Camozzi PME Series Instruction Manual

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
1
Operation and maintenance instructions for Series PME CANopen Electronic
proportional regulator
The products are designed and manufactured in conformity with the following directives:
-2014/30/UE “Electromagnetic compatibility”
They also comply partially or totally with regard to the applicable parts of the following standards:
-EN 61000-6-2:2005 Electromagnetic compatibility (EMC) —Part 6-2:
Generic standards - Immunity for industrial environments
-EN 61000-6-4:2007 Electromagnetic compatibility (EMC) —Part 6-4: Generic standards -
Emissions for industrial environments
-UL 61010-1: Safety requirements for electrical equipment for measurement, control and
laboratory use Part 1: General requirements and the following technical standards
and to the following technical standards:
-EN ISO 4414:2010 Pneumatics - General rules and safety requirements for systems and their
components.
For more information regarding the declarations of conformity, see the Certifications section
on the website http://catalogue.camozzi.com.
Made in Italy

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
2
Index
1. Product identification ..................................................................................................................5
2. Introduction .................................................................................................................................6
3. General recommendations ..........................................................................................................6
4. Product description......................................................................................................................7
5. Pneumatic symbol........................................................................................................................8
6. General characteristics and conditions of use.............................................................................9
7. Electrical/Pneumatic circuit.......................................................................................................17
8. Product storage and transport...................................................................................................17
9. Installation and start-up.............................................................................................................17
10. Device Configuration...............................................................................................................24
10.1. Information..........................................................................................................................25
10.2. Fieldbus ...............................................................................................................................26
10.3. Configurator ........................................................................................................................26
10.3.1. User setup........................................................................................................................27
10.3.2. K parameters....................................................................................................................29
10.3.3. Feedback setup................................................................................................................29
10.3.4. Specific device setup........................................................................................................30
10.3.5. Password..........................................................................................................................31
10.3.6. Saving parameters ...........................................................................................................31
11.CANopen pressure regulator ..................................................................................................32
11.1. Configuration via EDS file....................................................................................................32
11.2. Address and baud rate ........................................................................................................32
11.3. Object dictionary.................................................................................................................33
11.3.1. CiA 301 profile objects.....................................................................................................33
11.3.2. CiA 301 profile objects description..................................................................................40
11.3.2.1. 1000h Device type ...........................................................................................................40
11.3.2.2. 1001h Error register.........................................................................................................40
11.3.2.3. 1002h Manufacturer status register................................................................................40
11.3.2.4. 1003h Pre-defined error field..........................................................................................40
11.3.2.5. 1005h COB-ID sync ..........................................................................................................41

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
3
11.3.2.6. 1006h Communication cycle period................................................................................41
11.3.2.7. 1007h Synchronous window length ................................................................................41
11.3.2.8. 1008h Manufacturer device name ..................................................................................41
11.3.2.9. 1009h Manufacturer hardware version ..........................................................................41
11.3.2.10. 100Ah Manufacturer software version........................................................................41
11.3.2.11. 100Ch Guard time........................................................................................................42
11.3.2.12. 100Dh Life time factor .................................................................................................42
11.3.2.13. 1010h Store parameter field........................................................................................42
11.3.2.14. 1011h Restore default parameter ...............................................................................42
11.3.2.15. 1012h COIB-ID time stamp...........................................................................................42
11.3.2.16. 1014h COIB-ID EMCY....................................................................................................43
11.3.2.17. 1015h Inhibit time emergency.....................................................................................43
11.3.2.18. 1017h Producer heartbeat time ..................................................................................43
11.3.2.19. 1018h Identity object...................................................................................................43
11.3.2.20. 1019h Synchronous counter overflow value ...............................................................43
11.3.2.21. 1029h Error behaviour.................................................................................................44
11.3.2.22. 1200h Server SDO parameter 1 ...................................................................................44
11.3.2.23. 1400h –1407h Receive PDO Communication Parameter...........................................44
11.3.2.24. 1600h –1607h Receive PDO Mapping Parameter ......................................................45
11.3.2.25. 1800h –1807h Transmit PDO Communication Parameter .........................................45
11.3.2.26. 1A00h –1A07h Transmit PDO Mapping Parameter....................................................46
11.3.2.27. 1F80h NMT Startup......................................................................................................46
11.4. CiA 408 profile objects ........................................................................................................47
11.4.1. CiA 408 profile objects description..................................................................................47
11.4.1.1. 6040h Control Word........................................................................................................48
11.4.1.2. 6041h Status Word..........................................................................................................50
11.4.1.3. 6042h Device Mode.........................................................................................................50
11.4.1.4. 6043h Device control Mode ............................................................................................50
11.4.1.5. 604Fh Device Local ..........................................................................................................50
11.4.1.6. 6380h VRPC Setpoint.......................................................................................................50
11.4.1.7. 6381h VRPC Actual Value ................................................................................................51

