Cavius 2201-003 User manual

to connect the power supply. The product label
must not be removed as it contains important
information regarding the product.
All alarms to be connected in the house should
be put into ‘Learn Mode’ by sliding the switch on
the back of the alarm to the ‘Learn Mode’ position.
Please note: The learn switch placed on the back
of the alarm can only be in learn position when
the alarm is disassembled from the power supply
unit. The learn switch will automatically switch to
normal position when the alarm head is tted to
the power supply.
The red LED will light up to indicate that ‘Learn
Mode’ has been selected.
Do not remove the battery during ‘Learn Mode’ as
this will interrupt the learn process.
Press and hold the test button at one alarm only,
until it beeps and the LED ashes. This alarm will
become the master and will start sending out a
specic house code to the other alarms.
As the other alarms receive the specic house
code, they will also ash the LED light.
When all alarms flash the red LED, they are
connected and can be switched out of ‘Learn
Mode’ and installed.
2. THE BEST AREAS TO INSTALL THE SMOKE
ALARM:
• Note the local country regulations regarding
installation.
• Note the local regulations about information
to your insurance company regarding installed
smoke alarms.
• Install an alarm between possible re sources
and bedrooms as a minimum.
• Install alarms on each oor of the house, in
hallways and stairways.
• Alarms in each room such as bedrooms and
living rooms.
Additional alarms increase the security.
3. AREAS WHERE NOT TO INSTALL SMOKE
ALARMS:
• In dusty rooms
• At the top of a high pointed ceiling, in ceiling
corners, and within 50cm of a wall.
• In rooms where temperature goes outside the
range +4oto 38°Cor above 90% relative humidity
not condensing.
• In kitchens, garages, laundries, or too close to
replaces; areas where either dampness, gases
or smoke could occur.
Place the alarm where it is reachable in order to
test the alarm and for maintenance.
4. PLACEMENT:
The smoke alarm is designed to be installed on
a ceiling.
With a minimum of one smoke alarm per oor and
a maximum distance between smoke alarms of
10 meters.
For ceiling installation:
The smoke alarm should be a minimum of 50cm
from the wall.
For cathedral or peak ceiling:
Mains powered smoke alarm device
Commercial reference: 2201-003
Developed by CAVIUS
The smoke alarm is designed for private homes.
PLEASE READ THE USER GUIDE
CAREFULLY BEFORE INSTALLATION AND
RETAIN FOR FUTURE USE.
TECHNICAL INFORMATION
The smoke alarm is powered by mains power
(110-230V AC), with a lithium back-up battery
CR2. Please note that you should only use batteries
from one of the following suppliers: DURACELL
or HUIDERUI.
It can be RF interlinked with other 2201 alarms,
and with other CAVIUS Wireless Family alarms.
The maximum number of alarms that can be inter-
linked within a house group are 32.
Please note: These must be alarms from the CAVIUS
The distance between interlinked alarms depends
on the house layout and they should always be
tested after installation. It is not advised to install
alarms with a separation of more than 10m.
Diameter: 97mm. Height: 41mm (without mount-
ing base) 52mm (with mounting base).
Interlinked by RF: 868 MHz
Complies to standards: EN14604:2005 +AC:2008,
EN300-220, EN50130-4:2011, EN60065.
EN60950-1, RoHs, Reach.
1. HOW TO SET UP AND CONNECT ALARMS:
Start by pulling out the battery isolation
strip in the battery compartment
as shown.
Please note: RF connection is done with the
device powered with battery only. You do not have
UK
CHAMBER
FILTER
OPTIONAL HOLE
FOR LAMP WIRE
TEST BUTTON
SIREN RED & GREEN LED
ISOLATION
STRIP
DO NOT
REMOVE THE
PRODUCT LABEL
1NORMAL MODE
2LEARN MODE
Minimum
1
1
2
Minimum 50cm
from wall
Wall
Ceiling
Peak ceiling
Minimum 50cm
from peak

