Thank you for choosing Coolmay FX3GC series PLC. This manual mainly explains the features, general
specifications and wiring methods of FX3GC series. More detail programming information please refer to
"Coolmay CX3G&FX3GC PLC Programming Manual".
The FX3GC series is a compact PLC with the following features:
1. Highly integrated. Digital at most 16DI/16DO (digital type can be customized transistor, relay or mixed).
Analog at most 8AI 6AO, input can be customized temperature, current, voltage or mixed (support-5~5V/
-10V~10V), output can be customized current and voltage.
2. Comes with two PLC programming ports: MiniB USB port (faster download speed) and RS232 port.
3. Support multi-channel high-speed counting and high-speed pulse functions. High-speed counting
normally single-phase 6 60KHz, or AB (Z) phase 2 60KHz + AB phase 1 10KHz. High-speed pulse is normally
8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz. Acceleration and deceleration are independent; the total of
high-speed counting + high-speed pulse cannot exceed 480KHz.
4. Support special encryption. Setting the password to 12345678 can completely prohibit reading programs.
[Note: Only 8-bit password encryption is supported]
5. Convenient wiring, using 3.5mm pitch pluggable terminals.
Production Information
Naming rules
FX3GC
1 2 34567
-
8 9 1110
Com ports
(optional) High-speed counting
High-speed
pulse
Size
Single
phase
ABZ
phase Output Dimensions
(mm)
Normally
8 channels,
Y0-Y3 is 100KHz,
Y4-Y7 is 10KHz;
HSC + HSP
can not
exceed
480KHz.
90*65*32
Model
Digital
points
Analog
(optional)
DI DO MAX
AI
MAX
AO
CAN
(2.0A/B)
MT: Y0-Y7 is MOS tube output, Y10-Y17 is transistor output; MR: relay output; MRT: mixed output.
Optional according to customer requirements.
FX3GC PLC User Manual
Installation size
Mechanical Design Reference
Filter function
High-speed counting
Input level
With filter function, the filter time can be set among 0-60ms,
defaulted as 10ms
Normally single phase 6 channels 60KHz or AB (Z) phase
2 channels 60KHz + AB phase 1 channel 10KHz
Passive NPN, common terminal isolation, S/S connected to 24V+
Digital relay output index
Max current
Load voltage
Circuit insulation
On response time
Mechanical life (no load)
Electrical life (rated load)
Output level
2A/point, 5A/8point COM
Below DC30V/ Below AC220V
Relay mechanical insulation
About 10ms
10 million times
300,000 times
Normally open dry contact output, COM can be connected to positive or negative
Digital transistor output index
Max current
Load voltage
Circuit insulation
Isolation voltage
(power supply-external terminal)
On response time
High-speed frequency output
Output level
MOS tube: 2A/point, 4A/4point COM, 5A/12point COM;
MT: 0.5A/point, 0.8A/4point COM, 1.6A/12point COM
DC24V
Optocoupler insulation
1500VAC
High-speed output: 10μs, other 0.5ms
Normally 8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz
Low level NPN, COM connected to negative
Analog input index
Input signal
Response time
Analog input quantity
Accurary
1 scan cycle
0-8 Channel
12 bits
Analog output index
Output signal
Analog output quantity
Accurary
0-6 Channel
12 bits
External interface
Programming port
Environment
Operating temperature
Relative humidity
Storage temperature
Vibration frequency
0°C~50°C
5%~95%RH
-20°C~70°C
10-57Hz, amplitude 0.035mm; 57Hz-150Hz, acceleration speed 4.9m/s²
(10 times each on X, Y, Z, total 80 minutes each)
Comes with 2 programming ports: Mini B USB port
(faster download speed) and Rs232
2 Product structureDiagram
1. 35mm rail installation 2. Terminal block for power input signal
4. Digital input display LED 5. Digital output display LED
8. PLC programming port
9. RUN/STOP PLC operation switch 10. Analog input (optional 485)
11. Analog output (optional CAN) 12. Digital input terminal block
7. Optional RS485
Diagram 1 Installation dimension drawing
Dimensions 90*65*32(mm)
Product structure
90
65
32
6
9
1
8
12
3
2
7
10
11
4
4
55
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
RUN
ERR
PWR
Y
Diagram 3 FX3GC-16MR/MT/MRT
◆
◆
◆
Electrical Design Reference
◆
Hardware interface
◆
Basic parameters
FX C3G -16M 8 8
FX C3G -30M
FX C3G -32M
16 14
16 16
None
Diagram 6 FX3GC-32MR/
MT/MRT
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
RUN
ERR
PWR
Y
10
11
12
13
14
15
16
