Camozzi PME Series Manual

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
1
Operation and maintenance instructions for Series PME Electronic proportional
regulator
The products are designed and manufactured in conformity with the following directives:
-2014/30/UE “Electromagnetic compatibility”
They also comply partially or totally with regard to the applicable parts of the following standards:
-EN 61000-6-2:2005 Electromagnetic compatibility (EMC) —Part 6-2:
Generic standards - Immunity for industrial environments
-EN 61000-6-4:2007 Electromagnetic compatibility (EMC) —Part 6-4: Generic standards -
Emissions for industrial environments
-UL 61010-1: Safety requirements for electrical equipment for measurement, control and
laboratory use Part 1: General requirements and the following technical standards
and to the following technical standards:
-EN ISO 4414:2010 Pneumatics - General rules and safety requirements for systems and their
components.
For more information regarding the declarations of conformity, see the Certifications section
on the website http://catalogue.camozzi.com.
Made in Italy

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
2
Sommario
1. Product identification ..................................................................................................................3
2. Introduction .................................................................................................................................4
3. General recommendations ..........................................................................................................4
4. Product description:.....................................................................................................................5
5. Pneumatic simbol:........................................................................................................................6
6. General characteristics and conditions of use.............................................................................7
7. Electrical/Pneumatic circuit.......................................................................................................15
8. Product storage and transport...................................................................................................15
9. Installation and start-up.............................................................................................................15
10. Digital output ..........................................................................................................................19
11. NFCamApp ..............................................................................................................................20
11.1. Information..........................................................................................................................21
11.2. Configurator ........................................................................................................................22
11.2.1. USER SETUP......................................................................................................................22
11.2.2. RANGE SETUP ..................................................................................................................22
11.2.3. DIGITAL OUTPUT SETUP ..................................................................................................23
11.2.4. PASSWORD ......................................................................................................................24
11.2.5. SAVING PARAMETERS......................................................................................................24
12. Use...........................................................................................................................................24
13. Limitations on use...................................................................................................................25
14. Maintenance ...........................................................................................................................25
15. Environmental notes...............................................................................................................25
16. Contacts ..................................................................................................................................27

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
3
1. Product identification

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
4
2. Introduction
This manual illustrates how to properly use the Series PME electronic pressure regulator.
This version of the Controller is identified with code 0184 xx xx xxx x xxxxx, where 0184 indicates
the version of regulator and is followed by year, week, machine, station and serial number.
3. General recommendations
The recommendations regarding safe use in this document should be observed at all times.
•Some hazards can only be associated with the product after it has been installed on the
machine/equipment. It is the task of the final user to identify these hazards and reduced the
associated risks accordingly.
•The products dealt with in this manual may be used in circuits that must comply with the
standard EN ISO 13849-1.
•For information regarding component reliability, contact Camozzi.
•Before proceeding with use of the product, carefully read all information in this document.
•The instructions in this manual must be observed together with the instructions and
additional information regarding the product in this manual, available from the following
reference links:
oweb site http://www.camozzi.com
oCamozzi general catalogue
oTechnical assistance service
•Assembly and start-up operations must be performed exclusively by qualified and authorized
personnel on the basis of these instructions.
•It is the responsibility of the system/machine designer to ensure the correct selection of the
most suitable pneumatic component according to the intended application.
•For all situations not contemplated in this manual and in situations in which there is the risk
of potential damage to objects, or injury to persons or animals, contact Camozzi for advice.
•Never make unauthorized modifications to the product. In this case, any damage or injury
to objects, persons or animals will be the responsibility of the user.
•All relevant product safety standards must be observed at all times.
•Never intervene on the machine/system before verifying that all working conditions are safe.
•Before installation and maintenance, ensure that the specific envisaged safety locks are
active, and then disconnect the electrical mains (if necessary) and system pressure supply,
discharging all residual compressed air from the circuit and deactivating residual energy
stored in springs, condensers, recipients and gravity.
•To reduce the noise levels caused by the discharge of air from the component, envisage the
use of silencers or convey the fluid to a zone where no personnel are envisaged during
normal operation.
•Avoid covering the equipment with paint or other substances that may reduce heat
dissipation.

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
5
•Avoid cleaning with aggressive agents such as to dull the plastics and make it difficult to
read the screen
•In the event of an electrical power failure and pneumatic supply at the port connection 1,
the regulated pressure on port connection 2 will not be maintained and can be
discharged.
4. Product description:
The Series PME electronic pressure regulator is composed of:
•M12 5 pin connector (1): provides connection to power supply, command signal and to the
output digital signal (for more details refer to the paragraph “Installation and
Commissioning").
The analog version of the Series PME electronic pressure regulator is available with two
different command signal types:
•Analog Voltage: voltage command signal 0 - 10 V.
•Analog Current: current signal 4 - 20 mA.
The choice between the two models must be made when ordering the regulator.
The configuration of some features of the Series PME electronic pressure regulator is done
through the NFCamApp app.

