CertaUPS C400 Series User manual

C400 USER MANUAL
A COMPLETE INSTALLATION
AND USER GUIDE
THE C400 SERIES
An uninterruptible power supply (UPS)
incorporating online double conversion
technology, which eliminates all mains
power disturbances.
www.certaups.com
For assistance please contact your local
CertaUPS partner.

C400 User Manual
Page 4
Contents
SAFETY INFORMATION............................................................................................................................6
USER MANUAL SYMBOLS....................................................................................................................6
HANDLING...........................................................................................................................................6
OPERATING SAFETY.............................................................................................................................7
THE MODEL LIST..................................................................................................................................8
THE TECHNOLOGY...............................................................................................................................8
SUITABLE APPLICATIONS.....................................................................................................................9
UPS STANDARDS .................................................................................................................................9
UPS INSTALLATION................................................................................................................................10
UNPACKING.......................................................................................................................................10
C400 BOX CONTENTS CHECKLIST......................................................................................................10
INSTALLATION...................................................................................................................................11
C400 TOWER MODEL INSTALLATION................................................................................................11
C400 SERIES STARTUP AND SHUTDOWN..............................................................................................12
STARTING THE UPS WITH MAIN POWER PRESENT...........................................................................12
STARTING THE UPS FROM BATTERY .................................................................................................12
UPS SHUTDOWN WITH MAINS POWER............................................................................................13
UPS SHUTDOWN WITHOUT MAINS POWER.....................................................................................13
C400 SERIES OPERATION ..................................................................................................................13
DISPLAY FUNCTIONS .........................................................................................................................13
LCD DESCRIPTION..............................................................................................................................14
USER SETTINGS .................................................................................................................................15
COMMUNICATION PORTS.....................................................................................................................16
EPO CONNECTION.............................................................................................................................16
INTERFACE CARDS (OPTIONAL).........................................................................................................16
SOFTWARE ........................................................................................................................................16
WINPOWER INSTALLATION...............................................................................................................17
UPS MAINTENACE.................................................................................................................................18
UPS CARE...........................................................................................................................................18
TRANSPORTING THE UPS..................................................................................................................19
STORING THE UPS .............................................................................................................................19
BATTERY REPLACEMENT...................................................................................................................19
RECYCLING A UPS..............................................................................................................................20

C400 User Manual
Page 5
TECHNICAL DATA ..................................................................................................................................23
OPERATING ENVIRONMENT .............................................................................................................23
RUNTIMES.........................................................................................................................................24
DIMENSIONS AND WEIGHTS.............................................................................................................24

C400 User Manual
Page 6
SAFETY INFORMATION
USER MANUAL SYMBOLS
The following will be referenced throughout this document.
SYMBOL
DEFINITION
Caution! Follow instructions carefully
Caution, risk of electric shock
Power On/Off
Alternating current (AC)
Direct Current (DC)
Grounding
Recycle
Not to be disposed of in general waste
Waste electrical equipment or electronic equipment (WEEE) should not be disposed of in the general waste. CertaUPS
systems should always be disposed of at a proper recycling/hazardous waste disposal centre. Please see page 10 for disposal
guidance.
HANDLING
UPS handling weight guidelines
<18kg (<40lb)
One-person
18 –32 kg (40 –70 lb)
Two-person
32 –55 kg (70 –120 lb)
Three-person
>55 kg (>120 lb)
Forklift
Before any handling please ensure that the following precautions are taken:
QUALIFIED PERSONNEL Any persons servicing the UPS must be qualified and knowledgeable in UPS
technology and batteries
CLOTHING Correct PPE should always be worn
POWER OFF Ensure all mains power is disconnected before starting work
TOOLS always use insulated tools. Do not lay tools down near the Ups or batteries. Follow all insolation
procedures.
UPS GROUNDING The UPS must always be properly grounded
KEEP THESE INSTRUCTIONS IN A SAFE PLACE
This section contains essential information and instructions that should be followed to ensure the safe handling,
installation and maintenance of CertaUPS equipment and batteries.
AUTHORISED PERSONNEL TO HANDLE ONLY
UPS systems contain both AC and DC when disconnected from the mains outlet and should only be serviced
by qualified persons.

