAL
SOUNDER button.
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 18 of 24
General Fault
This light flashes yellow when there is a
fault on any part of the fire alarm system.
It is always lit in tandem with at least one
other Fault light which displays precise
information on the type of fault detected.
Zone Faults
All of the panel’s zone circuits (up to eight) are monitored for open
and short circuit faults and detector head removal (unless there is
an alarm condition or the zone is in test or disabled). All faults are
indicated by the relevant Zone Fault light(s) pulsing yellow. The
Sounder Status light will also pulse yellow if sounders are fitted.
For advice on how to correct this fault see page 19, section 1.1.
Supply
Present
This light
should be lit
green at all
times. If off, see
power supply
faults, page 19,
section 1.2.
Power Supply Fault
This light flashes yellow when
one or more of the following
has occurred:
1) The Mains supply is too low or
has failed completely.
2) Mains fuse (F1) has ruptured.
3) Battery fuse (F2) has ruptured.
4) The battery supply voltage is
too low.
5) The panel’s power supply unit
is faulty.
For advice on how to correct this
fault see page 19, section 1.2.
Remote Output Status
This light flashes yellow
when there is a fault on
the output’s aux. 24V
supply.
For advice on how to deal
with this type of fault see
page 22, section 1.6.
System Fault
This light flashes yellow
when one or more of the
following has occurred:
1) There is a microprocessor
“watchdog” fault.
2) The microprocessor’s
site memory has been
corrupted.
3) The microprocessor’s
program menu has been
corrupted.
4) The Main Control PCB is
faulty.
For advice on how to
correct this fault see page
21, section 1.3.
Repeater Fault
This light flashes
yellow when the
master panel cannot
communicate with
one or more repeater
panels (if fitted).
For advice on how to
correct this fault see
page 22, section 1.4.
Sounder Status
This light pulses yellow
when one or more
of the following has
occurred:
1) A conventional
sounder circuit has a
fault.
2) A sounder on a zone
circuit has a fault. The
relevant Zone Fault
light(s) will also pulse
yellow.
All sounder circuits are
monitored for open
and short circuit faults
(unless disabled or in
an alarm condition).
For advice on how to
correct this fault see
page 22, section 1.5.
12
37
546 8
supply
present
remote
output
general
fault
power
supply
fault
system
fault
repeater
fault
sounder
status
auxiliary
output
status
output
delays
test
remote
output
status
fault
output
status
general
disablement
accessed
Zone fault/disabled/test

1.1 Zone faults
•To find out if a head out fault has occurred on a zone circuit:
1. Remove the panel’s lid using the Torx key provided and press the ACCESS LEVEL THREE FUNCTIONS
button on the Main Control PCB to gain access to the panel’s engineer functions (see below).
2. Continue pressing the ACCESS LEVEL THREE FUNCTIONS button until HEAD OUT light pulses.
Any existing Zone Fault lights are suppressed and the zone light(s) for any zone(s) with a head out fault
are illuminated, e.g. if a detector head has been removed on zone 2, then Zone 2’s Fault light will be lit.
•To find out if an open circuit fault has occurred on a zone circuit:
1. Follow steps 1 and 2 outlined above until the OPEN CIRCUIT light pulses.
2. Any existing Zone Fault lights are suppressed and the zone light(s) for any zone(s) with an open circuit
fault are illuminated, e.g. if the wiring on zone 6 is broken, then Zone 6’s Fault light will be lit.
•To find out if a short circuit fault has occurred on a zone circuit:
1. Follow steps 1 and 2 detailed above until the SHORT CIRCUIT light pulses.
2. Any existing Zone Fault lights are suppressed and the zone light(s) for any zone (s) that have a short circuit
fault are illuminated, e.g. if the wiring on zone 4 has been shorted, then Zone 4’s Fault light will be lit.
Suggested actions:
1. Disconnect the faulty zone circuit completely and refit the end-of-line capacitor at the panel. If the
fault condition clears this confirms there is a wiring fault.
2. Refit and double check the wiring and the end-of-line capacitor on the zone. Trace the fault with
consideration for the type of fault indicated (see above).
Note: A common head out fault is a detector head badly seated in a base which is not making a true
connection.
1.2 Power supply faults
A power supply fault indicates one, or more, of the following faults. Page 11 of this manual must be referenced
when carrying out any of the suggested action procedures described below.
•The Mains supply voltage is too low or has failed completely, the Mains fuse (F1) has ruptured or the PSU has failed.
Symptoms: The panel runs on batteries, but not on Mains.
Suggested actions:
1. Taking all due precautions, check Mains voltages are within range (see Technical Specifications, page 24)
by probing Live and Neutral connections at connector block (CONN1). If not within range, repair Mains
supply.
2. If within range and the red Hazardous Voltages Present light is not lit, check the Mains fuse (F1).
3. If the fuse is intact, the red Hazardous Voltages Present light on the Power Supply PCB may, or may not,
be lit. The PSU is faulty and should be replaced. Isolate the Mains supply and wait for the red Hazardous
Voltages Present light to extinguish before replacing the Power Supply PCB.
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 19 of 24
DELAYS TEST
NONLATCHING
COINCIDENCE
ACCESS
LEVEL THREE
FUNCTIONS
OPEN
CIRCUIT
SHORT
CIRCUIT
REPEATER
FAULT
SYSTEM
FAULT
SW8
CFP ALARMSENSE PANEL CONTROLS
HEAD
OUT
SOUNDER
STATUS

