CARLO GAVAZZI RSGD VD210 User manual

1
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
• Soft starting and soft stopping of AC motors.
• Integrated electronic overload protection (Class 10)*.
• Serial communication (Modbus) over RS485**.
* RSGD VD210, VD210C, VX210, VX210C, VX310C, VX311C models only,
** RSGD VD210C, VX210C, VX310C, VX311C models only.
Three phase AC motor soft starter
Benets
• Easy to use. The RSGD is equipped with a self-
learning algorithm that automatically adjusts the
start parameters to optimise the motor starts and
stops.
• Fast installation and set-up. Only 3 settings are
required (FLC, ramp-up and ramp-down).
• Compact dimensions. 12 - 45 Arms in 45 mm wide
housing, 55 - 100 Arms in 75 mm wide housing.
• Integrated protection. Diagnostic functions
provide additional protection. RSGD is also
equipped with an overload protection (Class 10).*
• Torque control during ramp-down. Smoother
deceleration of the load.
• Complete monitoring. The RSGD is equipped
with a Modbus/RTU communication port by 2-wire
RS485 connection.**
• Guided model selection. Easy to use selection
tool to select the appropriate soft starter model
depending on the application type.
Description
RSGD is an extremely compact and easy to use
3-phase soft starter for AC induction motors rated
up to 100 Arms.
The starting parameters can be easily set-up
through 3 selector switches.
The integrated motor overload protection (Class
10)* and Modbus communication** result in a
higher installation exibility.
Applications
RSGD soft starters are the ideal solution for 3-phase xed speed AC induction motor applications where there
is the need to reduce the starting current and/or minimise stresses on the motor during start and stop.
The RSGD oers a number of integrated diagnostic functions that can replace additional components inside
the electrical panel.
Typical applications include: compressors, pumps and fans.
Main functions

2
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
References
Code Option Description Notes
R-
S-Soft starter
G-General purpose
D-Dual phase control
40 220 – 400 VAC +10% -15% operational voltage (Ue)
60 220 – 600 VAC +10% -15% operational voltage (Ue)
12 12 Arms
Rated operational current
@ 40 °C
16 16 Arms
25 25 Arms
32 32 Arms
45 45 Arms
55 55 Arms
70 70 Arms
85 85 Arms
100 100 Arms
E0 110 - 400 VAC +10% -15% control voltage (Uc)
Supply voltage: internally supplied RSGD40 only
F0 24 VAC/DC +10% -10% control voltage (Uc)
Supply voltage: internally supplied
FF 24 VAC/DC +10% -10% control/supply voltage
Supply voltage: externally supplied
RSGD60 models from 55 Arms to
100 Arms only
GG 100 - 240 VAC +10% -15% control/supply voltage
Supply voltage: externally supplied RSGD60 only
V-
DNo heatsink RSGD 45 mm only
XWith heatsink
22 relay outputs RSGD 45 mm only
33 relay outputs RSGD 75 mm only
1With integrated motor overload protection (Class 10)
0Without motor overload protection RSGD 45 mm only
1With fan RSGD 100 Arms only
0No fan
-Without communication RSGD 45 mm only
CWith Modbus communication
Enter the code entering the corresponding option instead of .
Order code
RSGD V

