4.- Setup and measurements
To enter the SETUP mode, press the setup key (9), for more than 1s. If all the capacitors are disconnected, the access in immediate, otherwise a disconnection sequence
starts and then accesses to setup menu. In the SETUP mode, if no key is pressed for 3 minutes, the equipment exits such mode and returns to normal operation mode.
Key to access the SETUP mode:
- Long push to enter and exit SETUP mode. Also ELETE max values when
in the measuring mode
- Short push: to change from display mode to edit mode and vice versa.
If no key is pushed during more than 3 minutes, the regulator exits the SETUP
mode without changing the setup.
Symbol showing which parameter is being displayed or edited.
- In the display mode: Cursors to select an option.
points to the option
- In edit mode: Change a parameter value
DisplaySETUP Parameters EditSETUPparameters Description
MENU OPTIONS
Target cos ϕ (def=1)
Reactive I of 1
st
step,
C/K adjustment
Range: 0.02 – 1.00
See paragraph 6
Program setting
epends on the kvar
relationship between
successive steps.
See paragraph 4.2
elay for successive
steps (2 -99 cycles) .
Selection of Nr of
outputs , max 6 or 12
depending on type
CT connection . See
paragraph 4.3. The
display shows T1, T2,
T3, T4, T5 or T6.
Accept the option
giving cosϕ between
0.7 Ind and 0.98 Cap
CT primary current
setting. See
paragraph 4.4
4.1.- RUN & Measuring mode
In normal operation mode (RUN mode) the regulator display may show different
parameters (V, I, cosϕ, etc.) The displayed parameter is pointed by the sign .
By default the regulator displays the cosϕ, but pushing the keys the
following parameters can be explored: Current (I), Current harmonics (THD), Mains
Voltage (V), Maximum current (I MAX) y Maximum voltage (V MAX). If both keys
are pushed simultaneously the regulator displays the Nr of connected steps.
A long push of key in maximum values screen causes de deletion of recorded
max values, in other parameters visualization screens we will go to SETUP
screens.
4.2.- Program selection
This setting depends on the kvar ratio between the different capacitor steps. For
instance if the bank is 10+20+20+20 kvar the program is 1:2:2:2, so the option 122
must be selected. The program P00 of simulation allows to see on screen the steps
that it would connect without managing to do it.
Display Program Display Program Display Program
P00 Simulation 111 1:1:1:1 T11 1:1:1:1 (Total)
122 1:2:2:2 T22 1:2:2:2 (Total)
124 1:2:4:4 T24 1:2:4:4 (Total)
248 1:2:4:8 T48 1:2:4:8 (Total)
112 1:1:2:2 T12 1:1:2:2 (Total)
4.3.- Selecting the CT connection phase
Choose among the options in the table depending on CT connection and the
phases where V is measured. In normal installations (no exported energy) choose
the option for which the displayed cosϕisbetween0.7Indand0.98Cap.
Display V-I phase shift at
cosϕ
ϕϕ
ϕ=1 Measuring phases
for V Phase where TC is
connected
T1 30º L3-L2 L3
T2 270º L3-L2 L1
T3 150º L3-L2 L2
T4 210º L3-L2 L3 (CT reversed)
T5 90º L3-L2 L1 (CT reversed)
T6 330º L3-L2 L2 (CT reversed)
4.4.- Selecting the rated primary current of CT
If the LED is blinking indicates that we are in SETUP mode and
adjusting primary CT current. When in RUN mode or when Iprimary is displayed,
the LED indicates whether the displayed current has a scale factor x1 (LED OFF)
or x10 (LED ON)
5.- Error Codes
ERR C DE DISPLAY DESCRIPCIÓN ACTUACIÓN
000 Alll zeros Load current below measuring threshold or
CT not connected
Forces all the
outputs OFF
E.02 cos ϕ and E.02
alternate blinking
Overcompensation. The regulador is asking to
disconnect Cs and they are all disconnected
NO ACTION
E.03 cos ϕ and E.03
alternate blinking
Sub-compensation. The regulator is asking for more
Cs and they are all connected
NO ACTION
E.04 cos ϕ and E.04
alternate blinking
Over current. The current is + 20%. Above primary
rated current
NO ACTION
E.05 cos ϕ and E.05
alternate blinking
Overvoltage. Voltage is +15%. Above rated voltage NO ACTION
6.- C/K table depending on initial cosϕ
ϕϕ
ϕ, desired cosϕ
ϕϕ
ϕand CT ratio
CT Ratio Lower step reactive power (kvar) at 400V
CT 2.5 5,00 7.5 10,0 12,5 15,0 20,0 25,0 30,0 37,5 40,0 50,0 60,0 75,0 80,0
150/5 0,12 0,24 0,36 0,48 0,60 0,72 0,96
200/5 0,09 0,18 0,27 0,36 0,45 0,54 0,72 0,90
250/5 0,07 0,14 0,22 0,29 0,36 0,43 0,58 0,72 0,87
300/5 0,06 0,12 0,18 0,24 0,30 0,36 0,48 0,60 0,72 0,90 0,96
400/5 0,05 0,09 0,14 0,18 0,23 0,24 0,36 0,48 0,58 0,67 0,72 0,87
500/5 0,07 0,11 0,14 0,18 0,22 0,29 0,36 0,45 0,54 0,54 0,72 0,87
600/5 0,06 0,09 0,12 0,15 0,18 0,24 0,30 0,36 0,45 0,48 0,60 0,72 0,90 0,96
800/5 0,07 0,09 0,11 0,14 0,18 0,23 0,27 0,33 0,36 0,45 0,54 0,68 0,72
1000/5 0,05 0,07 0,09 0,11 0,14 0,18 0,22 0,27 0,29 0,36 0,43 0,54 0,57
1500/5 0,05 0,06 0,07 0,10 0,12 0,14 0,18 0,19 0,24 0,29 0,36 0,38
2000/5 0,05 0,07 0,09 0,11 0,13 0,14 0,18 0,22 0,27 0,28
2500/5 0,06 0,07 0,09 0,10 0,12 0,14 0,17 0,22 0,23
3000/5 0,05 0,06 0,07 0,09 0,10 0,12 0,14 0,18 0,19
4000/5 0,05 0,06 0,07 0,09 0,11 0,14 0,14
C/K calculation:
If It is the primary rated current of the CT and
Ic the rated current of the lower capacitor step,
the C/K must be set according to the
calculations shown below:
Example : CT current ratio = 500/5
Lower step power: 60 kvar at 400V
A7,86
40073,1
000.60
I ;100
5
500
K
C
=
×
===
867,0
7,86
Ic
K/C ===
K
=
V.3
Q
I
C
=
C K
/=
For different voltages (V) of 400V, table result must be multiply for 400/V, or calculate C/K parameter using the expressions.
7.- Technical Service
For any inquiry about the regulator operation or in case of malfunction, see
detailed manual at www.circutor.es or contact with technical service.