C400 User Manual
Page 7
CAUTIONARY NOTES
Please be aware of the following risks when handling and operating CertaUPS units.
RISK TYPE
DETAILS
Electric shock
Even after the unit is disconnected from the mains power supply (building outlet
socket), components inside the UPS are still energised from the battery which is
potentially dangerous
The battery circuit is not isolated from the input voltage. Hazardous voltages may
occur between the battery terminals and the ground. Verify that no voltage is present
before servicing.
Hazardous voltages
Repairs must be carried out only by qualified UPS Engineer.
OPERATING SAFETY
Before operating any UPS system, please read the following guidance:
DO NOT install the UPS in a humid environment or expose to liquids
DO NOT block the ventilation of the UPS
DO NOT expose the UPS to direct sunlight or source of heat
DO NOT exceed ambient temperatures when operating or storing the UPS
DO NOT allow excessive particulates or foreign bodies to enter the UPS
DO follow all connection procedures and operational instructions in the order in which they appear within this
manual
DO check that the indicators on the rating plate correspond to the AC powered system and to the actual
electrical consumption of all the equipment to be connected to the UPS
DO ensure the outlet is installed near the UPS and is easily accessible
DO store the UPS in a dry environment
DO keep the UPS in a well-ventilated area
Additional considerations:
•To reduce the risk of fire or injury the unit must be supplied by a circuit which is protected by overcurrent by
means of an MCB or other protective devices.
•The upstream circuit breaker or local means of isolation must be easily accessible. The unit can then be
disconnected from the AC power source by opening the circuit breaker/isolator.
•If An additional AC contactor is to be used for back feed protection, this must comply with IEC/EN 62040-1
•Disconnection and overcurrent protection devices shall be provided by others for permanently connected
AC input and output circuits.
•The admissible storage temperature range is -15ºC to +40ºC with battery, -25ºC to +60ºC without battery.
•The operating temperature should be kept between 20 ºC to 25 ºC, failure to do so will reduce the expected
battery design life
FOR FURTHER INFORMATION ON REPLACEMENT PARTS AND SERVICING PLEASE CONTACT YOUR CertaUPS PARTNER.

C400 User Manual
Page 8
PRODUCT OVERVIEW
The CertaUPS C400 series is an uninterruptible power supply (UPS) incorporating online double conversion technology,
which eliminates all mains power disturbances.
THE MODEL LIST
Please check that the unit you have purchased is correct by referring to the model number, which appears on the
rear panel of the UPS unit.
ITEM
MODEL NAME
POWER RATING
MODEL TYPE
MODEL
DESCRIPTION
OTHER
1
C400-010-B
1000VA/900W
Tower
Internal battery
model
Single Phase input
Single Phase output
2
C400-010-C
1000VA/900W
Tower
Charger model
Single Phase input
Single Phase output
3
C400-020-B
2000VA/1800W
Tower
Internal battery
model
Single Phase input
Single Phase output
4
C400-020-C
2000VA/1800W
Tower
Charger model
Single Phase input
Single Phase output
5
C400-030-B
3000VA/2700W
Tower
Internal battery
model
Single Phase input
Single Phase output
6
C400-030-C
3000VA/2700W
Tower
Charger model
Single Phase input
Single Phase output
THE TECHNOLOGY
The C400 UPS series uses online double conversion technology, which ensures that clean and stable power is always
provided. An online UPS operating in, line mode will always provide a consistent supply of AC power to the load. This
is done by using the battery and the inverter to ensure a clean stable and supply. When the mains power fails, the
battery is no longer supplied by the rectifier and the batteries begin to discharge.
Once the battery is depleted the UPS will no longer be able to generate AC power through the inverter and the output
will in turn cease. Once the mains power is restored the rectifier will charge the batteries and then allow the inverter
to provide power to the load once more.
Key features:
•Wide input voltage window
•0.9 power factor
•Frequency converter feature
•EPO connection
•Future expansion or redundancy
•Internal manual bypass
•Small footprint
FULL PRODUCT DETAILS CAN BE FOUND AT WWW.CERTAUPS.COM/PRODUCT/CERTAUPS-C400/