3
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Operational voltage: 400 VAC Operational voltage: 600 VAC
Rated opera-
tional current
(Ie)
Control voltage
110 - 400 VAC
Control voltage
24 VAC/DC
Control / supply
voltage
100 - 240 VAC
Control / supply
voltage
24 VAC/DC
12 Arms
RSGD4012E0VD200
RSGD4012E0VD210
RSGD4012E0VD210C
RSGD4012F0VD200
RSGD4012F0VD210
RSGD4012F0VD210C
RSGD6012GGVD210
RSGD6012GGVD210C -
16 Arms
RSGD4016E0VD200
RSGD4016E0VD210
RSGD4016E0VD210C
RSGD4016F0VD200
RSGD4016F0VD210
RSGD4016F0VD210C
RSGD6016GGVD210
RSGD6016GGVD210C -
25 Arms
RSGD4025E0VD200
RSGD4025E0VX210
RSGD4025E0VX210C
RSGD4025F0VD200
RSGD4025F0VX210
RSGD4025F0VX210C
RSGD6025GGVX210
RSGD6025GGVX210C -
32 Arms
RSGD4032E0VD200
RSGD4032E0VX210
RSGD4032E0VX210C
RSGD4032F0VD200
RSGD4032F0VX210
RSGD4032F0VX210C
RSGD6032GGVX210
RSGD6032GGVX210C -
45 Arms
RSGD4045E0VX200
RSGD4045E0VX210
RSGD4045E0VX210C
RSGD4045F0VX200
RSGD4045F0VX210
RSGD4045F0VX210C
RSGD6045GGVX210
RSGD6045GGVX210C -
55 Arms RSGD4055E0VX310C RSGD4055F0VX310C RSGD6055GGVX310C RSGD6055FFVX310C
70 Arms RSGD4070E0VX310C RSGD4070F0VX310C RSGD6070GGVX310C RSGD6070FFVX310C
85 Arms RSGD4085E0VX310C RSGD4085F0VX310C RSGD6085GGVX310C RSGD6085FFVX310C
100 Arms RSGD40100E0VX311C RSGD40100F0VX311C RSGD60100GGVX311C RSGD60100FFVX311C
Selection guide

4
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Information Where to nd it
RSGD 45 mm instruction manual http://cga.pub/?eb523b
RSGD 75 mm instruction manual http://cga.pub/?aa922f
RSGD troubleshooting guide http://cga.pub/?a92131
RSGD 45 mm Modbus
communication protocol http://cga.pub/?41562d
RSGD 75 mm Modbus
communication protocol http://cga.pub/?2fe6d0
RSGD 45 mm Monitor software http://cga.pub/?6f9b0c
RSGD 75 mm Conguration software http://cga.pub/?e4fb5a
RS-USB driver http://cga.pub/?f3bda2
RSGD 45 mm CAD drawings http://cga.pub/?0bdae1
RSGD 75 mm CAD drawings http://cga.pub/?0f0b10
Further reading

5
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Category Type Trip Class Ramp-up
setting [s]
Ramp-down
setting [s]
Compressors
Scroll compressor 5 1 0
Screw compressor 5 2 to 5 0
Piston compressor 5 2 0
Centrifugal compressor 10 10 0
Pumps
Hydraulic pump 5 2 0
Centrifugal pump (start time <10sec) 5 5 to 10 10
Centrifugal pump (start time >10sec) 10 10 to 20 15
Piston pump 10 5 to 10 0
Fans
Centrifugal fan (<0.5m diameter) 10 5 to 10 0
Centrifugal fan (>0.5m diameter) 20 15 to 30* 0
Vacuum blowers 10 5 to 10 0
Feeders Screw feeder 10 2 to 10 0
Auger 10 5 to 10 0
Rotating machinery
Agitators 10 5 to 15 0
Mixers 10 5 to 10 0
Saws (<0.5m diameter) 10 5 to 10 5
Saws (>0.5m diameter) 20 15 to 30* 10
Grinder 20 15 to 30* 0
Crusher 30 20 to 30* 0
Conveyors 10 5 to 10 5
Note: when using the RSGD on high inertia loads (Trip Class 20, 30) ensure that enough time is left between starts to allow
the RSGD to cool down.
For Class 20 or 30 operation, an external overload device may be required.
* For RSGD 45 mm models set ramp-up time to 20.
Selection guide and typical application settings

