CONDUIT GLAND FOR USE WITH UNARMOURED AND
BRAID ARMOURED CABLES IN EXPLOSIVE ATMOSPHERES
TECHNICAL DATA
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-
Locknut, Earth Tag, Serrated Washer, Entry Thread (I.P.) Sealing Washer, Shroud
INSTALLATION INSTRUCTIONS
FOR A2FFC CONDUIT GLAND
Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS
Tel: +44 191 265 7411 • Fax: +44 1670 715 646
E-Mail: [email protected].uk • Web: www.cmp-products.com
CABLE GLAND TYPE : A2FFC
INGRESS PROTECTION : IP66, IP67, IP68
PROCESS CONTROL SYSTEM : ISO 9001
ISO/IEC 80079-34:2011
SCAN FOR INSTALLATION VIDEOS
Note: Standard Seal (Black) Temperature Range = -60°C to +130°C,
High Temperature Seal (Brown) Temperature Range = -20°C to +200°C for High Temperature Seal add ‘HT’ to Ordering Reference after Gland Type e.g. 20SA2FFCHT1RAC025.
Cable Gland Selection Table
Cable
Gland
Size
Entry
Threads
Thread Length
(Metric)
(Alternate Metric
Thread Lengths
Available)
Diameter of
Cable
Specific
Internal
Diameter of
Conduit
Maximum
External
Diameter of
Conduit
Across
Flats
Across
Corners Protrusion
Length
Maximum
Envelope
Diameter
Combined Ordering Reference
(*Brass Metric) Cable
Gland Weight
(Kgs)
Min Max Max Max Size Type Ordering Suffix
20S16 M20 x 1.5 15.0 3.2 4 .1 5.1 12.0 24.0 26.4 33.2 26.4 20S16 A2FFC 1RAC000 0.09
20S16 M20 x 1.5 15.0 3.2 5.2 6.8 13.0 24.0 26.4 33.2 26.4 20S16 A2FFC 1RAC001 0.09
20S16 M20 x 1.5 15.0 3.2 5.5 7.8 13.0 24.0 26.4 33.2 26.4 20S16 A2FFC 1RAC004 0.09
20S16 M20 x 1.5 15.0 3.2 8.0 9.1 15.0 24.0 26.4 33.2 26.4 20S16 A2FFC 1RAC009 0.08
20S16 M20 x 1.5 15.0 3.2 8 .1 9.5 15.0 24.0 26.4 33.2 26.4 20S16 A2FFC 1RAC010 0.09
20S16 M20 x 1.5 15.0 3.2 8 .1 10.2 16.0 24.0 26.4 33.2 26.4 20S16 A2FFC 1RAC020 0.09
20S16 M20 x 1.5 15.0 3.2 8 .1 10.9 17.0 24.0 26.4 33.2 26.4 20S16 A2FFC 1RAC025 0.09
20S16 M20 x 1.5 15.0 3.2 8 .1 11.7 17.4 24.0 26.4 33.2 26.4 20S16 A2FFC 1RAC030 0.09
20S M20 x 1.5 15.0 6.1 11.4 13.0 20.0 24.0 26.4 33.1 26.4 20S A2FFC 1RAC040 0.09
20S M20 x 1.5 15.0 6.1 11.7 13.9 20.0 24.0 26.4 33.1 26.4 20S A2FFC 1RAC045 0.09
20S M20 x 1.5 15.0 6.1 11.7 14.7 21.5 24.0 26.4 33.1 26.4 20S A2FFC 1RAC060 0.09
20 M20 x 1.5 15.0 6.5 13.1 15.6 21.6 27.0 29.7 35.4 29.7 20 A2FFC 1RAC050 0.10
20 M20 x 1.5 15.0 6.5 14.0 16.9 23.4 27.0 29.7 35.4 29.7 20 A2FFC 1RAC066 0.10
20 M20 x 1.5 15.0 6.5 14.0 18.0 24.0 27.0 29.7 35.4 29.7 20 A2FFC 1RAC070 0.10
20 M20 x 1.5 15.0 6.5 14.0 18.7 25.0 27.0 29.7 35.4 29.7 20 A2FFC 1RAC075 0.10
20 M20 x 1.5 15.0 6.5 14.0 20.0 26.3 27.0 29.7 35.4 29.7 20 A2FFC 1RAC080 0.12
20 M20 x 1.5 15.0 6.5 14.0 20.5 28.0 27.0 29.7 35.4 31.0 20 A2FFC 1RAC085 0.11
25 M25 x 1.5 15.0 11.1 15.3 17.6 25.0 36.0 39.6 43.1 39.6 25 A2FFC 1RAC100 0.16
25 M25 x 1.5 15.0 11.1 18.4 20.7 27.0 36.0 39.6 43.1 39.6 25 A2FFC 1RAC105 0.16
25 M25 x 1.5 15.0 11.1 19.0 22.3 28.5 36.0 39.6 43.1 39.6 25 A2FFC 1R AC110 0.17
25 M25 x 1.5 15.0 11.1 20.0 23.7 32.0 36.0 39.6 43.1 39.6 25 A2FFC 1RAC115 0.18
25 M25 x 1.5 15.0 11.1 20.0 25.1 31.0 36.0 39.6 43.1 39.6 25 A2FFC 1RAC120 0.17
25 M25 X 1.5 15.0 11.1 20.0 26.5 35.0 36.0 39.6 43.1 39.6 25 A2FFC 1RAC180 0.18
32 M32 x 1.5 15.0 17.0 26.0 28.1 35.8 41.0 45.1 43.1 45.1 32 A2FFC 1RAC250 0.21
32 M32 x 1.5 15.0 17.0 26.3 30.4 38.0 41.0 45.1 43.1 45.1 32 A2FFC 1RAC280 0.21
32 M32 x 1.5 15.0 17.0 26.3 34.6 45.0 41.0 45.1 43.6 48.0 32 A2FFC 1RAC290 0.25
40 M40 x 1.5 15.0 23.5 32.2 36.4 45.0 50.0 55.0 45.1 55.0 40 A2FFC 1RAC300 0.28
40 M40 x 1.5 15.0 23.5 32.2 40.0 49.0 50.0 55.0 45.1 55.0 40 A2FFC 1RAC380 0.30
50S M50 x 1.5 15.0 31.0 38.2 46.5 58.7 55.0 60.5 43.8 63.7 50S A2FFC 1RAC450 0.48