17
10
11
12
13
14
15
16
17
Y
Diagram 5 FX3GC-30MR/
MT/MRT
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
RUN
ERR
PWR
Y
10
11
12
13
14
15
16
17
10
11
12
13
14
15
A
B
Y
Y
is the public terminal of switch output;
485/CAN
-
1P
-
1C1
-
A0
-
V
-
4DA
8AD
-
RTM
16
3. Digital output terminal block
Terminal wiring specifications: 22-14AWG wire. The terminals of this series of models are all pluggable terminals.
For special model interfaces, please refer to the product silk screen.
other customization
0-5V/0-10V/-10~10V/-5~5V/0-20mA/4-20mA/other customization
Electrical parameters
Input voltage DC 24V
Digital input index
Isolation mode
Input ON
Input resistance
Input OFF
Photoelectric coupling
High-speed input 3.3KΩCommon input 4.3Ω
Electric current of high-speed input
is higher than 5.8mA/24V
Electric current of common input
is Higherthan 9.9mA/24V
Table 2 Electrical parameters
(Continued from the table above)
Pin No. Signal Description
5
8GND
TXD
Ground
Send
4RXD Receive ⑧
① ②
③ ④ ⑤
⑥⑦
Diagram 8 Optional
communication port
Table 1: Basic parameters
84
64
1
21
1
861
1
None
None
NoneNone
Electric current of high-speed input
is higer than 4.5mA/19V
Electric current of common input
is Higher than 4mA/17V
High-speed counting + high-speed pulse total does not exceed 480KHz
PT100/PT1000/thermocouple/NTC/0-10V/0-5V/-10~10V/-5~5V/0-20mA/4-20mA
◆
◆
◆
◆
Note: For detailed settings, please refer to "Coolmay CX3G&FX3GC Series PLC Programming Manual"
Diagram 7 RS232
programming port
RS232 programming port pin definition
GND is the common terminal of analog input/analog output
Diagram 4 FX3GC-16M
communication port/analog expansion
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
RUN
ERR
PWR
Y
A0
A1
A2
A3
A4
A5
A6
A7
D0
D1
D2
D3
D4
D5
A
B
13
13. Mini USB programming port (faster download speed)
S/SS/SS/SS/SS/S
S/S
Note: S/S is the common terminal of digital input, which is connected to the positive pole of 24V;
GND
GND
A1
B1
H
L
( )
※
485+ A1
485- B1
485+ A
485- B
H
L
~
AB phase
Normally
single
phase
6 channels
60KHz
Normally
AB phase
2 channel
60KHz+
1 channel
10KHz
Normally
ABZ phase
2 channel
60KHz
Installation size: DIN rail (35mm)
Refer to【Table 1: Basic parameters】
COM port
3
12
Comes with two programming ports:
Mini B-type USB port (faster download speed) and RS232 (8-pin mouse female socket)
16M can expand at most 2 RS485, 1 CAN port (2.0A/B), 6 inputs and 4 outputs analog
Or 1 RS485, 1 CAN port (2.0A/B), 8 inputs and 4 outputs simulation
Or 1 RS485, 8 inputs and 6 outputs analog
Or 2 RS485, 1 CAN port (2.0A/B)
1. Series: FX3GC: FX3GC series PLC
2. I/O points: 16: 8DI 8DO 30: 16DI 14DO 32: 16DI 16DO
3. Module M: Main Module
4. DO type: R: Relay; T: Transistor; RT: Relay and transistor mixed
5. AI 0-8 channels are optional
6. AO 0-6 channels are optional
7. AI type
V: 0 -10V V5: 0-5V V_: -10~10V V5_: -5~5V A0: 0-20mA A4: 4-20mA
8. AO type V: 0-10V V5: 0-5V A0: 0-20mA A4: 4-20mA V_: -10~10V V5_: -5~5V
[Note: Optional negative voltage occupies two DA channels]
9. C1 means single-phase high-speed counting, C2 means AB phase counting, and C3 means ABZ phase counting.
Normally single phase 6 channels 60KHZ, or AB (Z) phase 2 channels 60KHz + AB phase 1 channel 10KHz.
10. P0 means 10KHz high-speed pulse, P means 100KHz high-speed pulse. High-speed pulse normally
8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz; acceleration and deceleration are independent; high-speed
counting + high-speed pulse total cannot exceed 480KHz.
11. COM port. Refer to【Table 1: Basic parameters】
PT: PT100 PT1000: PT1000 NTC: Thermistor (10K/50K/100K)
E: E type thermocouple (K type/T type/S type/J type can be customized, supporting negative temperature)
RS485
Communication port description
Serial port 1: RS422 (PLC programming port): Supports Mitsubishi programming port protocol,
which can be used to download PLC programs or communicate with devices that support
Mitsubishi programming port protocol.
Serial port 2: RS485 (AB port): Support Mitsubishi programming port protocol, Mitsubishi BD protocol,
RS protocol and Modbus RTU protocol.
※ Support RS, RS2, WR3A, RD3A, ADPRW instructions.
Serial port 3: RS485 (A1B1 port): Supports Mitsubishi programming port protocol, RS2 protocol and
Modbus RTU protocol.
※Support RS2, WR3A, RD3A, ADPRW instructions.