6
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Motor
FLC [A]
HP Rating
@ 230V
Power kW
@ 400V Trip class 5 Trip class 10 Trip class 20 Trip class 30
6 1.5 3
RSGD4012..
VD200
RSGD4012..
VD210 / C
RSGD4012..
VD200
RSGD4012..
VD210 / C
RSGD4025..
VD200
RSGD4012..
VD210 / C
RSGD4025..
VD200
RSGD4012..
VD210 / C
9 2 3.7
RSGD4012..
VD200
RSGD4012..
VD210 / C
RSGD4012..
VD200
RSGD4012..
VD210 / C
RSGD4025..
VD200
RSGD4016..
VD210 / C
RSGD4032..
VD200
RSGD4025..
VX210 / C
12 3 5.5
RSGD4012..
VD200
RSGD4012..
VD210 / C
RSGD4016..
VD200
RSGD4012..
VD210 / C
RSGD4045..
VX200
RSGD4025..
VX210 / C
RSGD4045..
VX200
RSGD4025..
VX210 / C
16 5 7.5
RSGD4016..
VD200
RSGD4016..
VD210 / C
RSGD4025..
VD200
RSGD4016..
VD210 / C
RSGD4045..
VX200
RSGD4032..
VX210 / C
RSGD4045..
VX200
RSGD4032..
VX210 / C
22 7.5 11
RSGD4025..
VD200
RSGD4025..
VX210 / C
RSGD4032..
VD200
RSGD4025..
VX210 / C
RSGD4045..
VX200
RSGD4045..
VX210 / C
RSGD4045..
VX200
RSGD4045..
VX210 / C
30 10 15
RSGD4032..
VD200
RSGD4032..
VX210 / C
RSGD4045..
VX200
RSGD4032..
VX210 / C
RSGD4055..
VX310C
RSGD4070..
VX310C
37 10 18.5
RSGD4045..
VX200
RSGD4045..
VX210 / C
RSGD4045..
VX200
RSGD4045..
VX210 / C
RSGD4070..
VX310C
RSGD4085..
VX310C
45 15 22
RSGD4045..
VX200
RSGD4045..
VX210 / C
RSGD4045..
VX200
RSGD4045..
VX210 / C
RSGD4085..
VX310C
RSGD40100..
VX311C
55 20 30 RSGD4055..
VX310C
RSGD4055..
VX310C
RSGD40100..
VX311C -
70 25 37 RSGD4070..
VX310C
RSGD4070..
VX310C - -
85 30 45 RSGD4085..
VX310C
RSGD4085..
VX310C - -
100 30 55 RSGD40100..
VX311C
RSGD40100..
VX311C - -
• Contact Carlo Gavazzi representative for further information.
• Option “E0”: 110 - 400 VAC or option “F0”: 24 VAC/DC.

7
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Purpose Component name / code Notes
Manual motor starters
GMS-32 -
GMS-63 -
GMS-100 -
:
S: standard
H: high breaking capacity
Finger guards RFCG X6 6 pcs per box
Cooling fan RFAN-75-40 12 X1
For RSGD..100 only
Rated voltage : 12 VDC
Power consumption: 0.6 W
PC interface cable (Isolated USB to TTL cable) RS-USB For RSGD..12 to RSGD..45 only
CARLO GAVAZZI compatible components
Motor
FLC [A]
HP rating
@ 480 V
HP Rating
@ 600 V Trip class 5 Trip class 10 Trip class 20 Trip class 30
2.7 1.5 2
RSGD6012VD210 / C
3.9 2 3
5 3 4
6 3 5 RSGD6012..
VD210 / C
RSGD6012..
VD210 / C
RSGD6012..
VD210 / C
RSGD6012..
VD210 / C
9 5 7.5 RSGD6012..
VD210 / C
RSGD6012..
VD210 / C
RSGD6016..
VD210 / C
RSGD6025..
VX210 / C
11 7.5 10 RSGD6012..
VD210 / C
RSGD6012..
VD210 / C
RSGD6025..
VX210 / C
RSGD6025..
VX210 / C
16 10 15 RSGD6016..
VD210 / C
RSGD6016..
VD210 / C
RSGD6032..
VX210 / C
RSGD6032..
VX210 / C
22 15 20 RSGD6025..
VX210 / C
RSGD6025..
VX210 /C
RSGD6055..
VX310C
RSGD6055..
VX310C
27 20 25 RSGD6032..
VX210 / C
RSGD6032..
VX210 / C
RSGD6055..
VX310C
RSGD6055..
VX310C
32 20 30 RSGD6032..
VX210 / C
RSGD6032..
VX210 / C
RSGD6070..
VX310C
RSGD6070..
VX310C
41 30 40 RSGD6045..
VX210 / C
RSGD6045..
VX210 / C
RSGD6085..
VX310C
RSGD6085..
VX310C
52 40 50 RSGD6055..
VX310C
RSGD6055..
VX310C
RSGD60100..
VX311C -
70 50 60 RSGD6070..
VX310C
RSGD6070..
VX310C - -
85 60 75 RSGD6085..
VX310C
RSGD6085..
VX310C - -
100 75 100 RSGD6085..
VX310C
RSGD60100..
VX311C - -
• Contact Carlo Gavazzi representative for further information.
• Option “GG”: 100 - 240 VAC or option “FF”: 24 VAC/DC.
Note: Option FF available only for RSGD 75 mm models
Caution: the actual motor amps may be higher or lower than the average values listed above. We suggest to
use the actual motor current as listed on the motor nameplate. Use this table as a guide only.