C400 User Manual
Page 9
SUITABLE APPLICATIONS
Ideally suited for small to medium-sized offices, telecoms centres and security facilities. Please see list below (not
exhaustive):
Small data centres
Server room
IT facilities
Telecoms
Networking
ACCESSORIES
The following accessories are available to add to your C400 for enhanced functionality contact your CertaUPS supplier
for further details.
PART
DESCRIPTION
C-NMC
SNMP Network management card
C-REL
Relay card
C-DB9REL
Relay card (DB9 Interface)
C-EMP
Environmental monitoring probe (SNMP required)
C-MOD1
Modbus interface
C-MBS 1-3
Rack-mountable Maintenance bypass switch
UPS STANDARDS
DESCRIPTION
STANDARD
Conduction/Radiation
IEC/EN 62040-2
Harmonic Current
IEC/EN 61000-3-2
Voltage Fluctuation
IEC/EN 61000-3-3
ESD
IEC/EN 61000-4-2
RS
IEC/EN 61000-4-3
EFT
IEC/EN 61000-4-4
Surge
IEC/EN 61000-4-5
CS
IEC/EN 61000-4-6
MS
IEC/EN 61000-4-8
Voltage Dips
IEC/EN 61000-4-11
Low frequency signals
IEC/EN 61000-2-2
PLEASE FIND UPS PRODUCT DIAGRAMS AND FULL TECHNICAL SPECIFICATIONS ON PAGE 32 OR VISIT
WWW.CERTAUPS.COM/PRODUCT/CERTAUPS-C400/

C400 User Manual
Page 10
UPS INSTALLATION
INSPECTION
Every effort is made to ensure that CertaUPS systems are packaged as safely as possible to ensure that no damage is
incurred during shipment. Please visually inspect the UPS when it is received. Please keep all packaging in a safe place
for future use.
UNPACKING
The UPS unit must be positioned in a well-ventilated area that is free from excessive dust, heat and moisture. Please
take note of the specified operating temperatures and remain within these guidelines.
•Unpacking the unit in a low-temperature environment may cause condensation to occur in and on the
device. DO NOT install the UPS/ External Battery Module (EBM) until the inside and outside of the devices are
clear of condensation.
•The UPS/EBM units are heavy. Follow any special precautions provided on the packaging.
•Unpack the equipment and remove all packaging materials. DO NOT lift the using the front panel and rear
panel.
Rackmount/Tower model
C400 BOX CONTENTS CHECKLIST
C400 Series UPS
USB A to B
Software CD
Quick Start Guide
Warranty Card
PLEASE ENSURE ALL SAFETY INSTRUCTIONS HAVE BEEN OBSERVED AND UNDERSTOOD PRIOR TO UNPACKING AND
INSTALLING THE UPS
IF THE DEVICE IS DAMAGED, PLEASE NOTIFY THE CARRIER IMMEDIATELY
PACKING MATERIALS MUST BE DISPOSED OF
IN COMPLIANCE WITH ALL LOCAL WASTE
MANAGEMENT REGULATIONS.
RECYCLING SYMBOLS ARE PRINTED ON THE
PACKING MATERIALS TO FACILITATE
SORTING.
IF ANY OF THE ITEMS ARE MISSING FROM THE UPS BOX PLEASE NOTIFY YOUR SUPPLIER
DO NOT FORGET TO REGISTER THE UPS WARRANTY WWW.CERTAUPS.COM/SUPPORT/WARRANTY-REGISTRATION/

C400 User Manual
Page 11
INSTALLATION
•DO NOT connect the UPS to a mains supply until installation is completed
•Ventilation of the UPS is important for proper operation. Ensure the air vents on the front, side and rear of the
UPS are clear. Allow adequate space around the UPS. The airflow diagram is shown as below:
Installation considerations:
•The final location of the UPS unit must be on a flat stable surface in a well-ventilated environment
•DO keep at least 150mm of free space behind the rear panel
•If installing an additional unit, place it next to the first unit in its final location
•DO allow the UPS to reach ambient temperature before turning on
•The UPS needs to be fully charged to achieve full autonomy
C400 TOWER MODEL INSTALLATION
STEP ONE
Ensure utility power is switched off.
STEP TWO
Carefully place the UPS in its final location
STEP THREE
If not installing additional EBMs skip to step six.
Position the EBM adjacent to the UPS, ensure adequate space for UPS ventilation.
STEP FOUR
Connect the EBM to the UPS
STEP FIVE
To connect to multiple EBMs the EBM cable is connected directly into the previously installed EBM
STEP SIX
After setting up the UPS, the load can then be connected. Please make sure the load equipment is turned off before connecting
all loads into the output ports
STEP SEVEN
Plug the UPS into a mains power socket and turn Utility power on. The UPS will power on in bypass mode and begin charging
STEP EIGHT
To switch the UPS from bypass mode to online press and hold the ‘ON/Silence’ button for 1 second the unit will beep and the LCD
display will show “LINE” signalling that the UPS is powered and protecting the equipment
DO NOT MAKE ANY UNLICENSED MODIFICATIONS TO THE UPS. THIS MAY INCUR DAMAGE AND AFFECT THE UPS
WARRANTY.
A QUICK START VIDEO GUIDE FOR THE C400 TOWER MODEL IS AVAILABLE AT WWW.CERTAUPS.COM/MEDIA
C400 battery model tower variant.