CAN port: supports RS2 protocol and Modbus RTU protocol.
※Support RS2, WR3A, RD3A, ADPRW instructions.
6. PWR: Indicates the power-on state
RUN: The light is on when the PLC is running
ERR: The indicator light flashes when the program
error occurs (the indicator light is on when the
CPU error occurs)
( )
None
Diagram 10 shows the equivalent circuit diagram of the relay output module. The output terminals are in several groups,
and each group is electrically isolated. The output contacts of different groups are connected to different power circuits.
Programming Reference
Diagram 9 Input wiring diagram
Diagram 10 Relay output equivalent circuit
Diagram 11 Transistor output equivalent circuit
FX3GC-16M
Digital input
Digital output
For details, please refer to "Coolmay CX3G&FX3GC Series PLC Programming Manual"
Diagram 12 Inductive load absorption circuit schematic
Devices Distribution and Statement of Power-down Save
◆
◆
Diagram 13 Pulse output wiring diagram
Shenzhen Coolmay Technology Co., Ltd.
Tel: 0755-86950416
86960332
26051858
26400661
Fax: 0755-26400661-808
Email: M3@coolmay. com
Website: en.coolmay.com
◆
Serial NO. Register address
D8050
D8051
D8052
D8053
D8054
D8055
Set value range
0-4000
0-4000
0-4000
0-4000
0-4000
0-4000
Output type
When D8058.0~D8058.5=0,
the type is 0~20mA;
When D8058.0~D8058.5=1,
the type is 4~20mA.
Note: All the internal circuit shown only as a reference
※
Equivalent Circuit
Version 2021/06
1K
3.9K
S/S
X0 0V
X1
1K
3.9K
Y007
Y000
Load
Load
Y017
Y010
DC24V
Fuse
Load
Load
AC0~220V
Fuse
~
Load
Load
Load
Load
Sink output type
DC24V
Fuse
DC24V
Fuse
Y007
Y000
Y017
Y010
Y1
Y10
Y4
R=200Ω C=0.22uF,250VAC
R
C
~
Y5
~
PLC relay output
Induc tiv e load
DC24V power supply
Freewheeling diode 1N404
PLC transistor output
Induc tive load
Freewheeling diode 1N404
DC24V power supply
PLC relay output
Induc tiv e load
AC220V power supply
Induc tive load
PLC relay output
AC220V power supply
Varistor 10D471k (dark surge)
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
R
Y4
Y5
Y6
Y7 Direction(Dir)
Pulse(Pul)
Direction(Dir)
Pulse(Pul)
Y0
Y1
Y2
Y3
PLC internal
equivalent circuit
Direction(Dir)
Pulse(Pul)
Direction(Dir)
Pulse(Pul)
DC24V (5V drive must be connected in series with 2kΩ resistor)
GND
A0
A1
+
104p
GND
D0
D1
Analog input
(Analog input common terminal)
(Analog input 1)
104p +(Analog input 2)
If the analog input is unstable,
please add 104p ceramic capacitor or
external magnetic ring filter as appropriate
to increase the anti-interference ability.
104p
+(Analog input 8)
-
(Analog output common terminal)
+(Analog output 5)
+(Analog output 2)
+(Analog output 1)
Analog input is A0~A7
Analog output is D0~D5
The negative terminal is respectively connected
to the GND of the analog input/output terminal
24V
Any updates will be updated on our website en.coolmay.com
Auxiliary relay M
State S
[S0-S9] 10point Initial state/ [S10~S999] 990point keep/ [S1000~S4095] 3096point general
Timer T
[T0~T199] 200point 100ms general / [T250~T255] 6point 100ms keep
[M0~M383] 384point general / [M384~M1535] 1152point keep / [M1536~M7679] 6144point general
Data register D
[V0~V7] [Z0~Z7] 16point indexing
[D0~D127] 128point general/ [D128~D7999] 7872point keep/ [D8000~D8511] 512points special
Nested pointer
[N0~N7] 8 points master control
[P0~P255] 256 point / [P0~P1280] 1281 point (26232 and above version)
K
H
16-bit -32,768~32,767
32-bit -2,147,483,648~2,147,483,647
32-bit 0~FFFFFFFFH16 bits 0~FFFFH
Extended file register R
[R0~R22999] 23000point support for retentive/ [R23000~R23999] 1000point internal use
Pointer JUMP, CALL branch
Interruption
[I0□□~I5□□] 6 points input interruption / [I6□□~I8□□] 3 points timer interruption / [I010~I060] 6 points counter interruption
[T246~T249] 4 point 1ms grand total keep/ [T256~T319] 64 point 1ms general
[T200~T245] 46 points 10ms for general ※The 10ms timer is affected by the scan cycle. If the scan period is 12ms, the timer becomes 12ms and executes once.
[M8000~M8511] 512point special
Data register V, Z
PLC digital input wiring:
Port short connection: The S/S of the PLC input terminal is connected
to 24V, and the X terminal is connected to the power supply 0V, that is,
the input has a signal;
Two-wire system (magnetic control switch): PLC switch input is connected