8
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Element Component Function
ARamp-up time selector Sets the desired motor starting time.
BRamp-down time selector Sets the desired motor stopping time.
CFLC knob selector Sets the motor full load current (FLC). The FLC is setting is used by the RSGD for
the overload protection and for the maximum current allowed during motor start.
DTest/Reset
Simulate overload alarm (press for 1 sec when RSGD is in Idle state)
Enable/disable dry run function (press for 3 sec when RSGD is in Idle state)*
Set alarm recovery mode (press for 5 sec when RSGD is in Idle state)
Enable/disable overload function (press for 8 sec when RSGD is in Idle state)*
Reset alarms (press for < 1 sec when RSGD is in alarm mode and alarm mode
is Manual)
Enable/disable phase sequence protection (press for 10 sec when RSGD is in
Idle state)
Note: While the Test/Reset button is pressed the LED E5 will start ashing with a fre-
quency of 1 Hz (1/sec) in order to help the user count the number of seconds elapsed.*
E1 LED indicators Supply. Indicates that the RSGD supply is ON.
E2 LED indicators
Manual. Indicates the alarm reset mode.
Manual reset mode - LED ON, Auto reset mode - LED OFF
(Factory default setting: Auto, LED OFF)
E3 LED indicators
Phase sequence. Indicates if the wrong phase sequence protection is enabled
(LED OFF) or disabled (LED ON).
(Factory default setting: Enabled, LED OFF)
E4 LED indicators Alarm. Indicates that the RSGD is in alarm. The number of ashes indicates the
alarm type.
E5 LED indicators Ramping/bypass. Indicates whether RSGD is in ramping (ashing) or bypass (fully
ON).
QR QR code Scan to link to troubleshooting guide.
Structure
B
C
D
E1
E2
E3
E4
E5
A
B
C
D
E1
E2
E3
E4
E5
A
QR
QR
* RSGD VD210C, VX210C models only.

9
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Ramp-up Mode of operation
1 or 2 seconds
• When the ramp-up knob is in position 1 or 2, the RSGD will follow a self learning current
limit algorithm.
• As soon as A1-A2 (or ST for RSGD60 models) control voltage signal is applied, the RSGD
will start to ramp-up the motor.
• At the very rst start the current limit will be 4 x FLC setting.
• In the subsequent starts, the RSGD will automatically adjust the current limit setting to
maintain the motor start time as close as possible to the ramp-up time setting.
≥ 5 seconds
• When the ramp-up knob is in position 5 or above, the RSGD will follow a self-learning
current ramp algorithm.
• The RSGD will start with a set of default parameters for starting torque.
• Depending on the ramp-up time setting, the RSGD will apply a current ramp algorithm to
start the motor as close as possible to the set ramp-up time.
• During the motor start, the current will be limited to a maximum of 3.5 x FLC setting.
• In the subsequent starts, the RSGD will continue to adjust the starting parameters of initial
torque and current ramp to ensure that the motor is started as close as possible to the set
ramp-up time.
Ramp-down Mode of operation
1 to 30 seconds
• During ramp-down, the RSGD works on a torque control algorithm for smoother stopping
of the motor.
• As soon as the control voltage signal A1-A2 (or ST for RSGD 60 models) is removed, the
RSGD will slow down the motor gradually according to the ramp-down setting.
• The power semiconductors will be switched OFF as soon as the time (as per ramp-down
setting) has elapsed unless there is a risk of exceeding the maximum temperature on the
semiconductors. In such a case the RSGD will leave the motor to coast to stop.
0 seconds • If the ramp-down knob is set to 0, the RSGD will leave the motor to coast to stop (no ramp-
down).
The RSGD series of soft starters works on two distinct self-learning algorithms depending on the ramp-up time
settings.
Mode of operation

10
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Features
RSGD 45 mm RSGD 75 mm
Material PA66
Assembly DIN or panel
Protection grade IP20
Weight 0.5 to 0.75 kg approx. 2.3 kg
Overvoltage category Cat. III
General
Fig. 1 RSGD..12..VD200 to RSGD..32..VD200, RSGD..12..VD210/C to RSGD..16..VD210/C
Fig. 2 RSGD4045..VX200, RSGD..25VX210/C to RSGD..45..VX210/C

