Cansec SmartLock Pro User manual

SmartLock®Pro
INSTALLATION MANUAL
April 2009

SmartLock®Pro Page 2 of 29
Installation Manual April 2009 • Rev. 1.7
Table of Contents
INTRODUCTION ....................................................................................................................... 3
Diodes............................................................................................................................ 3
Power Supply Notice...................................................................................................... 3
Terminal Strips and Cable.............................................................................................. 4
SPECIFICATIONS..................................................................................................................... 5
SMARTLOCK CONTROLLER LAYOUT................................................................................... 7
LED Indicators................................................................................................................ 8
Mounting ........................................................................................................................ 8
RS-485 COMMUNICATIONS WIRING ...................................................................................... 9
CLAUSB Communications Device.................................................................................10
CANLAN Network Communications Device...................................................................11
SMARTLOCK CONNECT WIRING ..........................................................................................12
Modem Configuration (Dial-Up).....................................................................................12
Remote End (Dial-Up)...................................................................................................12
Programming module (Stand-Alone) .............................................................................13
READER WIRING ....................................................................................................................14
Wiegand Reader ...........................................................................................................14
iButton®Reader.............................................................................................................15
LOCK OUTPUT RELAY WIRING.............................................................................................16
DC Electric Strikes.........................................................................................................16
DC MagLocks................................................................................................................17
AC MagLocks and AC Electric Strikes...........................................................................18
INPUT WIRING.........................................................................................................................19
Exit Button, Handicap Button, Door Contact..................................................................19
OUTPUT WIRING.....................................................................................................................20
Door Operator, Forced Entry, Door-Held-Open .............................................................20
DIP SWITCH.............................................................................................................................21
Function ........................................................................................................................21
Location.........................................................................................................................21
Erase Controller Memory, Diagnostics...........................................................................22
Door Contact Bypass Switch Setting .............................................................................23
Set Address For SmartLock Connect (Stand-Alone)......................................................24
CONTROLLER ADDRESS TABLE..........................................................................................25
APPENDIX ...............................................................................................................................28
CLA50 Communications Wiring.....................................................................................28

SmartLock®Pro Page 3 of 29
Installation Manual April 2009 • Rev. 1.7
Introduction
The SmartLock®Pro access control panel is a single door controller with
inputs for both entry and exit readers. Readers and card formats supported
include standard 26-bit and 37-bit (Cansec) Wiegand formats, and Cansec
iButton®credentials. Other card formats can be accommodated with the use
of Cansec Protocol Converters (contact Cansec for further information).
SmartLock controllers can be used with SmartLock Pro, SmartLock Connect
and SmartLock Online software (SmartLock Online requires legacy firmware;
controller ordered as CA-SOLCTRL).
The SmartLock control panel stores all cardholder data in non-volatile
memory to ensure continued operation and security in the event that
communications are lost to the host PC. Up to two control panels are easily
mounted in a SmartLock enclosure along with a Cansec 12 VDC power
supply and a back-up battery.
DIODES
Diodes are required for inductive loads such as electric strikes/locks. Failure
to use appropriate diodes will void the control panel warranty.
POWER SUPPLY NOTICE
In some jurisdictions, the use of a UL approved power supply and
connection to the fire alarm system for emergency release may be required.
Installers should contact the local authority having jurisdiction to verify the
specific requirements. Also, a building permit may be required in some
jurisdictions for the installation of maglocks.

SmartLock®Pro Page 4 of 29
Installation Manual April 2009 • Rev. 1.7
TERMINAL STRIPS AND CABLE
Use Appropriate Cable Thickness
For optimal performance and communication, the terminal strips on the
SmartLock control panel are designed to be used with 26 –18 American
Wire Gauge (AWG) stranded, overall-shielded, twisted-pair cable. This is
equivalent to Belden 88761 or similar cable.
Use MARR Connectors
If you are bringing in cable that is too large for the terminal
strip, use a MARR connector (wire nut, marrette, thimble
connector, cone connector). Splice the thicker cable to a cable
that is the appropriate thickness, and then run the thinner
cable to the terminal strip on the control panel.
Use Splices for Parallel Wiring
The terminal strips are designed to allow one cable per hole.
If you need to connect multiple cables in a single hole, use a
MARR connector (wire nut, marrette, thimble connector,
cone connector). Splice multiple cables to a single cable, and
then run the single cable to the terminal strip on the control
panel.
Complimentary Screwdriver
A standard Cansec screwdriver is included with every control
panel for use with terminal strips.