Screw the mounting base on the ceiling.
Screw the power supply on the mounting base.
Once the mounting base with power supply is
installed, attach the alarm by twisting clockwise
until it clicks. If the battery is either missing or
inserted incorrectly, the smoke alarm will not be
able to click into the mounting base.
OPTION 2: ALARM MOUNTED ON TOP OF
CONDUIT BOX:
Connect the 3 wires from the conduit box on the
alarm power supply:
Live feed (L1), neutral (N), Ground ( ).
Screw the power supply on conduit box.
NOTE: Mounting base is not used when
the alarm is installed on conduit box.
OPTION 3: ALARM MOUNTED WITH LAMP
SOCKET:
Drill through the middle of the alarm (Diam. 8mm)
Install the power supply into the mounting base
ring or use the conduit box as shown in option
1 & 2.
NOTE: Alarm supply must be different from the
lamp supply which can be switched ON and OFF.
Remove the plastic cover to access to the power
supply connector.
Pass the lamp wire through the smoke alarm.
5. INSTALLING THE SMOKE ALARM:
NOTE: THIS ALARM NEEDS TO BE INSTALLED
BY A PROFESSIONAL.
MAKE SURE ELECTRICITY IS SWITCHED OFF
BEFORE STARTING THE INSTALLATION.
CAUTION: LIVE, NEUTRAL AND EARTH MUST
BE CORRECTLY INSTALLED AND NOT MIXED UP.
NOTE: The alarm is delivered in the packaging
with a dust cover, installed to protect the alarm for
exposure to excessive dust which could potentially
damage or reduce the function of the alarm while
the building is under construction. The dust cover
must be removed after the building is fully cleaned.
OPTION 1: ALARM MOUNTED ON MOUNTING
BASE OUT ON THE CEILING:
Use the mounting base ring to mark the screw
holes on the ceiling.
For surface wiring pass the feed wire through
the mounting base cable holder and screw after
termination.
Connect the 3 wires to the power supply: Live feed
(L1), neutral (N), Ground ( ).
MARK UP
4 SCREW HOLES
WITH A PEN
L1
N
N
L1 L2
L1
N
N
L1 L2
2
USE THE
ENCLOSED
SCREWS AND
PLUGS

Connect the 4 wires to the power supply: Live feed
(L1), neutral (N), Ground ( ), lamp feed wire (L2).
Install the wires as shown.
Install the cableholder and replace the cover.
NOTE: After putting the wires through the alarm,
check if the test button can move free. If the hole
is too small the test button cannot move.
can be added to the system
Minimum 10cm
6. TEST FUNCTION:
After installation, and at least once per quarter,
test all of your alarms to ensure they are operating
correctly and are within range of each other.
It is recommended to check visually every week if
the LED ashes correctly (every 48sec.).
Press the test button on any alarm for at least 10
seconds.This will send out a test signal from the
alarm; all other connected alarms should receive
the signal within a short time. The alarms will emit
a short beep and the LED will ash every 8 sec-
onds for 2 minutes.
NOTE: Test function also transmits a weaker RF
signal to ensure an optimal operation in normal
conditions.
When the test signal is sent out, the alarms will
respond in two ways:
1. A single beep every 8 seconds indicates that
the alarms are connected and functioning.
2. Three short beeps every 8 seconds indicates a
smoke sensor fault. The alarm should be cleaned
by running the vacuum (on a low setting) around
the smoke alarm chamber and tested again.
If required this indication can be stopped early on
each alarm by a short press of the test button.
TIP: It is safe to cover the sound output holes with
your nger or a cloth during the testing to minimize
the sound level emitted.
If the problem continues, please visit www.cavius.com
for any trouble shooting.
7. NORMAL MODE:
In normal mode the LED will ash every 48 seconds
to show correct operation.
The green LED is on when the alarm is connected
to mains power. It may take up to 1 minute to
indicate that mains power has been connected.
8. ALARM MODE:
When the smoke is detected, the smoke alarm will
go into ‘Alarm Mode’. It will sound the alarm signal
and the red LED will ash.
The smoke alarm will also transmit the alarm signal
to the other connected alarms, which will also
sound the alarm signal after a short delay.
The CAVIUS Wireless Family have two different
alarm signals:
Alarm signal 1 (--- --- ---) is life threatening
alarms, like a smoke alarm.
Alarm signal 2 (- - -) is a non life threatening
alarm, like a ooding alarm:
Smoke alarm signal: --- --- ---
Heat alarm signal: --- --- ---
Flood alarm signal: - - -
CO alarm low level signal: - - -
CO alarm high level signal: --- --- ---
Please note that only the originating alarm’s red
LED will ash, so it can be identied.
9. PAUSE/HUSH FUNCTION:
If the smoke alarms are to set into a false alarm by
cooking, replace, etc. they can be paused for 10
minutes by pressing the test button on the origi-
nating smoke alarm only (indicated by the ashing
LED).
The reason for this is that it is necessary to locate
the source of the alarm before using the hush
function. This is to make sure that it is not a life
threatening situation.
10. ADD EXTRA DEVICE:
The mains powered smoke alarm can be used
together with the alarms in the CAVIUS wireless
family: Smoke, Heat, Flood, CO & mains power
alarms. All CAVIUS interconnected alarms within the
as they run on the same frequency and use the
same data protocol.This means that the wireless
system can consist of a combination of smoke,
heat, ood etc.
Place all alarms into ‘Learn Mode’ and repeat
section 1.
Always test connection to all devices by repeating
test function section 6 after adding devices.
11. LOW BATTERY SIGNAL:
Your product has a battery back-up with a 1 year
life in battery mode without mains power, and up
to 10 years normal life with mains. However, we
recommend to replace the battery every 5 years.
When the battery is starting its end of life, a short
beep will sound out every 48 seconds for 30 days.
Light bulb: maximum 75W
Lamp: maximum 2 kgs weight
3
L2
N
L2
N
L1
N
N
L1 L2
HEAT ALARM
SMART REMOTE
FLOOD ALARM
SMOKE ALARM
MAINS POWERED
SMOKE ALARM

