CopperOptics PairGain PG-Flex FSU-796 List 3 User manual

PG-FLEX CENTRAL OFFICE
LINE UNIT STREAKER CARD
QUICK REFERENCE GUIDE
The PairGain®PG-Flex™ FSU-796 List 3 Central Office Line Unit (COLU) Streaker card is a continuity tester.
The card verifies that the Tip and Ring connections from the line unit slots of a PG-Flex Central Office Terminal
(COT) shelf (19" or 23") are wired correctly to the Central Office (CO) Main Distribution Frame (MDF).
When you receive the PG-Flex FSU-796 List 3 Streaker Card:
1Unpack the PG-Flex FSU-796 Streaker Card and visually inspect it for signs of damage. If the components
have been damaged in transit, immediately report the extent of damage to the transportation company and
to your sales representative. Order a replacement unit if necessary.
2Compare the contents of the package against the packing list. If the shipment is incorrect, contact PairGain
as described in the "Limited Warranty" section.
The illustration shows the FSU-796 List 3 front panel, and the table
below describes the features and functions for the front panel LEDs.
MODEL FSU-796 LIST 3, P/N150-1396-03
Feature Function
HDSL_1_T
HDSL_1_R
HDSL_2_T
HDSL_2_R
Lights when the HDSL 1 and 2 Tip or Ring
connector terminations from the MDF are shorted
to ground.
If the LED for the termination under test does not
light, or the wrong LED lights, the termination is
miswired.
If the opposite LED lights, the termination is
reversed.
AUX PWR_1_T
AUX PWR_1_R
AUX PWR_2_T
AUX PWR_2_R
Lights when the AUX PWR 1 and 2 Tip or Ring
connector terminations from the MDF are shorted
to ground.
If the LED for the termination under test does not
light, or the wrong LED lights, the termination is
miswired.
If the opposite LED lights, the termination is
reversed.
BYPASS_T
BYPASS_R Lights when the BYPASS Tip or Ring connector
termination from the MDF is shorted to ground.
If the LED for the termination under test does not
light, or the wrong LED lights, the termination is
miswired.
If the opposite LED lights, the termination is
reversed.
-48 CO Indicates that the CO battery is wired correctly.
TEST When pressed, lights allthe LEDs on the Streaker
card.
Unpack and Inspect the Shipment
Features of the FSU-796
Technical Assistance
PairGain Technical Assistance is available 24 hours per day, 7 days per week by contacting PairGain’s Customer
Service Engineering group.
During normal business hours (8:00 AM to 5:00 PM, Pacific Time, Monday through Friday, excluding holidays,
technical assistance calls are normally answered directly by a Customer Service Engineer. At other times, a
request for technical assistance is handled by an on-duty Customer Service Engineer through a callback process.
This process normally results in a return call within 30 minutes of initiating the request.
In addition, PairGain maintains a computer bulletin board system for obtaining current information on PairGain
products, product fault isolation tips and aids, helpful utilities, and for posting requests or questions. This system
is available 24 hours per day by calling (714) 730-3299. Transmission speeds up to 28.8 kbps are supported with
a character format of 8-N-1.
PairGain product, company, and application information can be found at http://www.pairgain.com using any Web
browser.
Limited Warranty
PairGain Technologies, Inc. warrants its products to be free of defective and faulty workmanship for a period of
60 months, under normal use, from the date of shipment. PairGain's obligation under this warranty is limited to
replacing or repairing, at PairGain's option, any such product that is returned during the warranty period per
PairGain's instructions and which product, in PairGain's sole option, is determined to be defective upon
examination at our plant.
Do not try to repair or disassemble the unit. If it fails, replace it with another unit and return the faulty unit to
PairGain for repair. Any modifications of the unit by anyone other than an authorized PairGain representative will
void the warranty.
If a unit needs repair, call PairGain at (800) 370-9670 for a Return Material Authorization (RMA) number and
return the defective unit, freight prepaid, along with a brief description of the problem, to the PairGain Repair
Center at 14352 Franklin Avenue, Tustin, CA 92780-7013.
PairGain will continue to repair or replace faulty modules beyond the warranty program at a nominal charge.
Contact your PairGain sales representative for details and pricing.
FCC Compliance
This unit complies with the limits for Class A digital devices pursuant to Part 15 of the FCC rules. These limits
are designed to provide reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, can cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which
case the user will be required to correct the interference at his own expense.
Refer to the installation section of the appropriate instruction manual for the unit you are installing to get
information on cabling, correct connections, and grounding.
Corporate Office: ForTechnicalAssistance:
14402 Franklin Avenue (800) 638-0031
Tustin, CA 92780
Tel: (714) 832-9922
FAX: (714) 832-9924
Copyright © 1997 PairGain Technologies Inc.
Section Number 363-796-103-01, Revision 01, February 23, 1998
1Slide the FSU-796 List 3 into the line unit slot to be tested. (Refer to the illustrations below for line unit
locations.)
2Verify that the -48 CO LED is lit. If the -48 CO LED is not lit:
• verify that the fuses are installed in the equipment bay’s fuse panel.
• verify that frame ground and CO battery are connected (refer to local practices).
• replace the FSU-796 (streaker card).
3Press the TEST switch and verify that all Tip and Ring LEDs are lit. Replace the FSU-796 if any of the
LEDs do not light.
.
The COT shelf power must be connected to provide -48V to the FSU-796 List 3.
Installing and Testing the FSU-796 List 3
19" Central Office Shelf
23" Central Office Shelf
1At the MDF, connect a jumper lead from frame ground to the appropriate Tip or Ring termination from the
COT shelf. Verify that the corresponding Tip or Ring LED on the FSU-796 is lit. (Refer to Table 1, “19"
Shelf System Connectors,”and Table 2, “23" Shelf System Connectors.”)
• If the correct Tip or Ring LED lights, proceed to the next connector termination.
• If the Tip or Ring LED under test does not light, check the wiring to the COT shelf.
• If the wrong LED lights, check the wiring to the COT shelf.
2Repeat the previous step for each line unit Tip and Ring termination.
*Wherenis 1, 2, 3, or 4 for Systems 1, 2, 3, or 4 respectively.
Table 1. 19" Shelf System Connectors
Connector System 1 System 2
HDSL P5 P7
BYPASS P10 P20
POWER_OUT P8 P9
Table 2. 23" Shelf System Connectors
Connector System 1 System 2 System 3 System 4
HDSL P5P6P7P8
BYPASS P13 P14 P15 P16
POWER_OUT P9 P10 P11 P12
Table 3. Line Unit Connector Definitions
System*Connector Function
System nHDSL_n_T1
HDSL_n_R1 Tip and Ring terminations for HDSL Pair #1 of System nto Remote
Terminal n.
-130 Vdc is simplexed on this line for powering the Remote Terminal.
System nHDSL_n_T2
HDSL_n_R2 Tip and Ring terminations for HDSL Pair #2 of System nto Remote
Terminal n.
+130 Vdc is simplexed on this line for powering the Remote Terminal.
System nPWR_1_T1
PWR_1_R1 System nauxiliary Power Pair #1. Used for auxiliary power to the RT
when using a PG-Flex doubler unit.
System nPWR_2_T2
PWR_2_R2 System nauxiliary Power Pair #2. Used for auxiliary power to the RT
when using a PG-Flex doubler unit.
System nBYPASS_n_T
BYPASS_n_R Termination for the metallic bypass pair into COT System n from RT n.
Testing the Line Unit Slots
Shelf Backplane Connector
(rear view)