11
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Fig. 3 RSGD..55..VX310C to RSGD..85..VX310C (DIN rail mount version)
Fig. 4 RSGD..100..VX311C (panel mount version)
RSGD 45 mm RSGD 75 mm
Ramp-up time 1 - 20 s 1 - 30 s
Ramp-down time 0 - 20 s 0 - 30 s
Initial torque Automatically determined by RSGD
FLC range settings
RSGD 12: 2 - 12 A
RSGD 16: 6 - 16 A
RSGD 25: 12 - 25 A
RSGD 32: 20 - 32 A
RSGD 45: 32 - 45 A
RSGD 55: 25 - 55 A
RSGD 70: 40 - 70 A
RSGD 85: 55 - 85 A
RSGD 100: 70 - 100 A
Settings

12
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Power Supply
RSGD40 RSGD60
Operational voltage range 187 - 440 VACrms 187 - 660 VACrms
Supply current at Idle < 30 mArms
Blocking voltage 1200 Vp 1600 Vp
Rated AC frequency 50/60 Hz (+/- 10%)
Rated insulation voltage 600 VAC 690 VAC
Dielectric withstand voltage:
Supply to input
Supply to heatsink
2.5 kVrms
2.5 kVrms
Integrated varistor Yes (across controlled phases)
Environmental
Working temperature -20°C to +60°C (-4°F to +140°F). Note: for temperatures > 40°C derating applies.
Storage tempreature -40°C to +80°C (-40°F to +176°F).
Relative humidity < 95% non-condensing @ 40°C.
Pollution degree 2
Installation category III
Installation altitude 1000 m
Vibration
Frequency 1
Frequency 2
Acc. to IEC/EN 60068-2-6
2 [+3/-0] Hz to 25 Hz displacement +/- 1.6 mm
10 Hz to 55 Hz @ 2g (19.96m/s2) @ constant displacement
Standard compliance
LVD: EN 60947-5-1 / EE: BS EN 60947-5-1
EMCD: EN 60947-5-1 / EMC: BS EN 60947-5-1
UL: 60947-4-2, E172877, NMFT, UL508a
cUL: C22.2 No. 60947-2, E172877, NMFT
CCC: GB/T 14048.6-2016
Approvals
Electromagnetic compatibility (EMC) - emissions
Radio interference eld
emission (radiated)
EN/IEC 55011
Class A (Industrial): from 30 to 1000 MHz
Radio interference voltage
emissions (conducted)
EN/IEC 55011
Class A (Industrial): from 0.15 to 30 MHz
Note: the tests were done using a screened cable for the communication lines.
PC2 (performance criteria 2): during the test, degradation of performance or partial loss of function is allowed.
However, when the test is complete, the product should return operating as intended.
Compatibility and conformity

13
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Electromagnetic compatibility (EMC) - immunity
RSGD 45 mm
Standard
RSGD 45 mm
with Modbus RSGD 75 mm
Electrostatic discharge (ESD)
EN/IEC 61000-4-2
8 kV air discharge, 4 kV contact
PC1 PC2 PC2
Radiated radio frequency
EN/IEC 61000-4-3
10 V/m, from 80 MHz to 1 GHz
10 V/m, from 1.4 to 2 GHz
3 V/m, from 2 to 2.7 GHz
PC1
PC1
PC1
Electrical fast transient (burst)
EN/IEC 61000-4-4
AC input: 2 kV, 5 kHz & 100 kHz
DC input: 1 kV, 5 kHz & 100 kHz
Signal: 1 kV, 5 kHz & 100 kHz
Control: 2 kV, 5 kHz &100 kHz
Output: 2 kV, 5 kHz & 100 kHz
PC1
PC2
PC2
PC2
PC2
PC2
2 kV (PC2)
PC2
1 kV (PC2)
4 kV (PC1)
PC2
PC2
PC2
PC2
PC2
Conducted radio frequency
EN/IEC 61000-4-6
10 V/m, from 0.15 to 80 MHz
PC2
Electrical surge,
EN/IEC 61000-4-5
Output, line to line: 1 kV
Output, line to earth: 2 kV
AC input, line to line: 1 kV
AC input, line to earth: 2 kV
DC input, line to line: 1 kV
DC input, line to earth: 2 kV
Signal and control, line to earth: 2 kV
PC2
PC1
PC1
PC1
PC2
PC2
PC1
PC2
PC2
PC2
PC1
0.5 kV (PC2)
1 kV (PC2)
1 kV (PC2)
PC2
PC2
PC1
PC1
PC2
PC2
1 kV (PC2)
Voltage dips,
EN/IEC 61000-4-11
0% for 10 ms and 20 ms
40% for 100, 200, 1000 ms
70% for 500 ms
80% for 5000 ms
0% for 5000 ms
PC2
PC2
PC2
PC2
PC2
PC2
PC2
PC2
PC3
PC3
PC2
PC2
PC2
PC2
PC2

