CertaUPS C400-010-B Installation instructions

C400 1000-3000 VA
Tower
1000-3000VA
Installation/Manual
Service and support
WWW.CERTAUPS.COM
INFO@CERTAUPS.COM
T: +44 (0)1246 431 431

CONTENT
1. SAFETY AND EMC INSTRUCTIONS.........................................................1
1.1 INSTALLATION........................................................................................1
1.2 OPERATION...........................................................................................2
1.3 MAINTENANCE,SERVICING AND FAULTS...................................................3
1.4 TRANSPORT ..........................................................................................3
1.5 STORAGE..............................................................................................3
1.6 STANDARDS ..........................................................................................4
2. DESCRIPTION OF COMMONLY USED SYMBOLS..................................5
3. INTRODUCTION .........................................................................................5
4. PANEL DESCRIPTION ...............................................................................7
4.1 BUTTON................................................................................................7
4.2LCD DESCRIPTION.................................................................................8
5. CONNECTION AND OPERATION............................................................10
5.1 INSPECTION: .......................................................................................10
5.2 CONNECTION: .....................................................................................10
5.3 BATTERY RECHARGE:...........................................................................14
5.4 TURN ON THE UPS:.............................................................................14
5.5 TEST FUNCTION:..................................................................................14
5.6 TURN OFF THE UPS:............................................................................15
5.7AUDIBLE ALARM MUTE FUNCTION:.........................................................15
6. OPERATING MODE FOR ALL MODELS.................................................16
6.1 LINE MODE..........................................................................................17
6.2 BATTERY MODE ...................................................................................18
6.3 BYPASS MODE.....................................................................................18
6.4 NO OUTPUT MODE...............................................................................19
6.5 EPO (EMERGENCY POWER OFF).........................................................19
6.6 ECO MODE (ECONOMY MODE).............................................................20
6.7 CVCF MODE.......................................................................................20
6.8ABNORMAL MODE ................................................................................20
7. SETTING BY LCD MODULE ....................................................................21
8. TROUBLE SHOOTING .............................................................................25
9. MAINTENANCE ........................................................................................28
9.1 OPERATION.........................................................................................28
9.2 STORAGE............................................................................................28
10. TECHNICAL DATA..................................................................................28

10.1 ELECTRICAL SPECIFICATIONS .............................................................28
10.2 OPERATING ENVIRONMENT ................................................................29
10.3 TYPICAL BACKUP TIME (TYPICAL VALUES AT 25°C IN MINUTES ).............29
10.4 DIMENSIONS AND WEIGHTS ................................................................30
11. COMMUNICATION PORT.......................................................................30
11.1 USBAND RS-232(OPTIONAL)COMMUNICATION PORTS ......................30
11.2 USB FOR HID POWER DEVICE............................................................30
11.2AS400 INTERFACE (OPTIONAL)..........................................................31
11.1 CMC INTERFACE (OPTIONAL).............................................................31
11.2 NMC INTERFACE (OPTIONAL).............................................................31
12. SOFTWARE.............................................................................................32
APPENDIX: REAR PANEL (IEC)..................................................................33

-1-
1. Safety and EMC Instructions
Please read carefully the following user manual and the safety
instructions before installing or operating the unit.
1.1 Installation
See installation instructions before connecting to mains power.
Condensation should occur if the UPS is moving directly from a cold to a
warm environment. The UPS must be absolutely dry before being
installed. Please allow an acclimatisation time of at least two hours.
Do not install the UPS near water or in damp environment.
Do not install the UPS where it would be exposed to direct sunlight or
near other heat sources.
Do not connect appliances or items of equipment which would overload
the UPS (e.g. laser printers, etc.) to the UPS output.
Place cables in such a way that no one can step on or trip over them.
Use a reliable earth source.
Only connect the UPS to an earthed shockproof outlet socket.
The building outlet connection must be easily accessible to disconnect
from the UPS.
When installing the UPS check that the sum of the leakage current of the UPS
and the connected load does not exceed 3.5mA.

-2-
Do not block the ventilation openings on the UPS housing. Ensure the air vents on
the front, side and rear of the UPS are clear at all times. At least 25cm of space on
each side is recommended. The air flow diagram is shown as below:
■Figure 1.1 Air flow diagram
This UPS is powered by more than one source, disconnection of the AC source
and the DC source is required before servicing.
An additional circuit breaker or fuse with rating 16A and breaking capacity 3kA
shall be used between power source and input when installation this unit.
1.2 Operation
Do not disconnect the mains cable on the UPS or the building wiring socket
(grounded shockproof socket) during operation as this would remove the ground
to the UPS and of all connected loads.
The UPS features its own internal current source (batteries). There is risk of
electrical shock from the UPS output sockets or output terminal block even if the
UPS is not connected to mains supply.
In order to fully disconnect the UPS, first press the ON/OFF button to turn off
the UPS, then disconnect the mains lead.
Ensure that no liquid or other external objects can enter the UPS.
Do not remove the enclosure. This system is to be serviced by qualified service
personnel only.
Remove the protective panel only after disconnecting the terminal connections.