to a two-wire magnetic control switch, the positive pole of the magnetic
control switch is connected to the X terminal, and the negative pole is
connected to 0V;
Three-wire system (photoelectric sensor or encoder): PLC switch is
connected to a three-wire photoelectric sensor or encoder, the power
supply of the sensor or encoder is connected to the positive power
supply, and the signal line is connected to the X terminal; the encoder
and photoelectric sensor are required to be of NPN type
(PNP needs special customization).
PLC digital output wiring:
Transistor: The output is NPN, COM is connected to the negative pole, and
Y is connected to the positive pole of the power supply after the load;
Relay: dry contact output, COM can be connected to positive or negative.
※
D8073 is the smoothing filter coefficient of all analog inputs, the setting range is 0~999.
The number of filter cycles=(R23600~R23607)*PLC scan time, the default is 100, the data cannot
be less than or equal to 0. If R23600=1, a PLC scan cycle is sampled once and the value in the
first analog input is changed once. The larger the value of R23600~R23607 is set, the more
stable the result value is.
Sampling of analog inputs
Note: The 5V driver must have a 2KΩ resistor in the DC24V string.
Programming software Compatible with "PLC programming software GX Developer8.86Q and GX Works2"
◆
FROM instruction can read directly: FROM K0 K0 D400 K8, read out 8 analog inputs.
Register read directly: D[8030]~D[8037] is the input value of analog [AD0~AD7];
The constant scan time is changed to D8059, which is started by M8039 (this function is
available in version 26232 and above). When the analog input has a thermocouple type, only
7 channels can be used, and AD4 (D8034) is the ambient temperature of the thermocouple.
8 channels can be used when there is no thermocouple type.
Note: For more details, please refer to Coolmay official website "PLC anti-interference processing method”
※
TO command output directly: T0 K0 K0 D500 K6, output 6 analog quantities.
※
The temperature type is one bit after the decimal point, ie 182=18.2 degrees.
※
目 录
—— Before using this product, please read the relevant manuals carefully.
Use the product under the environmental conditions specified in the manual.
FX3GC PLC User Manual
Diagram 14 PLC analog wiring
“FX3GC PLC User Manual" and "Coolmay PLC instruction programming manual"
Y
Y
Y
Y
Y
D5
A7
Y
Y
Y
Y
FX3GC-30M FX3GC-32M
Counter C
High-speed counter
[C0~C15] 16point general
[C200~C219] 20point general
16-bit up counter 32-bit up and down counter
[C16~C199] 184point keep
[C220~C234] 15point keep
The PLC input (X) is an externally powered DC24V sink type (passive NPN) with the input signal
isolated from the power supply. When using, connect S/S to 24V positive external power supply.
The equivalent circuit of the transistor output type PLC output part is shown in Diagram11. From the Diagram, the output
terminals are in several groups, and each group is electrically isolated. The output contacts of different groups can be
connected to different power circuits; the transistor output can only be used for DC 24V load circuits. The output wiring
mode is NPN, COM common cathode.
For the inductive load connected to the AC loop, the external circuit should consider the RC instantaneous voltage
absorption circuit; for the inductive load of the DC loop, consider adding a freewheeling diode, as shown in Diagram 12.
The wiring of stepper or servo motor is shown in Diagram 13. The default Y0-Y7 of 3G series PLC are
pulse points, and the direction can be customized.
PLC analog wiring
PLC anti-interference processing
1. Strong and weak power should be separately routed, not common; when there is strong electrical interference, add a
magnetic ring at the power supply end; and perform proper and effective grounding according to the type of casing.
2. When the analog quantity is disturbed, 104 ceramic capacitors can be added for filtering and correct and effective grounding.
Constant
[C235~C245 single phase counting]
[C246~C250 Single phase dual counting]
[C251~C255 dual phase counting]
Analog input register (AD means analog input, precision 12 bit); supports FROM instruction
or direct register reading