14
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
RSGD40..E0V RSGD40..F0V RSGD60..FFV RSGD60..GGV
Control voltage (Uc)
A1 - A2:
110 - 400 VAC
+10%, -15%
A1 - A2:
24 VAC/VDC
+10%, -10%
ST:
24 VAC/VDC
+10%, -15%
ST:
100 - 240 VAC
+10%, -15%
Control voltage range (Uc) 93.5 - 440 VAC 21.6 - 26.4
VAC/DC
21.6 - 26.4
VAC/DC 85 - 264 VAC
Maximum pick-up voltage 80 VAC 20.4 VAC/DC 20.4 VAC/DC 80 VAC
Minimum drop out voltage 20 VAC 5 VAC/DC 5 VAC/DC 20 VAC
Supply voltage range (Us) - -
A1 - A2:
24 VAC/DC
+10%, -10%
A1 - A2:
100 - 240 VAC
+10%, -15%
Rated AC frequency 45 - 66 Hz 45 - 66 Hz
(applies to 24 VAC supply) 45 - 66 Hz
Rated insulation voltage (Ui) 500 VAC
Dielectric strength:
Dielectric withstand voltage
Rated impulse withstand volt-
age
2 kVrms
4 kVrms
Control input current
0.5 - 5 mArms
(0.55 - 1.3 mArms
for RSGD 45mm)
0.4 - 1 mArms 0.5 - 1.5 mArms 0.4 - 3 mArms
Input to output response time
(Mains supply already present) 200 msec
Input to output response time
(Mains supply applied with
control)
2 sec 3 sec
Integrated varistor Yes
Inputs
Note 1: for the Canadian application, the control terminals A1, A2 (or A1, A2, ST for RSGD60 versions) of the RSGD
devices shall be supplied by a secondary circuit where power is limited by a transformer, rectier, voltage divider, or similar
device that derives power from a primary circuit, and where the short-circuit limit between conductors of the secondary
circuit or between conductors and ground is 1500VA or less. The short-circuit volt ampere limit is the product of the open
circuit voltage and the short circuit ampere.
Note 2: RSGD60 soft starters require a separate 100 - 240V, 50/60Hz single phase control source. Output connections (L1,
L2, L3, T1, T2, T3) are not galvanically isolated from the external supply connections (A1, A2, ST).
Note 3: For the RSGD60 versions the L1, L2, L3 voltage should be applied before or within 250ms from when the control
signal ‘ST’ is applied.