SmartLock®Pro Page 5 of 29
Installation Manual April 2009 • Rev. 1.7
Specifications
Power Requirements
SmartLock®Controller: ............................................ 12 VDC, 100 mA
NOTE: When determining power supply current requirements, you must consider lock
and reader current draw if using the same supply for these devices.
NOTE: In some jurisdictions, the use of a UL approved power supply and connection
to the fire alarm system for emergency release may be required. Installers should
contact the local authority having jurisdiction to verify the specific requirements. Also,
a building permit may be required in some jurisdictions for the installation of
maglocks.
Communications Cable (multi-drop configuration)
RS-485 Cable: ...................22 AWG, Stranded/Shielded, Twisted Pair
............................................................. 609 m (2000 ft) max total length
.....................................................................Belden 88761 or equivalent
On-Board Outputs
Lock Control: ................................... Form “C”, Rated @ 30 VDC, 1A
Door Operator: ................................. Form “C”, Rated @ 30 VDC, 1A
Forced/DHO Relays: ....................... Form “C”, Rated @ 30 VDC, 1A
On-Board Inputs
Exit Button: ....................................................................Normally Open
Door Contact:...............................................................Normally Closed
Door Operator:...............................................................Normally Open
...........................................................................................................................

SmartLock®Pro Page 6 of 29
Installation Manual April 2009 • Rev. 1.7
Reader Cable
Wiegand Readers:.................... 6 conductor (twisted pair not required)
............................................................................22 AWG, overall shield
............................................................... 152 m (500 ft)max total length
iButton®Readers:............................................................... 6 conductors
............................................................22 AWG, shielded or unshielded
................................................................... 15 m (50 ft) max total length
Dimensions & Weight
Controller Board: ...............................................84 mm (l) x 65 mm (w)
....................................................................... [ 3 5/16” (l) x 2 9/16” (w) ]
SmartLock Cabinet:.................. 260 mm (l) x 216 mm (w) x 80 mm (h)
....................................................... [ 10 1/4” (l) x 8 1/2” (w) x 3 1/8” (h) ]
Weight: ...............................................................................2 kg (4.5 lbs)
Specifications subject to change without notice.

SmartLock®Pro Page 7 of 29
Installation Manual April 2009 • Rev. 1.7
SmartLock Controller Layout
1 2 3 4 5 6 7 8
ON
WIEGAND
DATA LED
COMMS
LED
OFF
ON
81
+5V
+12V
N/O
N/C
N/O N/O
N/C N/C
+12 VDC
INPUT
EXIT READER
(WIEGAND)
ENTRY READER
(WIEGAND)
ENTRY READER
or
PROGRAMMING MODULE
(iBUTTON)
DOOR CONTACT
EXIT BUTTON
DOOR OPERATOR
(INPUTS)
LOCK CONTROL
DOOR OPERATOR
FORCED/HELD OPEN
(OUTPUTS)
RS-485
COMMUNICATIONS
RELAY LEDS
ADDRESS
SWITCH
READER VOLTAGE
SELECTOR
DEFAULT
(DO NOT CHANGE)
LOCK
FORCED
/ DHO
DOOR
OPER.
Important Notes:
1. Each controller must have a unique address.
Refer to the Controller Address Table.
2. Exit reader must be Wiegand only. Native iButton®reader not supported
for exit.
3. Before connecting readers with power ON, make sure Reader Voltage
Selection Jumper is set to proper voltage for reader, otherwise the reader
may be damaged.
4. Do NOT connect power to any inputs on the controller.
5. The Door Contact Input should be bypassed, if not used, by using a
jumper wire across the input or setting the switch to ignore the input. Refer
to the Door Contact Bypass Switch Setting.
6. This controller utilizes “self-resetting” fuses. There are no field-serviceable
parts.