Note: For analog input range and register corresponding value, please refer to
"Coolmay CX3G&FX3GC Series PLC Programming Manual"
Analog output register (DA means analog output, precision 12 bits); support TO instruction or direct register
assignment operation
Register direct assignment operation: D[8050]~D[8055] correspond to the analog output value of [DA0~DA5],
which occupies 2DA when negative voltage output is selected, and the set value range is as follows:
FX3GC PLC's soft components are permanently maintained after power-off, that is, all soft components in the holding
area will not be lost after the module is powered off.
The real-time clock uses a rechargeable battery to ensure that the clock is the current time. All power-down retention
functions must ensure that the voltage of the DC24V power supply is
above 23V after loading, and the PLC power-on time is longer than 2 minutes, otherwise the power-down function
will be abnormal.
QQ: 1687435500
Two-wire system: the positive pole of the power supply is connected to the positive pole of the transmitter, the
negative pole of the transmitter is connected to the AD terminal, and the negative pole of the
power supply is connected to the GND terminal; generally the wiring mode of the 0~20mA/
4~20mA transmitter;
Three-wire system: the positive pole of the power supply is connected to the positive pole of the transmitter,
the negative pole of the power supply and the negative pole of the signal output are the
same terminal, and the signal output of the transmitter is connected to the AD terminal;
The temperature analog is connected to the AD terminal and the GND terminal respectively. If it is a
three-wire PT100, it needs to be connected in two lines. The GND common terminal of analog input and
output can be shared.
Four-wire system: the positive pole and negative pole of the power supply are respectively connected to the
positive and negative poles of the power supply of the transmitter, and the positive and
negative poles of the signal output of the transmitter are respectively connected to the
AD terminal and the GND terminal;
X
Y
X00-X07 X00-X17 X00-X17
Y00-Y07 Y0-Y15 Y00-Y17
1. Please confirm the power supply voltage range of this product (Regular product
power supply is only 24V DC! The recommended output power of the power supply is
18W and above) and correct wiring before turning on the power to avoid damage.
2. When installing this product, please tighten the screws or clamp the guide rails
to avoid falling off.
3. Avoid wiring and plugging or unplugging the cable plug in a live state, otherwise
it is easy to cause electric shock or circuit damage. When the product emits peculiar
smell or abnormal sound, please turn off the power switch immediately. During screw
hole processing and wiring, do not drop metal chips and wire ends into the ventilation
holes of the controller, which may cause product failure and misoperation.
4. Please do not tie the power cord and the communication cable together or get too
close, keep a distance of more than 10cm. Strong current and weak current should be
separated and properly and effectively grounded. In severe interference situations,
shielded cables should be used for communication and high-frequency signal input and
output cables to improve anti-interference performance. The grounding terminal FG on
this machine must be grounded correctly to improve the anti-interference ability.
5. The digital input is external power supply DC24V drain type (passive NPN), and the
input signal is isolated from the power supply. When in use, connect S/S to the 24V
positive of the external power supply.
7. Please do not disassemble the product or modify the wiring at will. Otherwise it
may cause failure, malfunction, loss, or fire.
8. When installing and disassembling the product, please turn off all power supplies,
otherwise it will cause the equipment to malfunction or fault.
6. The COM of the digital output (transistor) is a common cathode.
Production Information…...………………………01
Mechanical Design Reference…………………02
Electrical Design Reference . ..… ……………… 03
Equivalent Circuit…..….……………. 04………………
Programming Reference………………………. 05 …
TIPS………………………………… ……06 ………………
Catalog
TIPS
8 point
8 point
14 point
16 point
14 point
16 point
Analog output