15
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
RSGD..12 RSGD..16 RSGD..25 RSGD..32 RSGD..45
Overload cycle
@ 40°C surrounding temperature
(acc. to EN/IEC 60947-4-2)
VD200: 3-5:175
VD210: 3-12:168
VD200:3-5:355
VX210:3-
12:168
VD200:3-5:175
VX210:3-
12:168
3-12:348
Maximum number of starts/hr
@ rated overload cycle
@ 40°C surrounding temperature
20 VD200: 10
VX210: 20 20 10
Maximum number of starts/hr
(with fan)
@ rated overload cycle
@ 40°C surrounding temperature
- - - - -
Rated operational current
@ 40°C 12 Arms 16 Arms 25 Arms 32 Arms 45 Arms*
Rated operational current
@ 50°C 12 Arms 15 Arms 23 Arms 28 Arms 40 Arms
Rated operational current
@ 60°C 12 Arms 13 Arms 21 Arms 24 Arms 34 Arms
Minimum load current 1 Arms 5 Arms
Note: the overload cycle describes the switching capability of the soft starter at a surrounding temperature of 40°C as
described in EN/IEC 60947-4-2. An overload cycle AC53b:3-12:348 means that the soft starter can handle a starting
current of 3x Ie for 12 seconds followed by an OFF time of 348 seconds.
* For RSGD6045 models, operational current is 45 Arms @ 25°C.
Outputs
RSGD..55 RSGD..70 RSGD..85 RSGD..100
Overload cycle
@ 40°C surrounding temperature
(acc. to EN/IEC 60947-4-2)
AC53b : 3 - 12 : 348
Maximum number of starts/hr
@ rated overload cycle
@ 40°C surrounding temperature
10
Maximum number of starts/hr
(with fan)
@ rated overload cycle
@ 40°C surrounding temperature
- - - 10
Rated operational current @ 40°C 55 Arms 70 Arms 85 Arms 100 Arms
Rated operational current @ 50°C 50 Arms 64 Arms 78 Arms 88.5 Arms
Rated operational current @ 60°C 46 Arms 59 Arms 71 Arms 77 Arms
Minimum load current 5 Arms

16
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
RSGT 45 mm RSGT 75 mm
Number of output relays 2 3
Function of relays Alarm, bypassed (top of ramp). Alarm, bypassed (top of ramp), run.
Rated operational voltage 250 VAC/30 VDC
Rated insulation voltage 250 VAC
Dielectric withstand voltage 2.5 kV
Overvoltage category II
Type of control circuit Electromechanical relay
Number of contacts Alarm and bypassed: 1 Alarm and bypassed: 2
Run: 1
Type of contacts Alarm: normally closed (NC)
Bypassed: normally open (NO)
Alarm and bypassed: changeover (NO,
NC)
Run: normally open (NO)
Type of current AC / DC
Rated operational current 3 Arms @ 250 VAC, 3 Arms @ 30 VDC
Type Bi-directional (static and dynamic variables and parameters)
Functions
Conguration of device
Start/Stop
Modication of set-point parameters
Monitoring of measured variables
Connection
2-wires
Note: to reduce the noise use a shielded cable and connect the shield to GND termi-
nal and to the ground at the same point.
Address Default : 1
Selectable via software: range 1 - 247
Protocol MODBUS (RTU)
Factory dened data format
Data bits: 8
Parity: none
Stop bit: 1
Selectable via software: parity: none (2 stop bits), odd (1 stop bit), even (1 stop bit)
Baud rate Default: 9.6k bits/s
Selectable via software: 9.6k, 19.2k, 38.4k bits/s
Auxiliary relays
RS485

17
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
The table below indicates the maximum number of starts/hr that can be done by the dierent RSGD models at
dierent operating currents with a surrounding temperature of 40°C.
Performance
Ratings:
kW rating according to: IEC/EN 60947-4-2
HP rating according to: UL508
* For RSGD6045 models, ratings are @25°C
Model IEC Rated
Current 220 - 240 VAC 380 - 415 VAC 440 - 480 VAC 550 - 600 VAC
RSGD..12 12 Arms 3 kW / 3 HP 5.5 kW / 5 HP 5.5 kW / 7.5 HP 9 kW / 10 HP
RSGD..16 16 Arms 4 kW / 5 HP 7.5 kW / 7.5 HP 9 kW / 10 HP 11 kW / 15 HP
RSGD..25 25 Arms 5.5 kW / 7.5 HP 11 kW / 10 HP 11 kW / 15 HP 20 kW / 20 HP
RSGD..32 32 Arms 9 kW / 10 HP 15 kW / 15 HP 18.5 kW / 20 HP 22 kW / 30 HP
RSGD..45* 45 Arms 11 kW / 15 HP 22 kW / 25 HP 22 kW / 30 HP 37 kW / 40 HP
RSGD..55 55 Arms 15 kW / 20 HP 30 kW / 30 HP 30 kW / 40 HP 45 kW / 50 HP
RSGD..70 70 Arms 20 kW / 25 HP 37 kW / 40 HP 45 kW / 50 HP 55 kW / 60 HP
RSGD..85 85 Arms 22 kW / 30 HP 45 kW / 50 HP 45 kW / 60 HP 55 kW / 75 HP
RSGD..100 100 Arms 30 kW / 30 HP 55 kW / 50 HP 55 kW / 75 HP 75 kW / 100 HP
Model Operational current
6 Arms 12 Arms 16 Arms 25 Arms 32 Arms 45 Arms
RSGD..12..VD200 40 20 - - - -
RSGD..16..VD200 50 25 20 - - -
RSGD..25..VD200 45 20 15 10 - -
RSGD..32..VD200 100 55 40 25 20 -
RSGD..45..VX200 80 40 30 18 15 10
Current / power ratings: kW and HP @ 40°C
Starts per hour
Model Operational current
6 Arms 12 Arms 16 Arms 25 Arms 32 Arms 45 Arms
RSGD..12..VD210/C 40 20 - - - -
RSGD..16..VD210/C 50 25 20 - - -
RSGD..25..VX210/C 90 40 30 20 - -
RSGD..32..VX210/C 100 55 40 25 20 -
RSGD..45..VX210/C 80 40 30 18 15 10
Model Operational current
25 Arms 45 Arms 55 Arms 70 Arms 85 Arms 100 Arms
RSGD..55..VX310C 25 13 10 - - -
RSGD..70..VX310C 30 16 13 10 - -
RSGD..85..VX310C 40 21 17 12 10 -
RSGD..100..VX311C 40 22 18 14 12 10