-3-
1.3 Maintenance, servicing and faults
The UPS operates with hazardous voltages. Repairs may be carried out only by
qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the
mains power supply (building wiring socket), components inside the UPS are still
connected to the battery which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the
batteries. Verify that no current is present and no hazardous voltage exists in the
capacitor or BUS capacitor terminals.
Batteries must be replaced only by qualified personnel.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Verify that no voltage is present before servicing.
Batteries have a high short-circuit current and pose a risk of shock. Take all
precautionary measures specified below and any other measures necessary
when working with batteries: remove all jewelry, wristwatches, rings and other
metal objects, only use only tools with insulated grips and handles.
When changing batteries always replace with the same quantity and the same
type of batteries.
Do not attempt to dispose of batteries by burning them. It could cause an
explosion.
Do not open or modify batteries. Effluent electrolyte can cause injury to the skin
and eyes and is considered toxic.
Please replace the fuse only by a fuse of the same type and of the same
amperage in order to avoid fire hazards.
Do not dismantle the UPS, except for qualified maintenance personnel.
1.4 Transport
Please transport the UPS only in the original packaging (to protect against shock
and impact).
1.5 Storage
The UPS must be stockpiled in the room where it is ventilated and dry.

-4-
1.6 Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted emission................................:IEC/EN 62040-2
Category C2
Radiated emission...................................:IEC/EN 62040-2
Category C2
Harmonic current...................................:IEC/EN 61000-3-2
Voltage fluctuation and flicker...............:IEC/EN 61000-3-3
*EMS
ESD........................................................:IEC/EN 61000-4-2
Level 3
RS..........................................................:IEC/EN 61000-4-3
Level 3
EFT.........................................................:IEC/EN 61000-4-4
Level 4
SURGE...................................................:IEC/EN 61000-4-5
Level 4
CS………………………………………….…..……...:IEC/EN 61000-4-6
Level 3
MS……………………………….…………………..: IEC/EN 61000-4-8
Level 4
Voltage Dips………………...…………..….....: IEC/EN 61000-4-11
Low Frequency Signals.........................:IEC/EN 61000-2-2

-5-
2. Description of commonly used symbols
Some or all of the following symbols may be used in this manual. It is advisable to
familiarise yourself with them and understand their meaning:
3. Introduction
This Online-Series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically for
sensitive IT equipment.
The double-converter principle eliminates all mains power disturbances. A rectifier
converts the alternating current from the socket outlet to direct current. This
direct current charges the batteries and powers the inverter. On the basis of this
DC voltage, the inverter generates a sinusoidal AC voltage, which permanently
supplies the loads.
Computers and periphery are thus powered entirely by the mains voltage. In the
event of power failure, the maintenance-free batteries power the inverter.
This manual covers the UPS listed as follows. Please confirm whether it is the
model you intended to purchase by performing a visual inspection of the Model
No. on the rear panel of the UPS.

-6-
The Model List
Item
Model name
Power
Rating
Model
type
Model description
Other
1
C400-010-B
1000VA/
900W
Tower
Standard model
Single Phase input
Single Phase
Output
2
C400-010-C
1000VA/
900W
Tower
Long Backup time
model
Single Phase input
Single Phase
Output
3
C400-020-B
2000VA/
1800W
Tower
Standard model
Single Phase input
Single Phase
Output
4
C400-020-C
2000VA/
1800W
Tower
Long Backup time
model
Single Phase input
Single Phase
Output
5
C400-030-B
3000VA/
2700W
Tower
Standard model
Single Phase input
Single Phase
Output
6
C400-030-C
3000VA/
2700W
Tower
Long Backup time
model
Single Phase input
Single Phase
Output
UPS Block Diagram

-7-
4. Panel Description
The display panel of C400-010 / 020 / 030-B (C) are all the same as shown as
below:
■Figure 4.1 Display panel
4.1 Button
Switch
Function
ON/Silence
Button
Turn on UPS system:
By pressing the ON-Button continuously for more than 1 second the UPS
system is turned on.
Deactivate acoustic alarm:
By pressing this Button an acoustic alarm can be deactivated in the
battery mode.
By short touch this Button all acoustic alarms can be deactivated in all
modes.
Perform battery test:
By pressing this Button the UPS can do a battery test within Line mode,
ECO mode or CVCF mode.
OFF
Button
When mains power is normal, the UPS system switches to No output or
Bypass mode by pressing OFF-Button “ “, and the inverter is off. At this
moment, if Bypass is enabled, then the output sockets are supplied with
voltage via the bypass if the mains power is available.
Deactivate acoustic alarm:
By pressing this Button an acoustic alarm can be deactivated in the bypass
mode.
Release the UPS from fault mode and EPO status.
Select
Button
The output voltage, frequency, Bypass disable/enable and operating
mode in No output or Bypass mode, Battery Ah, Battery remain time

