Commissioning
A ter installation, the valve must be tested and commissioned in
accordance with the instructions given below, taking into account
current applicable standards.
1) Ensure that the system is clean and ree rom any dirt or debris
be ore commissioning the thermostatic mixer.
2) It is recommended that the temperature is set using a suitable
calibrated digital thermometer. The valve must be
commissioned by measuring the temperature o the mixed
water emerging at the point o use.
3) The maximum outlet temperature rom the valve must be set
taking account o the luctuations due to simultaneous use.
It is essential or these conditions to be stabilised be ore
commissioning.
4) Adjust the temperature using the adjusting knob on the valve.
For sa ety reasons, it is advisable to limit the maximum mixed
water temperature to 120°F in domestic hot water systems.
Setting the tem erature
The temperature is set to the required value by means o the
adjusting knob with the graduated scale on the top o the valve.
Preset locking
Position the handle to the number required. Unscrew the head
screw, pull o the handle and reposition it so that the handle its
into the internal slot o the knob. Tighten the head screw.
Maintenance
In service tests should be carried out regularly to monitor the
mixer per ormance, as deterioration o per ormance could
indicate that the valve and/or the system require maintenance. I ,
during these tests, the temperature o the mixed water has
changed signi icantly in comparison with the previous test, the
details given in the installation and commissioning sections
should be checked and maintenance carried out.
The ollowing aspects should be checked regularly to ensure that
the optimum per ormance levels o the valve are maintained.
Every 12 months at least, or more o ten i necessary.
1) Check and clean the system ilters.
2) Veri y that any check valves positioned upstream o the Cale i
valve are operating correctly, without problems caused by
impurities.
3) The Cale i valve should not be dismantled. Limescale can be
removed rom internal components by immersion in a suitable
de-scaling luid.
4) When the components which can be maintained have been
checked, commissioning should be carried out again.
Min 1 2 3 4 5 6 7 Max
81 90 100 111 120 127 136 145 152
Pos.
27 32 38 44 49 53 58 63 67