
Model 201CRD & 301CRD Advanced oil burners — Instruction manual
Carlin part number MN2301 Rev. 04/12/04 – 19 –
Start-up & operation
Do not start the burner if the combustion chamber contains oil or
oil vapor.
Per UL requirements, the control will not turn on if the cad cell
senses flame during the self-test. If the cad cell sees light, the
control will remain in self-test mode until the cad cell no longer
senses light (flame). The amber LED will remain on, but blink off
momentarily every 3 to 4 seconds.
Model 50200 diagnostic LED’s
– Red OFF – Red ON – Red FLASHING
– Amber OFF – Amber ON – Amber FLASHING
– Amber BLINKING (blinks off momentarily every 3 to 4 seconds)
Service & Troubleshooting
Burner (control) will not come on
No power to control
• Check line voltage to the control (at least 102 VAC).
• Check all electrical connections.
Control is in lockout
• Red LED will be on. Press the reset button for 1 second.
• If the control returns immediately to lockout, The Safety
Monitoring Circuit may have detected an internal control
problem. Replace the control.
CAD cell seeing light
• Amber LED blinks off each 3 to 4 seconds. Remove one
yellow lead from FF terminal on the control.
If the amber LED remains on with a wire detached, the
control is defective.
If amber LED goes off , control is OK, and:
• light is leaking into the burner housing, OR
• CAD cell is defective, OR
• there is a problem with the CAD cell wiring or holder.
• If appliance was recently shut down, CAD cell may see
residual hot spots in chamber.
To troubleshoot:
• Check CAD cell by unplugging it and measuring the
resistance across its pins: dark resistance at least 50
KOHMS; room light resistance less than 10 KOHMS. Re-
place if necessary. If the CAD cell functions properly,
reinstall the cell and close the burner housing.
• Check for stray light by measuring the CAD cell resis-
tance looking into the inactive combustion chamber.
It should read at least 50 KOHMS.
Repeated flame failures ( flashing red LED)
Check for:
• CAD cell is defective.
• Air leaking into oil line causing flame out — Check oil line
connections and filter gasket.
• Defective nozzle causing flame to be erratic — Change
nozzle.
• Excessive airflow or draft causing flame to leave burner head
— Check for proper air shutter setting and draft.
• Excessive back pressure causing flame to be erratic — Check
appliance and flue for sooting/plugging.
Control locks out after TFI ( red LED on)
Check for:
• No oil to burner — Check oil supply, filter, lines.
• Shorted electrodes — Inspect for cracked porcelain and
replace as needed.
• Poor spark — Check electrode spacing and condition per
burner manual. Replace or realign if necessary.
• Nozzle clogged — Replace nozzle.
• Airflow too high — Check air shutter setting.
• Ignitor module defective — Replace if no spark.
• CAD cell defective.
• Oil valve stuck in closed position.
• Check wiring connections.
Power ON Open all manual oil line valves. Close the line switch. (If Red light
turns on constant , control is in lockout. See below to reset.)
Self-test 1 Each time the limit circuit sends power to the black wire, the
control performs a “boot-up” test to verify internal operation.
About 4 seconds after power application, the amber LED turns on.
The test continues for about 6 more seconds. If the test fails, the
control turns the amber LED off and repeats this test sequence until
successful. (This test occurs on every call for heat cycle if burner is
operated by a limit control (terminals “T-T” jumpered).
Stand-by (Thermostat circuit open, limit circuit closed) If Self-test 1 is
successful, amber LED turns off and control waits for thermostat
circuit to close.
Call for heat Set thermostat to call for heat. Thermostat circuit must close (and
black wire must receive power from the limit circuit).
Self-test 2 The amber LED turns on. For the first 3 to 4 seconds, the control
performs a self-test. If the cad cell senses flame, the control
repeats this test until flame is no longer detected. During this time,
the amber LED remains on, but blinks off momentarily every 3
to 4 seconds. If the control detects motor contacts closed, lockout
occurs.
Burner on After the self-test, amber LED turns off. The ignitor starts, followed
1 second later by the motor. The electronic time delay relay allows
the oil valve to open 4 seconds later.
TFI The cad cell must sense flame within the TFI time limit (trial for
ignition). After cad cell senses flame, the ignitor stays on another
10 seconds (flame stabilization period).
Run The burner continues firing during call for heat if the cad cell
senses flame. LED’s are off during normal running.
Lockout If cad cell does not sense flame within 15 seconds after burner
starts, lockout occurs. The control turns the red LED on constant,
and closes the alarm contact.
To Reset Push in and hold reset button for 1 second, then release.
Latch-up If the control locks out 3 times during a single call for heat, latch-
up occurs. The control turns on both the amber and red LED’s
constant. You must use the special procedure below to reset the
control after latch-up.
Reset after latch-up — Only a qualified service technician should
attempt to reset the control after latch-up. The problem that
caused the repeated burner problems must be corrected before
returning the burner to normal operation.
Push in and hold the reset button for about 10 seconds. The amber
and red LED’s will begin to flash alternately.
After the LED’s begin flashing, continue holding the reset button for
about another 20 seconds. The LED’s will turn off. Release the reset
button and the control will restart. (Releasing the button before the
LED’s turn off will cause the control to remain in latch-up.)
The 50200 control will not reset from lockout or latch-up if power
is interrupted.
Flame failure If the cad cell loses flame signal during operation (after the TFI),
the red LED flashes. The burner shuts off within 2 seconds. Re-
cycle: Control waits for 65 seconds (with red LED flashing), then
begins again at Self-test 2. Red LED goes off .
End cycle Set thermostat (or aquastat) to stop call for heat. The burner shuts
off within 2 seconds after end of call for heat.
Stand-by Control remains in stand-by mode until limit circuit sends power to
the black wire (call for heat).