18
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
Current derating curves
Spacing
100mm
100mm
SpacingSpacing
100mm
X1
Y2
Y1
0,0
2,0
4,0
6,0
8,0
10,0
12,0
14,0
20 30 40 50 60
Load current in Arms
Surrounding ambient temperature in ºC
RSGD..12
Spacing >=10mm
Spacing 0mm

19
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
0,0
2,0
4,0
6,0
8,0
10,0
12,0
14,0
16,0
18,0
20 30 40 50 60
Load current in Arms
Surrounding ambient temperature in ºC
RSGD..16
Spacing >=10mm
Spacing 0mm
0,0
4,0
8,0
12,0
16,0
20,0
24,0
28,0
20 30 40 50 60
Load current in Arms
Surrounding ambient temperature in ºC
RSGD..25
Spacing 50mm
Spacing 20mm
Spacing 10mm
Spacing 0mm
0,0
5,0
10,0
15,0
20,0
25,0
30,0
35,0
20 30 40 50 60
Load current in Arms
Surrounding ambient temperature in ºC
RSGD..32
Spacing 50mm
Spacing 20mm
Spacing 10mm
Spacing 0mm

20
Carlo Gavazzi LTD
RSGD
RSGD DS ENG26/05/2022
0,0
5,0
10,0
15,0
20,0
25,0
30,0
35,0
40,0
45,0
50,0
20 30 40 50 60
Load current in Arms
Surrounding ambient temperature in ºC
RSGD..45
Spacing 50mm
Spacing 20mm
Spacing 10mm
Spacing 0mm
0,0
10,0
20,0
30,0
40,0
50,0
60,0
20 30 40 50 60
Load current in Arms
Surrounding ambient temperature in ºC
RSGD..55
Spacing ≥ 20mm
Spacing 10mm
Spacing 0mm
0,0
10,0
20,0
30,0
40,0
50,0
60,0
70,0
80,0
20 30 40 50 60
Load current in Arms
Surrounding ambient temperature in ºC
RSGD..70
Spacing ≥ 20mm
Spacing 10mm
Spacing 0mm
This manual suits for next models
5
Table of contents
Other CARLO GAVAZZI Controllers manuals

CARLO GAVAZZI
CARLO GAVAZZI RSBS Series User manual

CARLO GAVAZZI
CARLO GAVAZZI RSGD User manual

CARLO GAVAZZI
CARLO GAVAZZI VariFlex3 RVLF Series User manual

CARLO GAVAZZI
CARLO GAVAZZI RSWT Series User manual

CARLO GAVAZZI
CARLO GAVAZZI RSBD Operating instructions

CARLO GAVAZZI
CARLO GAVAZZI Sx2WEB Series User manual

CARLO GAVAZZI
CARLO GAVAZZI NRGC Series User manual

CARLO GAVAZZI
CARLO GAVAZZI RSBS User manual

CARLO GAVAZZI
CARLO GAVAZZI VariFlex2 RVDF Series Assembly instructions

CARLO GAVAZZI
CARLO GAVAZZI VariFlex3 RVLF Series User manual