SmartLock®Pro Page 8 of 29
Installation Manual April 2009 • Rev. 1.7
LED INDICATORS
1. Relay LEDs turn RED when the corresponding relay is ON or
ACTIVATED.
2. The Wiegand data LED is normally ON and briefly flickers when valid
Wiegand data is received from the reader. If Wiegand data is not valid
or not supported, this LED will stay OFF until the next valid card is
read.
3. The communication LED will flicker GREEN while communicating
with SmartLock software.
MOUNTING
Up to two SmartLock controllers can be mounted in the SmartLock
enclosure along with a Cansec 12 VDC power supply and a backup battery.

SmartLock®Pro Page 9 of 29
Installation Manual April 2009 • Rev. 1.7
RS-485 Communications Wiring
Up to 30 SmartLock access control panels may be connected on an RS-485
bus. An additional 30 control panels may be connected via a Cansec
communications device.
NOTE: For CLA50 communications device wiring (for use with SmartLock
Connect dial-up configurations) please see Appendix I.

SmartLock®Pro Page 10 of 29
Installation Manual April 2009 • Rev. 1.7
CLAUSB COMMUNICATIONS DEVICE
1 2 3 4 5 6 7 8
ON
COMMS
LED
SMARTLOCK
CONTROLLER
#1
6 5 4 3 2 1
Serial
SW
USB
PWR
RxD
TxD
1 2 3 4
ON
RS-485
DIPSWITCH
SETTINGS
TO USB PORT
(CABLE SUPPLIED)
SHIELD
B A GND
GND
+12 VDC
SMARTLOCK
CONTROLLER
#2
ON
81
+5V
+12V
N/O
N/C
OFF
N/C N/C
N/O N/O
- Each Smartlock controller must
have a unique address
- For communication wiring, use 22
AWG, twisted pair, stranded,
shielded cable, 2000 ft ( ) MAX
total length. 609 m
- Use the CLAUSB factory default
jumper settings for communications
with Smartlock controllers.
open the CLAUSB and change the
jumper settings.
DO NOT
NOTES:
CLAUSB
ADDRESS “1” SHOWN
(Dipswitch 1 is OFF)
ON
OFF
ON
8 1
+5V
+12V
ADDRESS
SWITCH
B A GND
B A GND
TO OTHER
SMARTLOCK
CONTROLLERS
- 30 CONTROLLERS MAXIMUM
- 609 m (2000 ft.) MAXIMUM LENGTH
SHIELD
GND
+12 VDC

SmartLock®Pro Page 11 of 29
Installation Manual April 2009 • Rev. 1.7
CANLAN NETWORK COMMUNICATIONS DEVICE
1 2 3 4 5 6 7 8
ON
COMMS
LED
RS-485
SHIELD
B A GND
GND
+12 VDC
ON
81
+5V
+12V
N/O
N/C
OFF
N/C N/C
N/O N/O
- Each Smartlock controller must
have a unique address
- For communication wiring, use 22
AWG, twisted pair, stranded,
shielded cable, 2000ft ( ) MAX
total length. 609 m
- Canlan needs to be configured for
RS-485 communications. Refer to
the Canlan Installation and
Configuration guide for details.
NOTES:
ADDRESS “1” SHOWN
(Dipswitch 1 is OFF)
CANLAN
TCP\IP CONTROLLER
SMARTLOCK
CONTROLLER
#1
ON
OFF
ON
8 1
+5V
+12V
ADDRESS
SWITCH
B A GND
B A GND
SHIELD
GND
+12 VDC
SMARTLOCK
CONTROLLER
#2
TO OTHER
SMARTLOCK
CONTROLLERS
- 30 CONTROLLERS MAXIMUM
- 609 m (2000 ft.) MAXIMUM LENGTH