50S M50 x 1.5 15.0 31.0 38.2 51.2 61.0 55.0 60.5 43.8 65.0 50S A2FFC 1RAC500 0.49
50 M50 x 1.5 15.0 35.6 44.0 51.2 61.0 60.0 66.0 48.0 66.0 50 A2FFC 1RAC550 0.49
Dimensions are displayed in millimetres unless otherwise stated
FI412
Certication Revision Date
IFS 14 05/19
ATEX / IECEx 11 04/19
CSA 10 04/19
CMP Products Limited on its sole responsibility declares that the equipment referred to herein conforms to the requirements of the ATEX Directive 2014/34/EU and the following standards:
EN 60079-0:2018, EN 60079-1:2014, EN 60079-7:2015, EN 60079-15:2010, EN 60079-31:2014, BS 6121:1989, EN 62444:2013
David Willcock - Certification Engineer (Authorised Person)
CMP Products Limited, Cramlington, UK, NE23 1WH
15th April 2019
ATEX CERTIFICATION No : CML 18ATEX1308X, CML 18ATEX4312X
ATEX CERTIFICATION CODE : ^II 2G Ex db IIC Gb, II 2G Ex eb IIC Gb, II 1D Ex ta IIIC Da IP66, IP67, IP68
^II 3G Ex nR IIC IP66, IP67, IP68
IECEx CERTIFICATION No : IECEx CML 18.0173X
IECEx CERTIFICATION CODE : Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da, Ex nR IIC Gc IP66, IP67, IP68
CSA CERTIFICATION No : 1211841
CSA CERTIFICATION CODE : Ex d IIC, Ex e II, Ex nR II, Enclosure Type 4X
1. Read all instructions before beginning installation. Installation shall only be performed by competent, suitably trained personnel (in accordance with EN/IEC 60079-14) using the
correct tools; spanners should be used for tightening.
2. Inspection and maintenance shall only be performed by competent, suitably trained personnel (in accordance with EN/IEC 60079-14 (Initial Inspection) and EN/IEC 60079-17).
3. The interface between a cable entry device and its associated enclosure / cable entry will require additional sealing to achieve ingress protection (IP) ratings higher than IP54.
The minimum protection level is IP54 for explosive gas atmospheres and IP6X for explosive dust atmospheres. Parallel threads (and tapered threads when using a non-threaded
entry) require a CMP sealing washer or integral O-ring face seal (where available) to maintain IP66, 67 and 68 (when applicable). It is the installers responsibility to ensure the
IP rating is maintained at the interface.
Note: When fitted to a threaded entry, all tapered threads will automatically provide an ingress protection rating of IP66.
4. The standard product temperature range is -60°C to +130°C. The equipment should not be used outside of this range.
5. Cable glands do not have any serviceable parts and are therefore not intended to be repaired.
6. Cable glands are manufactured from Brass, Nickel Plated Brass, Stainless Steel, Mild Steel or Aluminium, with Silicone seals.The end user shall consider the performance of these
materials with regard to attack by aggressive substances that may be present in the hazardous area. Consideration should be given to potential degradation due to galvanic
corrosion at the interface of dis-similar metallic materials.
7. It is the end user’s responsibility to ensure the equipment materials are suitable for their final installation location. If in doubt consult CMP Products Limited.
8. Once installed do not dismantle except for inspection. An inspection should be conducted as per IEC / EN 60079-17 by a qualified person. After inspection the gland should be
re-assembled as instructed, ensuring the outer seal nut is correctly tightened to ensure the cable is secured.
9. Metric entry threads comply with ISO 965-1 and ISO 965-3 with a 6g tolerance as required by IEC 60079-1:2014. The CMP standard metric thread pitch is 1.5mm for threads