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
4
11.5. Manufacturer Objects .........................................................................................................52
11.5.1. Manufacturer objects description...................................................................................53
11.5.1.1. 2001h Pressure regulation check mode..........................................................................53
11.5.1.2. 2002h Enable pressure regulation check ........................................................................53
11.5.1.3. 2003h Pressure regulation check timeout ......................................................................53
11.5.1.4. 2004h Pressure regulation protection timeout...............................................................53
11.5.1.5. 2007h Fail safe.................................................................................................................53
11.5.1.6. 2008h PID mode ..............................................................................................................53
11.5.1.7. 2009h PID Custom Parameter .........................................................................................54
11.5.1.8. 220Bh Numerator multiplier ...........................................................................................54
11.5.1.9. 220Ch Denumerator multiplier .......................................................................................54
11.5.1.10. 200Dh Error code.........................................................................................................54
11.5.1.11. 200Eh Dead band.........................................................................................................55
11.5.1.12. 200Fh Enable pressure switch control.........................................................................55
11.5.1.13. 2010h Lower limit switch control ................................................................................56
11.5.1.14. 2011h Upper limit switch control ................................................................................56
11.5.1.15. 2012h Enable pressure window control ......................................................................56
11.5.1.16. 2013h Lower limit window control..............................................................................57
11.5.1.17. 2014h Upper limit window control..............................................................................57
11.5.1.18. 2015h Use profile CiA 408............................................................................................57
11.5.1.19. 2016h Enable Termination Resistance.........................................................................57
11.5.1.20. 2017h Enable Emergency Transmission ......................................................................58
11.5.1.21. 2018h Hysteresis..........................................................................................................58
11.5.1.22. 2019h Internal sensor filter cutoff...............................................................................59
12. Diagnostic................................................................................................................................60
13. Use...........................................................................................................................................61
14. Limitations on use...................................................................................................................62
15. Maintenance ...........................................................................................................................62
16. Environmental notes...............................................................................................................62
17. Contacts ..................................................................................................................................64

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
5
1. Product identification

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
6
2. Introduction
This manual illustrates how to properly use the Series PME electronic pressure regulator with
CANopen interface.
This version of the Controller is identified with code 0214 xx xx xxx x xxxxx, where 0214 indicates
the version of regulator and is followed by year, week, machine, station and serial number.
3. General recommendations
The recommendations regarding safe use in this document should be observed at all times.
•Some hazards can only be associated with the product after it has been installed on the
machine/equipment. It is the task of the final user to identify these hazards and reduced the
associated risks accordingly.
•The products dealt with in this manual may be used in circuits that must comply with the
standard EN ISO 13849-1.
•For information regarding component reliability, contact Camozzi.
•Before proceeding with use of the product, carefully read all information in this document.
•The instructions in this manual must be observed together with the instructions and additional
information regarding the product in this manual, available from the following reference links:
oweb site http://www.camozzi.com
oCamozzi general catalogue
oTechnical assistance service
•Assembly and start-up operations must be performed exclusively by qualified and authorized
personnel on the basis of these instructions.
•It is the responsibility of the system/machine designer to ensure the correct selection of the
most suitable pneumatic component according to the intended application.
•For all situations not contemplated in this manual and in situations in which there is the risk of
potential damage to objects, or injury to persons or animals, contact Camozzi for advice.
•Never make unauthorized modifications to the product. In this case, any damage or injury to
objects, persons or animals will be the responsibility of the user.
•All relevant product safety standards must be observed at all times.
•Never intervene on the machine/system before verifying that all working conditions are safe.
•Before installation and maintenance, ensure that the specific envisaged safety locks are active,
and then disconnect the electrical mains (if necessary) and system pressure supply, discharging
all residual compressed air from the circuit and deactivating residual energy stored in springs,
condensers, recipients and gravity.
•To reduce the noise levels caused by the discharge of air from the component, envisage the use
of silencers or convey the fluid to a zone where no personnel are envisaged during normal
operation.
•Avoid covering the equipment with paint or other substances that may reduce heat dissipation.