C400 User Manual
Page 12
C400 battery tower variant.
C400 SERIES STARTUP AND SHUTDOWN
STARTING THE UPS WITH MAIN POWER PRESENT
Please switch off the connected loads before turning on the UPS, and switch on connected devices one by
one after the UPS is turned on. Switch off all connected loads before turning off the UPS.
The C400 Series UPS can be started either “hot” or “Cold”, meaning the UPS can be activated regardless of
whether the unit has a main supply (Hot) or if no mains power is available (Cold).
Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
To start the UPS via mains power (Hot start):
1. Check all the connections are properly connected and correct.
2. Supply mains power to the UPS, the fans will start and the LCD will show the default UPS status summary
screen displaying “byPA” to signify the unit is in internal bypass mode.
3. Hold the “On/Science”button continuously for 1 second, the buzzer will beep and the UPS will start to turn
on.
4. After a few seconds, the UPS will start in Line mode. If the utility power is abnormal, the UPS will transfer to
battery mode without output interruption to the UPS.
5. When the UPS is online “LINE” will be displayed on the LCD display
STARTING THE UPS FROM BATTERY
Before using this feature, the UPS must have been powered by utility power with output enabled at least
once to ensure the unit is adequately charged.
After connecting the UPS to any EBMs you should wait for 10 seconds before pressing the “On/Silence”
button for pre-charging the auxiliary power supply.
Battery start can be disabled.
To start the UPS via battery power (Cold start):
1. Check all the connections are properly connected and correct.
2. Press the “On/Silence”button continuously for more than 100ms and the UPS will power on. The fans will
start and the LCD will show “STbY” on the default UPS status summary screen after finishing the initialisation
self-test.
3. Press the “On/Silence”button continuously for 1 second the UPS will start to initialise.
4. After a few seconds, the UPS will transfer to battery mode. If the mains power comes back the UPS will
transfer to Line mode without output interruption of the UPS.
5. When the UPS is running from battery power “bATT” will be displayed on the LCD display, when main power
is restored the display will change to “LINE”.
A QUICK START VIDEO GUIDE FOR THE C400 RACKMOUNT/TOWER MODEL IS AVAILABLE AT
WWW.CERTAUPS.COM/MEDIA

C400 User Manual
Page 13
UPS SHUTDOWN WITH MAINS POWER
When in Bypass UPS output voltage is still present!
To shutdown the UPS with mains power:
1. Press the “OFF”button for 1 second.
2. After that, the UPS will transfer to bypass mode immediately and display “byPA” on the LCD.
3. In order to cut off the UPS output remove the mains power supply. A few seconds later the LCD will shut
down and no output power is available from the UPS output terminal.
UPS SHUTDOWN WITHOUT MAINS POWER
To shutdown the UPS without mains power:
1. Power off the UPS by pressing the “OFF”button for 1 second, the buzzer will beep for 300ms and “STbY” will
be displayed on the LCD at which point the UPS output will stop.
2. A few seconds later the LCD display will power off.
C400 SERIES OPERATION
FRONT PANEL
The CertaUPS C400 has a four-button user interface and a graphical LCD. It provides useful information about the
UPS itself, load status, events, measurements and settings. In the event of a critical alarm, the LCD backlight will
illuminate red.
DISPLAY FUNCTIONS
The following table shows the function of each of the buttons:
BUTTON
FUNCTION
DESCRIPTION
ON/Silence
Button
Power on
When the unit has no mains power and batteries
connected, press for >100ms to power on
Turn on
When the unit is powered on and in Standby mode, press
this button for >1s to turn on
Battery test
By pressing this Button the UPS can do a battery test within
Line mode, ECO mode or CVCF mode
Silence alarm
Pressing the button for <1s will mute/unmute any alarms
OFF
Button
Turn off
When mains power is normal, the UPS system switches to
Bypass mode when pressed
Clear fault
By pressing this button, the UPS can clear fault mode and
EPO status
Select
Button
Scroll down
The select Button allows configurable options to be
selected.
Enter
Button
Confirm
selection
Allows confirmation of options displayed via Select button
IF AN ERROR CODE APPEARS PLEASE REFER TO THE ALARMS AND FAULTS SECTION OF THE MANUAL PAGE 29 OR
CONTACT YOUR CertaUPS REPRESENTIVE