up to M75, and 2.0mm from M90 and above. Special thread pitches between 0.7 – 2.0mm are available on all products on request. See certificate for details of other thread
types. NPT threads are in accordance with ASME B1.20.1-2013 gauging to Cl 3.2 for external threads. For details of other thread types refer to IECEx certificate.
10. The enclosure surface finish must be smooth and flat to facilitate sealing with an O-ring or Entry Thread Sealing Washer for the required IP rating.
11. Enclosure will need to be sufficiently strong to support the cable and cable gland assembly. Enclosure entries must be perpendicular. Any draft angles from the casting/moulding
process should have a perpendicular flat spot machined to facilitate sealing with an O-ring or Entry Thread Sealing Washer.
12. CMP Products recommends when using the cable gland with a through-hole, the hole must be circular, free of burrs and the diameter no larger than 0.7mm above the thread
major diameter. A suitable CMP Products locknut shall be used to secure the product. See CMP Products catalogue for locknut options.
13. A CMP earth tag should be used when it is necessary to provide an earth bond connection. CMP earth tags have been independently tested to comply with Category B rating
specified in IEC 62444 (no ratings stated in IEC 60079-0). Ratings are shown in the associated table. CMP earth tags slip over the cable gland or accessory entry thread from
inside/outside the enclosure and must be secured with a locknut (if fitted internally).
SPECIFIC CONDITIONS OF USE
1. All cable gland types and sizes are only suitable for fixed installations. Cables must be effectively clamped to prevent pulling or twisting.
2. The entry item component may be supplied with an alternative nearest equivalent recognised thread type and size to the metric thread, whilst maintaining a tolerance of fit,
equal to or better than, a medium fit to ISO 965-1 & ISO 965-3. Intended for use within existing installations only, that incorporate female thread types that are no longer
permitted by the current edition of EN/IEC 60079-1, but comply with the requirements of EN 50018:2000 & IEC 60079-1:2001.
3. Ingress discs shall be removed (not remain fitted within cable glands) intended for installation within flameproof (Ex d) enclosures.
IMPORTANT NOTES FOR INSTALLERS
EXPLOSIVE ATMOSPHERES CLASSIFICATION
CMP Earth Tag Size Short Circuit Ratings Symmetrical Fault Current
(kA) for 1 second
20 3.06
25 4.06
32 5.40
40 7.20
50 10.40
63 10.40
75 10.40
2776
INCORPORATING EU DECLARATION OF CONFORMITY TO DIRECTIVE [2014/34/EU]
www.cmp-products.comwww.cmp-products.com
INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND TYPES A2FFC
CABLE GLAND COMPONENTS - It is not necessary to dismantlethe cable gland any further than illustrated below
1. Entry Item
2. Seal
3. Seal Nut
4. Conduit Anchor
PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION
1. Slacken the seal nut (3) to relax the seal.
3. Fit the gland into the equipment and fully tighten the entry item (1).
4. Bring the conduit into engagement with the conduit anchor (4) and then screw the anchor into the conduit until it is fully
engaged.
5. Tighten the seal nut (3) by hand until resistance is felt (when the seal engages the cable) and then tighten further one full turn with a
spanner.
1. 2. 3. 4.
2. Pass enough cable through the seal (2) to suit the installation.
There is no need to disassemble the gland in order to fit it to the conduit.