SmartLock®Pro Page 12 of 29
Installation Manual April 2009 • Rev. 1.7
SmartLock Connect Wiring
MODEM CONFIGURATION (DIAL-UP)
CLA50
RS-485
TO CONTROLLERS
CANSEC MODEMS CUSTOM MODEM CABLE
PART # CA-SOMOCAB
REMOTE END (DIAL-UP)
1 2 3 4 5 6 7 8
ON
COMMS
LED
RS-485
B A GND
GND
+12 VDC
ON
81
+5V
+12V
N/O
N/C
OFF
N/C N/C
N/O N/O
ADDRESS “1” SHOWN
(Dipswitch 1 is OFF)
A
B
GND
SHIELD
12 VDC PLUG IN
TRANSFORMER
2.1 mm PLUG,
CENTRE POSITIVE
(SUPPLIED)
CUSTOM
MODEM CABLE
PART # CA-SOMOCAB
CLA50
CANSEC MODEM
TO OTHER
SMARTLOCK
CONTROLLERS
- 30 CONTROLLERS MAXIMUM
- 609 m (2000 ft.) MAXIMUM LENGTH
SHIELD
SMARTLOCK
CONTROLLER
#2
B A GND
B A GND
SHIELD
ON
OFF
ON
81
+5V
ADDRESS
SWITCH
+12V
SMARTLOCK
CONTROLLER
#1
GND
+12 VDC

SmartLock®Pro Page 13 of 29
Installation Manual April 2009 • Rev. 1.7
PROGRAMMING MODULE (STAND-ALONE)
NOTES:
The stand-alone programming module must be installed within 50 feet
of the SmartLock controller in a location accessible for programming
using the portable programming key.
The programming module should be installed on the secure side of the
door in a dry location.
If an iButton®reader is being used, wire it to the same reader port in
parallel with the programming module.
The programming module comes in a plastic box. Drill the required
holes for mounting and feed the cable through the cable feed-through.
See the SmartLock Connect Operator Guide for complete instructions on
programming using the portable programming key.
+5V
+12V
N/O
N/C N/C N/C
N/O N/O
VCC
BEEP
RED LED
GREEN LED
TK
GND
1 2 3 4 5 6 7 8
ONOFF
DIP SWITCH POSITIONS THROUGH
MUST BE FOR STAND-ALONE OPERATION
16
ON
CABLE: 22 AWG, 6 CONDUCTOR,
STRANDED, 50 ft (15m) MAX LENGTH
GND
+12 VDC

SmartLock®Pro Page 14 of 29
Installation Manual April 2009 • Rev. 1.7
+VDC
GND
BEEPER
GREEN LED
D1
D0
+VDC
GND
BEEPER
GREEN LED
D1
D0
GND
+12 VDC
EXIT READER
*OPTIONAL
**CONTROLS ENTRY READER LOCK
ENTRY READER
SET READER
VOLTAGE
1 2 3 4 5 6 7 8
ON
ON
81
+5V
+12V
N/O
N/C
OFF
N/C N/C
N/O N/O
WIEGAND
DATA LED
Reader Wiring
WIEGAND READER
IMPORTANT: Before applying power to the controller, verify that the
reader voltage jumper is set correctly for the reader being connected.
Connecting a 5 V reader to a 12 V power supply will damage the reader.
NOTE: The SmartLock®controller supports Cansec’s 37-bit format as well as
standard 26-bit format.
CABLE: 22 AWG, 6 CONDUCTORS,
NON-TWISTED PAIR, OVERALL
SHIELDED, MAX. DISTANCE IS
500ft (152 m).

SmartLock®Pro Page 15 of 29
Installation Manual April 2009 • Rev. 1.7
iBUTTON®READER
NOTE: Exit reader not supported with SmartLock iButton readers.
NOTE: If using the SmartLock Connect Programming Module with iButton
readers, connect the programming module in parallel with the iButton
reader.