C400 User Manual
Page 14
LCD DESCRIPTION
The table below gives details on the information provided by the UPS user display:
DISPLAY
FUNCTION
INPUT
(Left side)
Alternates between displaying input voltage/frequency values.
Indicates the input is connected and supplied with mains AC.
OUTPUT
(Right side)
Alternates between displaying input voltage/frequency values.
LOAD
Indicates the load level. Each segment represents 20% of the maximum rated load. One segment
would be displayed if the level is 0~20%
BATTERY
Indicates the battery capacity. Each segment represents 20% of the full charge capacity
MODE/FAULT/WARNING
Indicates the operating mode Fault type, Warning type or battery remaining time, several warning
types at the same time will be displayed alternately.
Indicates the UPS is in setting mode.
Indicates the UPS is in Fault mode.
IF ANY OTHER STATUS APPEARS, OR FOR FURTHER GUIDANCE ON WHAT TO DO PLEASE SEE THE TROUBLESHOOTING
SECTION ON PAGE 28 OR CONTACT A CertaUPS REPRESENTIVE

C400 User Manual
Page 15
The UPS can be controlled and configured using basic button functions via the front panel, to make adjustments:
•
Hold the “Enter” button for 1 second, the UPS will beep for 300ms and the will be displayed indicating
the unit is in settings mode.
•
“OPV” will be displayed to indicate the currently selected option, to select this option to edit hold “Enter”
for a further 1 second or to move to the next option hold “select”for more than 1 second.
•
When an option is selected hold the “Select” button for 1 second to change the configured option value.
The value will flash while being edited.
•
To set a value press and hold the “Enter” button.
USER SETTINGS
The following table displays the options that can be changed by the user:
Most settings in this menu require the UPS to be in bypass to take effect.
OPTION
DESCRIPTION
AVAILABLE SETTINGS
DEFAULT SETTINGS
OPV
OUTPUT VOLTAGE
220V/230V/240V
230
OPF
OUTPUT FREQUENCY
50Hz/60Hz
ASF
bYPA
BYPASS MODE
The UPS would turn to bypass mode within a few
seconds if “Bypass Enable” (001) is selected, and
turn to no output mode within a few seconds if
“Bypass Disable” (000) is selected
000/001
001
MOdE
OPERATING MODE
UPS/ECO/CVCF
UPS
*EbAH
EXTERNAL BATTERY AH
005-300
000
bATT
BATTERY REMAINING TIME
In battery mode or battery test mode, the display
will alternate between battery time (in unit Min or
Sec) and “bATT” on the LCD every 2s.
000/001
000
*CHG
CHARGING CURRENT
3.0/6.0 (for C400-010-C)
1.5/3.0/4.5/6.0 (for C400-020/030-C)
-
*Charger models only
** Consult your CertaUPS representative before adjusting any battery settings incorrect settings may damage your
equipment.
Modes of operation
ECO mode (Economy mode)
Also called high-efficiency mode. After turning the UPS on in ECO mode, the output power will be supplied from
mains power directly via an internal filter while the mains power is within a certain range, so the high-efficiency
performance would be gained in ECO mode. Once the mains power is out of range, the UPS will transfer to battery
mode and the load will be supplied continuously by the battery.
1) ECO Mode can be enabled through the LCD setting or the software (Winpower, etc.).
2) The transfer time of UPS output from ECO mode to battery mode is less than 10ms. It is suggested that this may not
be suitable for applications involving sensitive loads.
CVCF mode
CVCF (Constant Voltage Constant Frequency) also called converter mode. The UPS will work in frequency free-run
with a fixed output frequency (50Hz or 60Hz). Once the mains are lost or abnormal, the UPS will transfer to battery
mode and the load is supplied continuously by the battery.
1) CVCF mode can be enabled through the LCD setting or the software (Winpower, etc.).
2) The normal power rating will be derated to 60% the converter mode.
BY DEFAULT, THE LCD WILL DISPLAY THE UPS STATUS SUMMARY SCREEN.