This manual suits for next models

31

Other CMP Cables And Connectors manuals

CMP TMC2 User manual

CMP

CMP TMC2 User manual

CMP E1FW Service manual

CMP

CMP E1FW Service manual

CMP Huron User manual

CMP

CMP Huron User manual

CMP 25280-3-000 Series Guide

CMP

CMP 25280-3-000 Series Guide

CMP C2K User manual

CMP

CMP C2K User manual

CMP PXSS2K-REX User manual

CMP

CMP PXSS2K-REX User manual

CMP PXRC-REX User manual

CMP

CMP PXRC-REX User manual

CMP CW User manual

CMP

CMP CW User manual

CMP A2F User manual

CMP

CMP A2F User manual

CMP T3CDS User manual

CMP

CMP T3CDS User manual

CMP PXSS2K Service manual

CMP

CMP PXSS2K Service manual

Popular Cables And Connectors manuals by other brands

REUTLINGER 80 SVII instruction sheet

REUTLINGER

REUTLINGER 80 SVII instruction sheet

ODU MAC LC Product information

ODU

ODU MAC LC Product information

enphase CT-200-SOLID Quick install guide

enphase

enphase CT-200-SOLID Quick install guide

Euvision Split 16 4x4 Service notes

Euvision

Euvision Split 16 4x4 Service notes

Sealey POWER PRODUCTS PROJUMP PROJ12 instructions

Sealey

Sealey POWER PRODUCTS PROJUMP PROJ12 instructions

Camille Bauer PRKAB 560 operating instructions

Camille Bauer

Camille Bauer PRKAB 560 operating instructions

Gefen DisplayPort EXT-DPSB-100 user manual

Gefen

Gefen DisplayPort EXT-DPSB-100 user manual

Elation COMPU WARE 2004 user manual

Elation

Elation COMPU WARE 2004 user manual

Olimpia splendid KIT B0620 Instructions for assembly

Olimpia splendid

Olimpia splendid KIT B0620 Instructions for assembly

Fenix PSV 10 installation manual

Fenix

Fenix PSV 10 installation manual

MAT Roto-Twist RT-150 Installation, operation & maintenance instructions

MAT

MAT Roto-Twist RT-150 Installation, operation & maintenance instructions

Atlas Copco RTX-30 Quick setup guide

Atlas Copco

Atlas Copco RTX-30 Quick setup guide

Tripp Lite 352-01M Specification sheet

Tripp Lite

Tripp Lite 352-01M Specification sheet

ZiLOG ZUSBOPTSC01ZACG user manual

ZiLOG

ZiLOG ZUSBOPTSC01ZACG user manual

Kramer LPE Installation, start-up and maintenance instructions

Kramer

Kramer LPE Installation, start-up and maintenance instructions

Onset Computer Corporation CABLE-HWS-G Installation

Onset Computer Corporation

Onset Computer Corporation CABLE-HWS-G Installation

Burndy Continental Industries ThermOweld BRE-3 instructions

Burndy

Burndy Continental Industries ThermOweld BRE-3 instructions

Allen-Bradley ControlLogix 1756-CP3 installation instructions

Allen-Bradley

Allen-Bradley ControlLogix 1756-CP3 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.