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
6
5. Pneumatic simbol:
Version with integrated
exhaust valve and external
servo-pilot supply
Version with integrated
exhaust valve and internal
servo- pilot supply
3 ways N.C. version with external
servo-pilot supply
3 ways N.C. version with internal
servo- pilot supply

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
7
6. General characteristics and conditions of use
General characteristics and conditions of use
PME1
PME2
Reference standards
CE; RoHs
Materials
Body: Aluminum Cover: Technopolymer Seal:NBR and FKM
Assembly position
Any
Overall dimensions
L = 50 mm; W = 50 mm; H = 88 mm
L = 50 mm; W = 50 mm; H = 133 mm
Weight
350gr circa
630gr circa
Medium and its quality
Filtered and non-lubricated compressed air of class 7.4.4 according to
ISO 8573.1. Inert gases and oxygen only for OX1 versions.
Maximum free flow rate
(Pin 10 bar)
Measured at ±5% of Preg
Pout 6 bar: 1.100 l/min ANR (PRE104)
Pout 4 bar: 1.200 l/min ANR (PRE104)
Pout 6 bar: 4.500 l/min ANR (PRE238)
Pout 4 bar: 5.200 l/min ANR (PRE238)
Maximum system
pressure drop
50 cc/min
10 cc/min
Maximun inlet pressure
(refer to coding table)
11 bar (D); (G) and (F)
Regulated pressure range
0,05 - 10,3 bar (0,72-150 PSI)(D)
0,05 - 6 bar (0,72-87 PSI)(F) 0,05 - 7 bar (0,72-101,5 PSI) (G)
Number of ways
3
Ambient temperature
0 ÷ 50 °C
Protection class
IP65 (according to EN 60529)
Open-type (according to UL 61010)
Pneumatic ports
Standard version: G1/4, 1/4 NPTF
Manifold version: G1/4; 1/4 NPTF
Standard version: G1/4, G3/8
Manifold version: G1/4
Vibrations sine
According to EN 60068
part 2-6:2009-11 (table
B.1)
Frequency range: 10-500Hz
Displacement 0-peak: 0,75mm or 100 m/s2
Number of cycle: 10
Continuous shock
According to DIN EN
60068-2-27:2010-02 (table
A.1)
Peak acceleration: 150 m/s2
Duration: 11ms
Pulse shape: half sine
Electric port
M12 5 Pin Male A-key
Input signal setpoint
Analog version: 0÷10V (2), 4÷20 mA (4)
Electrical power supply
24Vdc ±10%
Current consumption
Max 0,110A in case of versions with valve function 3/2 way NC

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
8
Max 0,200A in case of versions with VS function
Hysteresis (*)
0,5% FS
0,7% FS
Repeatability (*)
0,4% FS
0,4% FS
Linearity (*)
0,3% FS
0,3% FS
Resolution (*)
0,3% FS
0,6% FS
Overpressure discharge
With relieving
Modularity
With Series MD
(*) measured with Inlet pressure = Maximum regulated pressure + 1bar and a volume
connected to the outlet without any loss.

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
9
•Efficiency curve
y = 0,1033x
0
1
2
3
4
5
6
7
8
9
10
11
010 20 30 40 50 60 70 80 90 100
Regulated pressure [bar]
Electrical control signal [%]
Efficiency curve 10,33 bar

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
10
•FLOW CHARTS SIZE 1 - Standard version (1/4G)
Typical curve of flow rate from 0,5 to 6 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 7 bar
Typical curve of flow rate from 0,5 to 7 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 8 bar
Typical curve of flow rate from 1 to 9 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 10 bar

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
11
•FLOW CHARTS SIZE 1 –Manifold version (1/4G)
Typical curve of flow rate from 0,5 to 6 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 7 bar
Typical curve of flow rate from 0,5 to 7 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 8 bar
Typical curve of flow rate from 1 to 9 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 10 bar
DECAY FACTOR
N° = number of regulators in manifold configuration
D(%) = relative percentage decay of the maximum flow rate
Note: the air inlet is only from one side, in case it should be on the
right and on the left, only consider the positions as from 1 ÷ 3..