-8-
Enter
Button
display disable/enable and Charger current in all modes, could be selected
by pressing Select-Button, and confirmed by pressing Enter-Button.
4.2 LCD description
■Figure 4.2 LCD display
LCD icon function
Display
Function
Input Information
Indicates input voltage/frequency value,
which are displayed alternately.
Indicates the input is connected with
mains, and the input power is single
phase input.
Output Information
Indicates output voltage/frequency value,
which are displayed alternately.

-9-
Load Information
Indicates the load level. Every grid
represents the level of 20%. One grid
would be displayed if the level is 0~20%
Battery Information
Indicates the battery capacity. Every grid
represents the capacity of 20%.
Mode/Fault/Warning Information
Indicates the operating mode Fault type,
Warning type or battery remaining time,
several warning types at the same time
could be displayed alternately.
Misc
Indicates the UPS is in setting mode.
Indicates the UPS is in Fault mode or has
some warnings.

-10-
5. Connection and Operation
5.1 Inspection:
Inspect the packaging carton and its contents for damage. Please inform the
transport agency immediately if you find signs of damage.
Please keep the packaging in a safe place for future use.
Note: To avoid any safety issue, please ensure that the incoming feeder (mains)
is isolated completely while whole installing process.
5.2 Connection
(1) UPS Input Connection
If the UPS is connected via the power cord, please use the corect socket
with protection against electric current, and pay attention to the capacity
of the socket. The UPS System has an input breaker on the standard
cabinet.
(2) UPS Output Connection
The output sockets and types of the UPS are shown below:
Model No.
Output Socket -IEC(pcs)
C400-010-B
4*C13
C400-010-C
3*C13
C400-020-B
4*C13
C400-020-C
6*C13
C400-030-B
4*C13+1*C19
C400-030-C
3*C13+Terminal block
The system may be installed and wired only by qualified
electricians in accordance with applicable safety regulations!
When installing the electrical wiring, please note the nominal
amperage of your incoming feeder.

-11-
For C400-030-C IEC model, connect the output and ground wires to the
terminal block according to Figure 5.1 and the table 5.1
■Figure 5.1 Output Connection diagram of C400-030-C IEC model
Table 5.1
Terminal
position
Wire function
Terminal wire size
rating
Tightening torque
L
Line Out
1.5mm2-2.5mm2
(14AWG-12AWG )
0.5Nm(4.4 Lb In)
N
Neutral Out
Output Ground

-12-
(3) Battery Input Connection for long backup time model
When connecting the external batteries it’s recommended to pay
attention to these following items:
Use the battery pack with voltage:
24VDC for C400-010-C (2 pcs of 12V batteries),
48VDC for C400-020-C (4 pcs of 12V batteries),
72VDC for C400-030-C (6 pcs of 12V batteries)
Note: Connection of batteries more than or less than required will cause
abnormality or permanent damage.
One Standard type battery connector on the rear panel is used for
connecting the battery pack.
The battery connection procedure is very important. Any incompliance may
result in the risk of electric shock. Therefore, the following steps must be
strictly complied with.
Prepare the battery cable with Standard type connector which should be
able to carry the current.
If there is a battery breaker then turn it off first. Then connect the battery
cable to the Standard type battery connector on the real panel.
Connect the input power cord of the UPS to mains power supply, the
battery would start to be charged.
Caution!
A DC breaker must be connected between the UPS and external
battery if not using a standard battery pack.
Caution!
The output sockets of the UPS system may still be electrically live
even if the power supply system has been disconnected.

-13-
(4) EPO Connection
EPO (Emergency Power Off) function is a standard feature for these
UPS, the polarity of EPO is configurable; EPO is normally close as
default setting. If the connection between two ports of the EPO
connector is disconnected, EPO function will be active and the UPS
will stop output power immediately.
● Normally open
Normally the EPO connector is open on the rear panel. Once the
connector is closed with a wire, the UPS will stop output until EPO
status is reset.
Disable EPO status Enable EPO status
● Normally closed
Normally EPO connector is closed with a wire on the rear panel. Once
the connector is open, the UPS will stop output until the EPO status
is disabled.
Enable EPO status Disable EPO status