C400 User Manual
Page 16
Please contact your local CertaUPS partner for further information before configuring the UPS.
COMMUNICATION PORTS
RS232/USB
The RS232 and USB communication ports cannot be used
simultaneously.
•Connect the communication cable to the serial or USB port on
the computer.
•Connect the other end of the communication cable to the
RS232 or USB communication port on the UPS.
Both RS232 and USB connections allow for 2 way communication between the device connected and the UPS. This
can be used for both issuing configuration commands, communicating with the UPS and issuing shutdown commands.
When connected via USB to a PC the UPS will present itself as a HID compliant ACPI device allowing for zero
configuration shutdown initiated by the UPS in the event of a power failure.
EPO CONNECTION
The EPO (Emergency Power Off) connection allows the UPS to be powered off by changing the state of a normally
open circuit.
•Normally closed - Normally EPO connector is closed with a
wire on the rear panel. Once the connector is open, the UPS
will stop output until the EPO status is disabled.
INTERFACE CARDS (OPTIONAL)
The Network Management Card allows the UPS to communicate with monitoring devices by utilising network
connectivity. The C400 series has one available expansion bay for the following connectivity cards:
•NMC/SNMP Card –this interface card provides SNMP and HTTP capabilities as well as monitoring through a
Web browser interface using RJ45 10/100Mbps over TCP/IP.
•AS400 card - for RS485 communication protocol. Please contact your CertaUPS partner for details.
SOFTWARE
The C400 series is compatible with WinPower which is an open-source, online UPS monitoring and management
software tool.
MISCONFIGURATION COULD RESULT IN FAILURE OF THE EQUIPMENT AND PERSONAL INJURY.
TO REGISTER A FAULT PLEASE VISIT WWW.CERTAUPS.COM/SUPPORT/FAULT-REPORTING/

C400 User Manual
Page 17
Key features:
•Power flow display for monitoring UPS status
•Scheduled system shutdown/restart
•Warning notification via E-mail / SMS / Windows system log*
•Scheduled UPS test
•Password security protection
•Remote monitor/control via LAN
•Safety to shutdown multi-system
•Selectable User Interface (Background)
•UPS parameter setting
•SNMP Central monitoring up to 1000 units
•Record logs for analysis
•Multi-language support: English, Italian, Turkish, Spanish, French, Portuguese, Polish, Thai, Germanic, Russian
and Japanese.
*Requires a GSM modem (not supplied)
WINPOWER INSTALLATION
STEP ONE
Go to: https://www.certaups.com/downloads/ download winpower
STEP TWO
Choose the operating system you need and follow the instruction described on the website to download the software.
STEP THREE
When downloading all the required files from the internet, enter the product key:
511C1-01220-0100-478DF2A
WHEN THE INSTALLATION IS COMPLETE,
WinPOWER WILL APPEAR AS A GREEN
PLUG ICON LOCATED IN THE SYSTEM
TRAY, NEAR THE CLOCK.
FOR FURTHER GUIDANCE ON UPS MONITORING, PLEASE CONTACT YOUR CertaUPS PROVIDER OR VISIT
WWW.CERTAUPS.COM

C400 User Manual
Page 18
UPS MAINTENACE
UPS CARE
For the best preventive maintenance:
Keep the area around the equipment clean
Keep the equipment free from dust
Ensure the equipment is positioned in a well-ventilated area
For maximum battery life keep the equipment at an ambient temperature of 20-25°C (77°F max)
Carry out regular environmental and battery checks
The batteries are rated for a 3-5 year service life. The service life varies depending on the frequency of usage
and ambient temperature. Batteries used beyond expected service life will often have severely reduced
runtimes. Replace batteries at least every 4 years to keep units running at peak efficiency and prevent failure.
ADOPTING A PREVENTATIVE MAINTENANCE SCHEDULE IS CRITICAL TO ACHIEVING OPTIMUM UPS PERFORMANCE