13. MAINTENANCE & TROUBLE SHOOTING:
The smoke alarm should be vacuum cleaned
once per quarter, to remove dust particles, and
it can be wiped with a damp cloth. (Do not open
the alarm).
NOTE: You can easily vacuum clean the smoke
chamber through the dedicated openings in the
top cover, and it’s possible to test the alarms by
pressing the cover at the same time.
High humidity condensing which can be resolved
by drying the smoke alarm.
If the smoke alarm does not work when the test
button is pushed, the probable cause is a power
failure. Always test the alarm after replacement
of battery.
If the problem continues, please visit www.cavius.com
for any trouble shooting.
Only the alarm with the low battery will sound,
no other connected alarms will sound. It is safe
to change batteries in the alarms without going
through the learn process again – they will not for-
get the codes during the battery change process.
12. BATTERY REPLACEMENT:
To replace the battery, detach the smoke alarm
from the power supply by twisting counterclock-
wise.
Remove the plastic cover to access the battery.
Replace the battery respecting the polarities.
Attach the alarm on power supply by twisting
clockwise until it clicks, and test the alarm.
14. OTHER INFORMATION:
Do not paint the alarm.
Disposal: For battery and product, please dispose
properly at the end of life. This is electronic waste
which should be recycled.
WARNING: Please remove dust cover after
installation. Smoke will not be able to reach the
chamber while dust cover is in place.
The CE mark afxed to this product conrms its
compliance with the European Directives which
apply to the product and, in particular, its compli-
ance with the harmonized specications of stan-
dard EN 14604 relating to Construction Products
Regulation 305/2011.
All Rights reserved: CAVIUS Aps assumes no respon-
sibility for any errors, which may appear in this manual.
Furthermore, CAVIUS Aps reserves the right to alter the
hardware, software, and/or specications detailed herein at
any time without notice, and CAVIUS Aps does not make
any commitment to update the information contained
herein. All the trademarks listed herein are owned by
their respective owners. Copyright © CAVIUS Aps.
0333
17
Download DoP document: www.cavius.com
EN 14604:2005 + AC :2008
DoP no.: 2201-003
126979 rev1
Developed by CAVIUS Aps Julsøvej 16, DK-8600
Manufactured in P.R.C.
4
Table of contents
Other Cavius Smoke Alarm manuals

Cavius
Cavius 2203-002 User manual

Cavius
Cavius 2001-030 User manual

Cavius
Cavius LUMI-PLUGIN LP120 User manual

Cavius
Cavius 2103 User manual

Cavius
Cavius 2104-001 User manual

Cavius
Cavius 2106-003 User manual

Cavius
Cavius 4002-001 User manual

Cavius
Cavius 3002-TK001 User manual

Cavius
Cavius 2107-001 User manual

Cavius
Cavius 2203-002 User manual

Cavius
Cavius 3103-002 User manual

Cavius
Cavius 2007-003 User manual

Cavius
Cavius 2208 User manual

Cavius
Cavius 3104-001 User manual

Cavius
Cavius 2107-001 User manual

Cavius
Cavius 4002-001 User manual

Cavius
Cavius RAUCHWARN MELDER User manual

Cavius
Cavius 2008-001 User manual

Cavius
Cavius 2008-002 User manual

Cavius
Cavius 2103-002 User manual