This manual suits for next models

3

Other Coolmay Controllers manuals

Coolmay EX3G-70KH User manual

Coolmay

Coolmay EX3G-70KH User manual

Coolmay CX3G Series Owner's manual

Coolmay

Coolmay CX3G Series Owner's manual

Coolmay C600S User manual

Coolmay

Coolmay C600S User manual

Coolmay CX3G-32M Owner's manual

Coolmay

Coolmay CX3G-32M Owner's manual

Coolmay EX3G-43HB-24M Owner's manual

Coolmay

Coolmay EX3G-43HB-24M Owner's manual

Popular Controllers manuals by other brands

INVERTEC optidrive E IP20 user guide

INVERTEC

INVERTEC optidrive E IP20 user guide

AlfaRadio AlfaSpid RAK instruction manual

AlfaRadio

AlfaRadio AlfaSpid RAK instruction manual

Emec Centurio PRO operating manual

Emec

Emec Centurio PRO operating manual

AMX NetLinx Integrated NXI Operation/reference guide

AMX

AMX NetLinx Integrated NXI Operation/reference guide

Jung 240-10 operating instructions

Jung

Jung 240-10 operating instructions

Trane Tracer UC

Trane

Trane Tracer UC

HP MSA 2040 installation instructions

HP

HP MSA 2040 installation instructions

DSE 8860 installation instructions

DSE

DSE 8860 installation instructions

ADVATEK LIGHTING PixLite T8-S Mk3 quick start guide

ADVATEK LIGHTING

ADVATEK LIGHTING PixLite T8-S Mk3 quick start guide

Electro-Voice DeltaMax DMC-1152X Specification sheet

Electro-Voice

Electro-Voice DeltaMax DMC-1152X Specification sheet

HydroCheck HC8000T Installation

HydroCheck

HydroCheck HC8000T Installation

Siemens SSC61.5U installation instructions

Siemens

Siemens SSC61.5U installation instructions

Oasis Landscaper 12 Installation and operation manual

Oasis

Oasis Landscaper 12 Installation and operation manual

Luxel Radak Power Controller II Series manual

Luxel

Luxel Radak Power Controller II Series manual

Vacon 100 INDUSTRIAL Installation and user manual

Vacon

Vacon 100 INDUSTRIAL Installation and user manual

Thorlux SmartTouch installation instructions

Thorlux

Thorlux SmartTouch installation instructions

Vents SRS-1 quick start guide

Vents

Vents SRS-1 quick start guide

Daikin RoCon HP operating instructions

Daikin

Daikin RoCon HP operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.