SmartLock®Pro Page 16 of 29
Installation Manual April 2009 • Rev. 1.7
Lock Output Relay Wiring
DC ELECTRIC STRIKES
NOTE: Use 1N400x series diode as shown, to prevent “back EMF” from
damaging the controller.
Option 1
≤250mA
Option 2
> 250mA

SmartLock®Pro Page 17 of 29
Installation Manual April 2009 • Rev. 1.7
DC MAGLOCKS
NOTE: Use 1N400x series diode as shown to prevent “back EMF” from
damaging the controller if the maglock is not equipped with sufficient spike
and surge protection. Check the maglock specifications for details.
Option 1
≤250mA
Option 2
> 250mA

SmartLock®Pro Page 18 of 29
Installation Manual April 2009 • Rev. 1.7
AC MAGLOCKS AND AC ELECTRIC STRIKES

SmartLock®Pro Page 19 of 29
Installation Manual April 2009 • Rev. 1.7
Input Wiring
EXIT BUTTON, HANDICAP BUTTON, DOOR CONTACT
NOTE:DO NOT apply power or attempt to switch any current through
these inputs as this will result in damage to the controller.
NOTE: If not connecting a door contact, make sure you set switch position 8
to ON (right in orientation show) to bypass/disable the door contact input.
Otherwise, the door will be in alarm condition.
NOTE: Exit Button requires momentary closure to activate relay. Door
Contact is used for forced-entry and door-held-open annunciation, and also
deactivates the lock relay when the door closes.
1 2 3 4 5 6 7 8
ON
EXIT BUTTON
- NORMALLY OPEN
- MOMENTARY TO
ACTIVATE
HANDICAP BUTTON
- NORMALLY OPEN
- MOMENTARY TO ACTIVATE
- ENABLED ONLYAFTER
VALID CARD OR
EXIT BUTTON
DOOR CONTACT
- NORMALLY CLOSE
EXIT
HC
DC
IF YOUARE CONNECTINGA DOOR CONTACT
SET DIP SWITCH 8 TO OFF (LEFT)
IF YOU ARE CONNECTING A DOOR CONTACT
SET DIP SWITCH 8 ON (RIGHT)
NOT
OFF

SmartLock®Pro Page 20 of 29
Installation Manual April 2009 • Rev. 1.7
Output Wiring
DOOR OPERATOR, FORCED ENTRY, DOOR-HELD-OPEN
Use dry contact relays.
NOTE: Maximum power through any of these relays is 30 VDC at 1 A.
NOTE: Door Operator requires momentary closure to activate relay.
1 2 3 4 5 6 7 8
ON
OFF
ON
81
+5V
+12V
N/O
N/C
N/O N/O
N/C N/C
SET RELAY CONTACTS
= N/O = N/C
LOCK
DOOR
OPER.
FORCED
/ DHO
RELAY LEDS TURN
ON ACTIVATION
RED
DOOR OPERATOR OUTPUT
ACTIVATED MOMENTARILY WHEN
HANDICAP BUTTON IS DEPRESSED
AFTER LOCK RELAY IS ACTIVATED.
FORCED ENTRY/DHO OUTPUT
ACTIVATED ON FORCED ENTRYAND/OR
DHO ALARM AS CONFIGURED IN SOFTWARE
N/O: RELAY CLOSES ON
ACTIVATION
N/C: RELAY OPENS ON
ACTIVATION
Table of contents
Other Cansec IP Access Controllers manuals
Popular IP Access Controllers manuals by other brands

Belco Security
Belco Security DA3000 user manual

Rosslare
Rosslare AY-B86 0 Series user guide

Roger
Roger PR302 installation guide

BFT
BFT COMPASS SC-RS 232 Installation and user manual

TH COMMUNICATIONS
TH COMMUNICATIONS MZ10D7 quick start guide

Third Millennium
Third Millennium OSDP RX Series installation guide