•The battery fuse (F2) is ruptured.
Symptoms: The panel runs on Mains, but not on batteries.
Suggested actions:
1. Isolate the Mains supply and disconnect the batteries.
2. Remove the Main Control PCB and check the battery fuse (F2) on the Power Supply PCB for continuity.
3. If ruptured check the Power Supply and Main Control PCBs for signs of damage. If none found, replace
fuse with the correct type, ensuring that the fuse clip is not damaged when re-inserting the fuse.
4. Refit the Main Control PCB and reconnect the batteries.
5. If the green Supply Present light is lit, reconnect the Mains supply and check that the power supply
fault has cleared. If the Supply Present light is not lit, either the Power Supply PCB or the Main Control
PCB is faulty and should be replaced.
6. If the battery fuse (F2) is intact, proceed to check the battery voltage/condition (see below).
•The battery voltage is too low, or in poor condition.
Symptoms: The panel runs on Mains, but may or may not run on batteries.
If the Mains supply has failed and the battery supply has been discharged to the point where the voltage is
too low (i.e less than 21V), the panel will automatically turn off to avoid damaging the batteries by allowing
them to deep discharge. The panel will not restart unless fresh, fully charged batteries are connected, or the
Mains supply is restored.
If the Mains supply has not failed, but the total battery voltage is less than 21V, the PSU will not charge the
batteries to avoid damage to the charging circuit. If the batteries can be charged, the panel will still show a
power supply fault until they have sufficient charge, at which point the power supply fault will automatically
be cleared. Depending on battery size and the depth of discharge, this may take several hours. If the batteries
are in poor condition they must be replaced.
If the batteries (or their leads) are high resistance, then this will also result in a PSU fault. This fault may occur
due to:
- batteries that have been stored for many months
- low quality batteries
- old batteries
- loose/poor connections to the batteries.
If the batteries are in good condition and all the other checks have been performed and no faults found,
the Power Supply PCB is faulty and should be replaced. Note: Batteries that are not connected, connected in
reverse, or with opposite polarities will also cause a power supply fault condition.
•Supply Present light not lit.
If the Supply Present light is not lit one of the following faults has occurred:
1. Both the Mains supply and the standby batteries have failed. This could be because the Mains supply has
failed and the batteries have been exhausted.
Suggested action: Restore the Mains supply and the Supply Present light should come back on.
However, if the batteries are discharged this will be recognised as a fault by the panel and indicated as
such. See ‘Battery voltage too low’ above.
2. The Power Supply PCB, the Main Control PCB and/or the cable that connects them is faulty.
If the Mains supply is present (indicated by the red Hazardous Voltages Present light being lit on the
Power Supply PCB), check that the connector cable between the Power Supply PCB and the Main Control
PCB is fully inserted at both ends. If so, either the Power Supply PCB and/or the Main Control PCB and/or
the connector cable are faulty and should be replaced.
LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 20 of 24
This manual suits for next models
11
Table of contents
Other C-TEC Control Panel manuals

C-TEC
C-TEC CAST ZFP Operating and maintenance manual

C-TEC
C-TEC XFP User manual

C-TEC
C-TEC CAST XFP User manual

C-TEC
C-TEC CAST XFP Installation and operation manual

C-TEC
C-TEC CAST XFP Installation and operation manual

C-TEC
C-TEC CAST ZFP Instruction Manual

C-TEC
C-TEC XFP501E/CA Product guide

C-TEC
C-TEC XFP502/X User manual

C-TEC
C-TEC EACIE Operating and maintenance manual

C-TEC
C-TEC XFP510-32 User manual