-14-
5.3 Battery recharge
Fully charge the batteries (external) of the UPS system by leaving the UPS
system connected to the mains power for 1-2 hours approximately. The UPS
system is able to operate immediatly without undertaking the recharging
process, but the backup time may be shorter than the nominal value
specified.
5.4 Turn on the UPS
(1) With mains power connecting:
Press On-button continuously for more than 1 second to turn on the UPS,
the UPS will move onto the Line mode; the LCD screen will indicate the
status of the UPS.
(2) Without mains power connecting:
Even though mains power is not connected to the UPS, the UPS still can
be turned on by just simply pressing on button continuously for more
than 1 second with external batteries connected, the UPS will get into the
Battery mode, and the LCD screen will indicate the state of the UPS.
Note: The default setting for bypass mode is no output after UPS is
connected to mains power and the breaker is turned on. This can be
configurable.
5.5 Test function
Test function is checking battery performance of the UPS system by pressing
the On-Switch for more than 1 second while the UPS is operating in Line
mode. The UPS will detect whether the battery is connected or the battery
has reduced capacity. The UPS can also implement this test automatically
and periodically, the time period is configurable.

-15-
5.6 Turn off the UPS
(1) In Line Mode:
Press OFF button continuously for more than 1 second to turn off the UPS,
the UPS will go into no output or bypass mode. In this situation, the UPS
might have output power if bypass mode is enabled. Disconnect the
mains power to turn off the output.
(2) In Battery Mode:
Press OFF button continuously for more than 1 second to turn off the UPS,
the UPS will get into no output or standby mode. After 10s UPS will be
shutdown completely.
5.7 Audible alarm mute function
If the audio alarm is not required in battery mode, the audio alarm is able to
be muted by pressing the ON button continuously for more than 1 second.
Moreover, the audible alarm will be active again when the battery reaches
low status to remind the end user that UPS output power will shutdown
soon.
If the audible alarm is not required in bypass mode, the audible alarm is able
to be muted by pressing the OFF button continuously for more than 1 second.
This action doesn’t affect the warning and fault alarm.
In any mode, if the warning or fault alarm is not required, you can mute it by
pressing the ON button for less than 0.5 second, and enable it by pressing the
ON button for less than 0.5 second again. If a new warning or fault alarm
appears, the buzzer will beep again.

-16-
Alarm Table List
6. Operating Mode for All Models
Different messages/strings will be displayed on the LCD screen corresponding to
different UPS operating modes, as shown in the following table 6.1. Different
Warning/fault code, as shown in the following table 6.2. Only one normal
operating string or fault string is presented a time. However if several warnings
happen at the same time, they will be displayed on the LCD alternately. In this
case, the normal operating mode string and the warning string will be shown
circularly. Once a fault comes forth, all previous warnings will not be shown again;
only the fault string will be presented.
Table 6.1:Operating Mode
Operating mode
Code
No output mode
STbY
Bypass mode
bYPA
Line mode
LINE
Battery mode
bATT
Battery test mode
TEST
ECO mode
ECO
Converter mode
CVCF
NO.
Status
Alarm
1
Battery mode
Beep once every 4 sec
2
Battery mode with battery low
Beep once every sec
3
Bypass mode
Beep once every 2 min
4
Overload
Beep twice every sec
5
Warning active
(see Warning & Fault Code Table )
Beep once every sec
6
Fault active
Beep continuously
7
Button function active
Beep once

-17-
Table 6.2:Warning & Fault Code
Warning
String
Site fail
SITE
Fan fail
FANF
Battery over voltage (over charged)
HIGH
Battery low
bLOW
Charge fail
CHGF
Inverter temperature high
TEPH
Battery open
bOPN
Overload
OVLD
Digital bigger charger fail
dCHF
Inner temperature high
ITPH
Fault
String
Inverter short
SHOR
Overload fault
OVLD
Inverter soft start fail
ISFT
Bus soft start fail
bSFT
Over temperature fault
OVTP
Inverter Volt Low
INVL
Inverter Volt High
INVH
Bus volt over
bUSH
Bus volt Low
bUSL
Bus short
bUSS
Inverter NTC open
NTCO
Emergency Power Off
EPO
6.1 Line mode
The LCD display in Line mode is shown as figure 6.1. The information about
the mains power, the battery level, the UPS output and the load level will be
displayed. The “LINE” string indicates UPS working in Line mode.
■Figure 6.1 Line mode
This manual suits for next models
5
Table of contents
Other CertaUPS UPS manuals

CertaUPS
CertaUPS C200-1500 User manual

CertaUPS
CertaUPS PowerControl C500R-060-B UPS User manual

CertaUPS
CertaUPS C60 Series User manual

CertaUPS
CertaUPS C650 User manual

CertaUPS
CertaUPS C200 Series User manual

CertaUPS
CertaUPS C450R User manual

CertaUPS
CertaUPS C500 User manual

CertaUPS
CertaUPS C400R-010-B User manual

CertaUPS
CertaUPS C300R-020-B User manual

CertaUPS
CertaUPS C300R User manual