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
12
•FLOW CHARTS SIZE 2 - Standard version (1/4G)
Typical curve of flow rate from 0,5 to 6 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 7 bar
Typical curve of flow rate from 0,5 to 7 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 8 bar
Typical curve of flow rate from 1 to 9 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 10 bar

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
13
•FLOW CHARTS SIZE 2 - Standard version (3/8G)
Typical curve of flow rate from 0,5 to 6 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 7 bar
Typical curve of flow rate from 0,5 to 7 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 8 bar
Typical curve of flow rate from 1 to 9 bar
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Inlet pressure 10 bar

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
14
•Step response (Values determined according to ISO 10094-1)
PME-104
Type of Dynamic tests
Dynamic Characteristics
No tank
Volume 0,4L
Volume 2L
Step 0% to 100%
Shifting Time [ms]
36
82
175
Response Time [ms]
260
372
1.261
Settling Time [ms]
179
247
934
Step 100% to 0%
Shifting Time [ms]
39
64
177
Response Time [ms]
678
957
4.152
Settling Time [ms]
470
708
3.170
PME-238
Type of Dynamic tests
Dynamic Characteristics
No tank
Volume 0,4L
Volume 2L
Step 0% to 100%
Shifting Time [ms]
60
60
95
Response Time [ms]
350
465
850
Settling Time [ms]
250
325
650
Step 100% to 0%
Shifting Time [ms]
60
60
80
Response Time [ms]
850
860
870
Settling Time [ms]
600
590
565

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
15
7. Electrical/Pneumatic circuit
8. Product storage and transport
•Adopt all measures possible to avoid accidental damage to the product during transport, and
when available use the original packaging.
•Observe the specified storage temperature range of -20 ÷ 70 °C.
9. Installation and start-up
•During unpacking, take great care not to damage the product.
•Check whether there are any faults caused by product transport or storage.
•Separate all packaging material to enable the recovery or disposal in accordance with current
standards in the country of use.
•Where possible avoid the risk of repeated pressure surges on the circuit where the
component is installed.
•The components must be fixed correctly using, where possible, the specific anchors and
ensuring that the fixture remains efficient even when the actuator is repeatedly used at a
high frequency and in the presence of strong vibrations.
•Once the component is installed, ensure that all air ways are securely connected to the
respective couplings.
•If the power supply is turned off, residual pressure may remain on the secondary side of the
regulators. The manufacturer must provide for additional exhaust components.
Recommended pneumatic circuit
•Keep the protective cap of the M12 connector until the regulator is completely installed.

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
16
•PME1 series electronic regulator can be connected to DIN rails using the relative elements
PCF-E520 fitted on the rear of the body using two M4 threaded holes.
•The Series PME electronic regulator can be directly fixed to a support using the 2 through
holes with diameter 4mm present on the body (not available in the PME1 manifold version).
•The PME electronic regulator can be fixed to the wall with the optional bracket code PRE-ST:
1. Fix the bracket to the wall with suitable screws
2. Connect the fittings G1/4; G3/8 or NPTF according to the PRE regulator size
3. Connect the regulator to the bracket with the two M4 x 55 screws supplied
•Make sure that the bracket is completely resting on the wall
•Connection of Manifold regulators with related Kit PRE-M-Pin-1-2
1. Insert the pins (1) in the seats on the regulator body
2. Insert the O-ring seal (3) into the special seat on the side face of the body
3. Bring the two modules sideways up until contact
4. Tighten the four grub screws (2) until they are locked (Tightening torque: 2,5 ± 0,5 Nm)

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
17
•There are 2 additional pneumatic ports on the PME series electronic regulator:
oM5 to discharge the exhaust valve to the outside. It is important to keep this port
free and clean to ensure that air is discharged without obstructions that could limit
the flow. If necessary, remove the pre-assembled filter, connect a suitable coupling
and use a hose to convey discharged air to a suitable area.
oM5 for external servo-pilot supply. The regulator is supplied with a preassembled cap
for the versions with internal servo-pilot supply and with the fitting 6625 3-M5 for
the versions with external servo-pilot supply.
•In order to connect the regulator with MD series, use the PRE-1/4-C kit for regulator with
G1/4 pneumatic port or use the PRE-3/8-C kit for regulator with G3/8 pneumatic port.
•The board implements a protection against inversion of polarity on the power supply
voltage.
•The board is also fitted with a non-resettable 1A fuse to limit the maximum current
absorption of the servovalve. Use a power supply unit able to deliver a current of at least
0,5A (recommended 1.0A).
•If UL/CSA standard compliance is required, the unit shall be supplied by an isolated power
source which fulfils at least one of the following the requirements of:
- Limited-Energy Circuit in accordance with UL/CSA 61010-1/ UL/CSA 61010-2-201
- Limited Power Source (LPS) in accordance with UL/CSA 60950-1
- a Class 2 supply source which complies with the National Electrical Code (NEC), NFPA 70,
Clause 725.121 and Canadian Electrical Code (CEC), Part I, C22.1. (typical examples are a
Class 2 transformer or a Class 2 power sources in compliance with, UL 5085-3/ CSA-C22.2
No. 66.3 or UL 1310/CSA-C22.2 No. 223). In order to respect the UL/CSA 61010
requirements, install the regulator inside a box, not in external environment.
•The power supply voltage must be within the range of 24V±10%.
•The board implements a protection against overload of the reference signal.
•The M12 8 pin male connector has the following pinout