C400 User Manual
Page 19
TRANSPORTING THE UPS
The following procedure should be performed or supervised by personnel knowledgeable about batteries
and the required precautions. Keep unauthorised personnel away from batteries. If the UPS requires any type
of transportation, the batteries must be disconnected (but not removed) before the unit is transported:
Verify that the UPS is off and disconnected from mains power
Place the UPS on a flat stable surface with the front of the cabinet facing you
Remove the UPS front cover
Disconnect the internal battery connectors
Replace the UPS front cover
To avoid damage and to prevent DOA’s always use a reputable courier for all equipment transportation.
STORING THE UPS
Where UPS equipment is stored for a long period of time, the batteries must be recharged every six months. The
optimal storage vdc for VLRA batteries, depending on the environment is between 20-40%. This can be achieved by
connecting the UPS to mains power.
DO NOT store the equipment in a warm, damp, dusty environment
DO NOT use the equipment if the batteries have not been recharged/if the recharge date exceeds six months
DO NOT Expose the UPS to direct sunlight or source of heat
DO Store the equipment in a cool, dry, clean environment
DO ensure the batteries are recharged every six months for a minimum of 48 hours
DO ensure EBMs are recharged every six months for a minimum of 3 hours
BATTERY REPLACEMENT
DO NOT Allow unauthorised personnel near the batteries. Servicing should be performed by qualified, knowledgeable personnel only
DO NOT Dispose of batteries in a fire. Batteries may explode when exposed to flame
DO NOT Open or modify the battery or batteries in any way. Released electrolyte is harmful to the skin and eyes and maybe extremely toxic
DO NOT Attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury
DO Ensure personnel servicing the batteries are all knowledgeable on the required precautions for battery servicing
DO Replace the batteries with the same type and number of batteries or battery packs
DO Dispose of the batteries responsibly. Please refer to local regulations and disposal requirements
DO Determine if the battery is inadvertently grounded. If inadvertently grounded, remove contact to ground. Contact with any part of a grounded
battery can result in electrical shock. The likelihood of shock can be reduced if grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).
DO Disconnect charging source prior to connecting or disconnecting battery terminals
Batteries can present a risk of electrical shock or burn from high short circuit current. Observe the following precautions:
Remove watches, rings, or other metal objects
Use tools with insulated handles
Do not lay tools or metal parts on top of batteries
Wear rubber gloves and boots
THE INTERNAL UPS BATTERIES MUST BE DISCONNECTED BEFORE TRANSPORT
UPS BATTERIES MUST BE RECHARGED EVERY SIX MONTHS. ALWAYS CHECK THE BATTERY RECHARGE DATE ON THE
SHIPPING CARTON BEFORE USE.
DO NOT DISCONNECT THE BATTERIES WHILE THE UPS IS IN BATTERY MODE
CONSIDER ALL WARNINGS, CAUTIONS, AND NOTES BEFORE REPLACING BATTERIES
ELECTRIC ENERGY HAZARD. DO NOT ATTEMPT TO ALTER ANY BATTERY WIRING OR CONNECTORS.
ATTEMPTING TO ALTER WIRING CAN CAUSE INJURY

C400 User Manual
Page 20
REPLACING THE EBM (charger models only)
Turn the Main battery switch (MBS) to bypass on the back of the UPS and switch off the input. The EBM(s) are then
ready to replace.
To replace the EBM(s):
1. Unplug the EBM power cable and battery detection cable from the UPS. If additional EBM(s) are installed,
unplug the EBM power cable from each EBM
2. Replace the EBM(s)
•Plug the EBM cable(s) into the battery connector(s)
•Verify that the EBM connections are secure and that adequate bend radius and strain relief exist for each
cable
•Connect the EBM cable to the UPS
•Reinstate the input supply to the UPS
Only use the correct battery pack for your UPS rating with voltage:
24VDCfor C400-010-C (2pcs of 12V batteries)
48VDC for C400-020-C (4pcs of 12V batteries)
72VDCfor C400-030-C (6pcs of 12V batteries)
Note: Connection of batteries more than or less than required will cause abnormality or permanent
damage.
To test new batteries:
1. Charge the batteries for 48 hours.
2. Press the “ON” button when the UPS is turned on
The UPS should start a battery test if:
•The batteries are fully charged
•The UPS is in Normal mode with no active alarms
•Bypass voltage is acceptable
During the battery test, the UPS transfers to Battery mode and discharges the batteries for 10 seconds. The front
panel displays “bATT”.
RECYCLING A UPS
DO NOT dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required.
Refer to your regulations for disposal requirements.
DO NOT open or modify the battery or batteries. Released electrolyte is toxic and harmful to the skin and eyes.
THE EBM IS HEAVY AND REQUIRES A MINIMUM OF 2 PEOPLE TO LIFT.
A SMALL AMOUNT OF ARCING MAY OCCUR WHEN CONNECTING AN EBM TO THE UPS.
THIS IS NORMAL AND WILL NOT CAUSE SHOCK. INSERT THE EBM CABLE INTO THE UPS BATTERY CONNECTOR
QUICKLY AND FIRMLY
CONTACT YOUR LOCAL RECYCLING OR HAZARDOUS WASTE CENTRE FOR INFORMATION ON PROPER
DISPOSAL OF THE USED EQUIPMENT.