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
7
•Avoid cleaning with aggressive agents such as to dull the plastics and make it difficult to read
the screen
•In the event of an electrical power failure and pneumatic supply at the port connection 1, the
regulated pressure on port connection 2 will not be maintained and can be discharged.
4. Product description
The Series PME electronic pressure regulator is composed of:
•M12 5 pin connector (1): provides connection to power supply and command signal (for more
details refer to the paragraph “Installation and Commissioning").
Only one version of PME CANopen is available.
The configuration of some features of the Series PME electronic pressure regulator and of CANopen
parameters is done through the NFCamApp app.

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
8
5. Pneumatic symbol
SIZE 1 AND 2
Version with internal servo-
pilot supply, two pilot valves
2/2 NC.
Version with external servo-
pilot supply, two pilot valves
2/2 NC.
Version with internal
servopilot supply and two
pilot valves; one 2/2 NC and
one 2/2 NO (exhaust).
Version with external
servopilot supply and two
pilot valves; one 2/2 NC and
one 2/2 NO (exhaust).
Version with internal servo-
pilot supply and two pilot
valves 2/2 NC, exhaust
conveyable.
Version with external
servopilot supply and two
pilot valves 2/2 NC, exhaust
conveyable.
Version with internal
servopilot supply and two
pilot valves; one 2/2 NC and
one 2/2 NO to exhaust,
exhaust conveyable.
Version with external
servopilot supply and two
pilot valves; one 2/2 NC and
one 2/2 NO to exhaust,
exhaust conveyable.
SIZE 1 AND 2 MANIFOLD
Manifold version with internal
servo-pilot supply and two
pilot valves 2/2 NC.
Manifold version with external
servo-pilot supply and two
pilot valves 2/2 NC.
Manifold version with internal
servo-pilot supply and two
pilot valves; one 2/2 NC and
one 2/2 NO to exhaust.
Manifold version with external
servo-pilot supply and two
pilot valves; one 2/2 NC and
one 2/2 NO to exhaust
Manifold version with internal
servo-pilot supply and two
pilot valves 2/2 NC and
exhaust conveyable.
Manifold version with external
servo-pilot supply and two
pilot valves 2/2 NC and
exhaust conveyable
Manifold version with internal
servo-pilot supply and two
pilot valves; one 2/2 NC and
one 2/2 NO to exhaust,
exhaust conveyable.
Manifold version with external
servo-pilot supply and two
pilot valves; one 2/2 NC and
one 2/2 NO to exhaust,
exhaust conveyable.

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
9
6. General characteristics and conditions of use
General characteristics and conditions of use
PME1
PME2
Reference standards
CE; RoHs
Materials
Body: Aluminum Cover: Technopolymer Seal:NBR and FKM
Assembly position
Any
Overall dimensions
L = 50 mm; W = 50 mm; H = 88 mm
L = 50 mm; W = 50 mm; H = 133
mm
Weight
350gr circa
630gr circa
Medium and its quality
Filtered and non-lubricated compressed air of class 7.4.4 according to
ISO 8573.1. Inert gases and oxygen only for OX1 versions.
Maximum free flow rate
(Pin 10 bar)
Measured at ±5% of Preg
Pout 6 bar: 1.100 l/min ANR (PRE104)
Pout 4 bar: 1.200 l/min ANR (PRE104)
Pout 6 bar: 4.500 l/min ANR (PRE238)
Pout 4 bar: 5.200 l/min ANR (PRE238)
Maximum system pressure
drops
20 cc/min
10 cc/min
Maximum inlet pressure
(refer to coding table)
11 bar (D); (G) and (F)
Regulated pressure range
0,05 - 10,3 bar (0,72-150 PSI)(D)
0,05 - 6 bar (0,72-87 PSI)(F) 0,05 - 7 bar (0,72-101,5 PSI) (G)
Number of ways
3
Ambient temperature
0 ÷ 50 °C
Protection class
IP65 (according to EN 60529)
Open-type (according to UL 61010)
Pneumatic ports
Standard version: G1/4; G1/8; 1/4 NPTF
Manifold version: G1/4; G1/8; 1/4 NPTF
Standard version: G1/4, G3/8
Manifold version: G1/4
Vibrations sine
According to EN 60068 part
2-6:2009-11 (table B.1)
Frequency range: 10-500Hz
Displacement 0-peak: 0,75mm or 100 m/s2
Number of cycles: 10
Continuous shock
According to DIN EN 60068-
2-27:2010-02 (table A.1)
Peak acceleration: 150 m/s2
Duration: 11ms
Pulse shape: half sine
Electric port
M12 5 Pin Male A-key
Input signal setpoint
CANopen profile Cia301 and Cia408 (optional)
Factory values
Address: 127; Baud Rate: 1Mbps; Unit of measure for pressure: mBar