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
18
•For the electrical connection the following cable types are available:
CODE
DESCRIPTION
CS-LF05HB-D200
co-moulded connector M12 5 pole, female, straight with 2-metre cable shielded
CS-LF05HB-D500
co-moulded connector M12 5 pole, female, straight with 5-metre cable shielded
CS-LR05HB-D200
co-moulded connector M12 5 pole, female, bend with 2-metre cable shielded
CS-LR05HB-D500
co-moulded connector M12 5 pole, female, bend with 5-metre cable shielded
CS-LR03HB-C200
co-moulded connector M12 5 pole 3 wires, female, bend with 2-metre cable unshielded
CS-LR03HB-C500
co-moulded connector M12 5 pole 3 wires, female, bend with 5-metre cable unshielded
NOTE: in the cable versions with 3 wires, only pins 1 (24 VDC), 4 (GND) and 3 (IN +) are available.
Pin 5 (Dout) is not available.
PIN
ANALOG
1
24 VDC
Power supply
Connect to the positive pole (24VDC) and to the negative pole (GND) of the power supply
4
GND
3
IN+
Input of voltage (0-10V) or current (4-20mA) reference signal
Connect to the positive pole of the reference signal generator.
Internal resistance with voltage input: >10kΩ. Use reference signal generator with low
impedance and with output current >1mA@10V.
Internal resistance with current input: 100Ω.
It is mandatory to connect all negative poles of the power supply and the reference signal
generator together.
2
N.C.
NOT CONNECTED
5
Dout
Digital output signal (0-24V)
Connect to a digital input. If the input is of the NPN type, use pin 1 (24VDC) as reference of
digital input; otherwise if the input is of the PNP type, use pin 2 (GND) as reference of digital
input. Output resistance: >15MΩ. Max current: 50mA.

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
19
10.Digital output
The digital output (OUT signal, pin 5) is a 0-24V digital signal. Through the NFCamApp
application it is possible to set the logic of this output:
•Active –high level: if the output is activated, its value is brought to a high logic level.
•Active –low level: if the output is activated, its value is brought to a low logic level.
Furthermore, based on the electrical connection made by the user, the following
configurations can be obtained:
•PNP: in this configuration the output signal refers to GND (pin 4), therefore the PNP digital
input of the control system must be connected between pin 5 (Dout) and pin 4 (GND).
•NPN: in this configuration the output signal refers to + 24V (pin 1), therefore the NPN digital
input of the control system must be connected between pin 5 (Dout) and pin 1 (+ 24V)
The operating mode of the digital output depends on what code is ordered. There are three
different operating modes:
•Error: the digital output changes state if the Regulator detects an error.
•Switch pressure: with this operating mode it is possible to set two fixed pressure thresholds,
a lower one and a higher one. The digital output changes state if the regulated pressure is
outside the range delimited by the two thresholds set. This is a useful way to check whether
the regulated pressure lies within the preset pressure range.
•Window pressure: with this operating mode it is possible to set two thresholds, a lower one
and a higher one, which determine a pressure range with respect to the target pressure
value.
The digital output changes state if the regulated pressure is outside the instantaneous range
(depending on the value of the target pressure at that moment) delimited by the two
thresholds set.
This is a useful way to check whether the regulated pressure lies within the pre-established
precision range.

Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
20
11.NFCamApp
NFCamApp is a configuration application that can be installed on android mobile device and
available on Play Store.
NFCamApp communicates with the Series PME electronic pressure regulator via NFC
connection and is able to configure the device.
Following the configurator of the Series PME electronic pressure regulator is described in
detail. For installation and use of the NFCamApp, please refer to the dedicated manual.
Other manuals for PME Series
1
This manual suits for next models
4
Table of contents
Other Camozzi Controllers manuals
Popular Controllers manuals by other brands

Festo
Festo VPPI S1BT Series operating instructions

Hanna Instruments
Hanna Instruments HI 720 instruction manual

Siemens
Siemens SIMATIC NET SPC 4-2 LF manual

Fuji Electric
Fuji Electric FRENIC-HVAC series instruction manual

Stahl
Stahl 8602/1 Series Modification Instructions

sisel
sisel ENDA EUP Series manual