C400 User Manual
Page 21
DO NOT discard the UPS or the UPS batteries in the general waste. This product contains sealed lead-acid
batteries and must be disposed of responsibly. For more information contact your local recycling centre.
DO NOT discard of waste electrical or electronic equipment (WEEE) in the trash. For proper disposal contact
your local recycling centre.
TROUBLESHOOTING
The C400 series is designed for durable, automatic operation. It also provides alerts whenever potential operating
problems occur.
•Alarms are displayed on the LCD status screen with the logo blinking. Some alarms may be announced by
a beep every 1 second. Example = "Battery low"
•Faults are announced by a continuous beep and red LCD backlight
ALARMS & FAULTS
Use the following troubleshooting chart to determine the UPS alarm condition.
WARNING/FAULT
PROBLEM
CAUSE
SOLUTION
/
No indication, no warning tone
even though the system is
connected to the mains power
supply
No input voltage/Breaker open
Check building wiring socket outlet and
input cable, Check the Breaker.
/
No Communication data
RS232 wire is not matched/USB
wire is not matched
Check or change the RS232/USB cable
/
Emergency supply period
shorter than nominal value
Batteries not fully charged or
require replacement
Charge the batteries until fully charged,
contact your CertaUPS representative.
FANF
Fan fail
Fan RPM out of tolerance
Check if the fan is running
HIGH
Battery over voltage
The battery is overcharged
Switching to battery mode automatically,
and after the battery voltage is normal
and the mains is normal, the UPS would
Switch to line mode automatically again.
bLOW
Battery low
Battery voltage is low
When audible alarm sounding every
second, the battery is almost empty.
bOPN*
Battery open
The battery pack is not
connected correctly
Confirm with battery test, Check the
battery bank is connected to the UPS,
Check the battery breaker
CHGF
Charger fail
The charger has failed
Contact your CertaUPS representative.
dCHF
Digital charger failure
The charger has failed
Contact your CertaUPS representative.
bUSH
Bus high
UPS internal fault
Contact your CertaUPS representative.
TO REGISTER A FAULT PLEASE VISIT WWW.CERTAUPS.COM/SUPPORT/FAULT-REPORTING/
ALARMS SHOWN ON THE CONTROL PANEL DO NOT MEAN THAT THE OUTPUT POWER IS AFFECTED. INSTEAD THEY ARE
PREVENTIVE ALARMS INTENDED TO ALERT THE USER

C400 User Manual
Page 22
bUSL
Bus low
UPS internal fault
Contact your CertaUPS representative.
bSFT
Bus soft start fail
UPS internal fault
Contact your CertaUPS representative.
bUSS
Bus short
UPS internal fault
Contact your CertaUPS representative.
TEPH
Inverter temperature high
The inside temperature of the UPS
is too high
Check the ventilation of the UPS, check
the ambient temperature.
ITPH
Inner Ambient temperature high
The ambient temperature is too
high
Check the environment ventilation.
INVH
Inverter high
UPS internal fault
Contact your CertaUPS representative.
INVL
Inverter low
UPS internal fault
Contact your CertaUPS representative.
ISFT
Inverter soft start fail
UPS internal fault
Contact your CertaUPS representative.
NTCO
Inverter NTC open
UPS internal fault
Contact your CertaUPS representative.
SHOR
Inverter short
Output short circuit
Remove all the loads. Turn off the UPS.
Check whether the output of UPS and
loads for short circuits. Make sure the short
circuit is removed, and the UPS has no
internal faults before turning on again.
OVTP
Over-temperature fault
Over-temperature
Check the ventilation of the UPS, check
the ambient temperature and ventilation.
OVLD
Overload
Overload
Check the loads and remove some non-
critical loads. Check whether some loads
are failed.
SITE
Site fail
Phase and neutral conductor at
the input of UPS system are
reversed
Rotate mains power socket by 180° or
connect the UPS system.
EPO
EPO active
EPO function is enabled
Plug into the EPO switch.
*Charger model only
Check the alarm condition and perform the applicable action to resolve the condition.
If an alarm status changes the alarm will need to be silenced again.
This manual suits for next models
6
Table of contents
Other CertaUPS UPS manuals

CertaUPS
CertaUPS Tower 6-10K User manual

CertaUPS
CertaUPS C500 User manual

CertaUPS
CertaUPS C300R User manual

CertaUPS
CertaUPS C650 User manual

CertaUPS
CertaUPS C400R Series User manual

CertaUPS
CertaUPS C60 Series User manual

CertaUPS
CertaUPS PowerControl C500R-060-B UPS User manual

CertaUPS
CertaUPS C300R-020-B User manual

CertaUPS
CertaUPS C200-1500 User manual

CertaUPS
CertaUPS C450R User manual