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
10
Electrical power supply
12 -10% 24 +10% Vdc
Current consumption
Max 0,250A (refer to the table below for more details)
Hysteresis (*)
0,5% FS
0,7% FS
Repeatability (*)
0,4% FS
0,4% FS
Linearity (*)
0,3% FS
0,3% FS
Resolution (*)
0,3% FS
0,6% FS
Overpressure discharge
With relieving
Modularity
With Series MD
(*) measured with Inlet pressure = Maximum regulated pressure + 1bar and a volume
connected to the outlet without any loss.
Integrated
exaust valve
Code
Maximum current
consumption
NO
PMExxx-Ex5xxx-xx
PMExxx-Ex7xxx-xx
0,150 A
SI
PMExxx-Ex6xxx-xx
PMExxx-Ex8xxx-xx
0,200 A
•Efficiency curve
y = 0,1033x
0
1
2
3
4
5
6
7
8
9
10
11
010 20 30 40 50 60 70 80 90 100
Regulated pressure [bar]
Electrical control signal [%]
Efficiency curve 10,33 bar

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
11
•FLOW CHARTS SIZE 1 - Standard version (1/4G)
Typical curve for version PME104-EF…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Typical curve for version PME104-EG…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Typical curve for version PME104-ED…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
12
•FLOW CHARTS SIZE 1 –Manifold version (1/4G)
Typical curve for version PME1M4-EF…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Typical curve for version PME104-EG…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Typical curve for version PME104-ED…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
DECAY FACTOR FOR MANIFOLD REGULATOR SIZE 1
N° = number of regulators in manifold configuration
% = relative percentage decay of the maximum flow rate
Note: the air inlet is only from one side, in case it should be on the
right and on the left, only consider the positions as from 1 ÷ 3..

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
13
•FLOW CHARTS SIZE 2 - Standard version (1/4G)
Typical curve for version PME204-EF…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Typical curve for version PME204-EG…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Typical curve for version PME204-ED…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
14
•FLOW CHARTS SIZE 2 - Standard version (3/8G)
Typical curve for version PME238-EF…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Typical curve for version PME238-EG…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Typical curve for version PME238-ED…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
15
•FLOW CHARTS SIZE 2 –Manifold version (1/4G)
Typical curve for version PME2M4-EF…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Typical curve for version PME204-EG…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
Typical curve for version PME204-ED…
P = Regulated outlet pressure and exhaust pressure
Q = Flow
% = Percentage of the command signal
DECAY FACTOR FOR MANIFOLD REGULATOR SIZE 2
N° = number of regulators in manifold configuration
% = relative percentage decay of the maximum flow rate
Note: the air inlet is only from one side, in case it should be on the
right and on the left, only consider the positions as from 1 ÷ 3..

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
16
•Step response (Values determined according to ISO 10094-1)
PME-104
Type of Dynamic tests
Dynamic Characteristics
No tank
Volume 0,4L
Volume 2L
Step 0% to 100%
Shifting Time [ms]
36
82
175
Response Time [ms]
260
372
1.261
Settling Time [ms]
179
247
934
Step 100% to 0%
Shifting Time [ms]
39
64
177
Response Time [ms]
678
957
4.152
Settling Time [ms]
470
708
3.170
PME-238
Type of Dynamic tests
Dynamic Characteristics
No tank
Volume 0,4L
Volume 2L
Step 0% to 100%
Shifting Time [ms]
60
60
95
Response Time [ms]
350
465
850
Settling Time [ms]
250
325
650
Step 100% to 0%
Shifting Time [ms]
60
60
80
Response Time [ms]
850
860
870
Settling Time [ms]
600
590
565

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
17
7. Electrical/Pneumatic circuit
8. Product storage and transport
•Adopt all measures possible to avoid accidental damage to the product during transport, and
when available use the original packaging.
•Observe the specified storage temperature range of -20 ÷ 70 °C.
9. Installation and start-up
•During unpacking, take great care not to damage the product.
•Check whether there are any faults caused by product transport or storage.
•Separate all packaging material to enable the recovery or disposal in accordance with current
standards in the country of use.
•Where possible avoid the risk of repeated pressure surges on the circuit where the component
is installed.
•The components must be fixed correctly using, where possible, the specific anchors and ensuring
that the fixture remains efficient even when the actuator is repeatedly used at a high frequency
and in the presence of strong vibrations.
•Once the component is installed, ensure that all air ways are securely connected to the
respective couplings.
•If the power supply is turned off, residual pressure may remain on the secondary side of the
regulators. The manufacturer must provide for additional exhaust components.
Recommended pneumatic circuit
•Keep the protective cap of the M12 connector until the regulator is completely installed.

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
18
•PME1 series electronic regulator can be connected to DIN rails using the relative elements PCF-
E520 fitted on the rear of the body using two M4 threaded holes.
•The Series PME electronic regulator can be directly fixed to a support using the 2 through holes
with diameter 4mm present on the body (not available in the PME1 manifold version).
•The PME electronic regulator can be fixed to the wall with the optional bracket code PRE-ST:
1. Fix the bracket to the wall with suitable screws
2. Connect the fittings G1/4; G3/8 or NPTF according to the PRE regulator size
3. Connect the regulator to the bracket with the two M4 x 55 screws supplied
•Make sure that the bracket is completely resting on the wall
•Connection of Manifold regulators with related Kit PRE-M-Pin-1-2
1. Insert the pins (1) in the seats on the regulator body
2. Insert the O-ring seal (3) into the special seat on the side face of the body
3. Bring the two modules sideways up until contact
4. Tighten the four grub screws (2) until they are locked (Tightening torque: 2,5 ± 0,5 Nm)

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
19
•There are 2 additional pneumatic ports on the PME series electronic regulator:
oM5 to discharge the exhaust valve to the outside. It is important to keep this port free and
clean to ensure that air is discharged without obstructions that could limit the flow. If
necessary, only for version with conveyable port, remove the pre-assembled filter, connect
a suitable coupling and use a hose to convey discharged air to a suitable area.
oM5 for external servo-pilot supply. The regulator is supplied with a preassembled cap for
the versions with internal servo-pilot supply and with the fitting 6625 3-M5 for the versions
with external servo-pilot supply.
•In order to connect the regulator with MD series, use the PRE-1/4-C kit for regulator with G1/4
pneumatic port or use the PRE-3/8-C kit for regulator with G3/8 pneumatic port.
•The board implements a protection against inversion of polarity on the power supply voltage.
•The board is also fitted with a non-resettable 1A fuse to limit the maximum current absorption
of the servovalve. Use a power supply unit able to deliver a current of at least 0,5A
(recommended 1.0A).
•If UL/CSA standard compliance is required, the unit shall be supplied by an isolated power source
which fulfils at least one of the following the requirements of:
- Limited-Energy Circuit in accordance with UL/CSA 61010-1/ UL/CSA 61010-2-201
- Limited Power Source (LPS) in accordance with UL/CSA 60950-1
- a Class 2 supply source which complies with the National Electrical Code (NEC), NFPA 70, Clause
725.121 and Canadian Electrical Code (CEC), Part I, C22.1. (typical examples are a Class 2
transformer or a Class 2 power sources in compliance with, UL 5085-3/ CSA-C22.2 No. 66.3 or
UL 1310/CSA-C22.2 No. 223). In order to respect the UL/CSA 61010 requirements, install the
regulator inside a box, not in external environment.
If the equipment is used in a manner not specified by the manufacturer, the protection provided
by the equipment may be impaired.
•The power supply voltage must be within the range of 24V±10%.
•The board implements a protection against overload of the reference signal.
•The M12 5 pin male connector has the following pinout

Operation and maintenance instructions
Series PME CANopen proportional pressure
regulator
5000054187
Ver. 01
20
N.B. For the electrical connection the following cable types are available:
CODE
DESCRIPTION
CS-LF05HB-D200
Overmolded connector M12 5 poles female straight 2 mt cable shielded
CS-LF05HB-D500
Overmolded connector M12 5 poles female straight 5 mt cable shielded
CS-LF05HB-C200
Overmolded connector M12 5 poles female straight 2 mt cable unshielded
CS-LF05HB-C500
Overmolded connector M12 5 poles female straight 5 mt cable unshielded
CS-LR05HB-D200
Overmolded connector M12 5 poles female angled 2 mt cable shielded
CS-LR05HB-D200
Overmolded connector M12 5 poles female angled 5 mt cable shielded
CS-LR05HB-C200
Overmolded connector M12 5 poles female angled 2 mt cable unshielded
CS-LR05HB-C200
Overmolded connector M12 5 poles female angled 5 mt cable unshielded
CS-AA08EC
4-ways T connector for BUS-IN and BUS-OUT
CS-AA05EC
3-ways T connector for BUS-IN and BUS-OUT
PIN
NAME
DESCRIPTION
SYMBOL
1
NC
Not connected
2
V+
Power supply: connect to the positive pole of the
power supply (referred to GND)
3
GND
Ground (referred to pin 2): connect to the negative
pole of the power supply
4
CAN_H
CAN H bus line
5
CAN_L
CAN L bus line