This manual suits for next models

1

Other CopperOptics Network Hardware manuals

CopperOptics PairGain PG-Flex FLC-706 User manual

CopperOptics

CopperOptics PairGain PG-Flex FLC-706 User manual

CopperOptics PairGain PG-Flex FRL-742 User manual

CopperOptics

CopperOptics PairGain PG-Flex FRL-742 User manual

CopperOptics PairGain PG-Flex RT FRL-772 List 1 User manual

CopperOptics

CopperOptics PairGain PG-Flex RT FRL-772 List 1 User manual

CopperOptics PairGain PG-Flex FLC-703 User manual

CopperOptics

CopperOptics PairGain PG-Flex FLC-703 User manual

CopperOptics PairGain HiGain HRU-512 User manual

CopperOptics

CopperOptics PairGain HiGain HRU-512 User manual

CopperOptics PairGain HiGain HRU-412 User manual

CopperOptics

CopperOptics PairGain HiGain HRU-412 User manual

CopperOptics PairGain HiGain HDU-45 User manual

CopperOptics

CopperOptics PairGain HiGain HDU-45 User manual

CopperOptics PairGain PG-FLEX FRC-754 User manual

CopperOptics

CopperOptics PairGain PG-FLEX FRC-754 User manual

CopperOptics PairGain PG-Flex FCS-718 User manual

CopperOptics

CopperOptics PairGain PG-Flex FCS-718 User manual

CopperOptics PairGain HiGain HLU-388 User manual

CopperOptics

CopperOptics PairGain HiGain HLU-388 User manual

CopperOptics PairGain PG-Flex FCS-719 User manual

CopperOptics

CopperOptics PairGain PG-Flex FCS-719 User manual

CopperOptics PairGain PG-Flex FCS-718 User manual

CopperOptics

CopperOptics PairGain PG-Flex FCS-718 User manual

CopperOptics PairGain PG-Flex FLL-712 List 1 User manual

CopperOptics

CopperOptics PairGain PG-Flex FLL-712 List 1 User manual

CopperOptics PairGain HiGain ELU-319 List 5 User manual

CopperOptics

CopperOptics PairGain HiGain ELU-319 List 5 User manual

CopperOptics PairGain PG-Flex FRC-753 User manual

CopperOptics

CopperOptics PairGain PG-Flex FRC-753 User manual

Popular Network Hardware manuals by other brands

gefran SBI-DCP-33 instruction manual

gefran

gefran SBI-DCP-33 instruction manual

Linksys BEFN2PE Specifications

Linksys

Linksys BEFN2PE Specifications

Huawei BBU3900 installation guide

Huawei

Huawei BBU3900 installation guide

Axis C8110 installation guide

Axis

Axis C8110 installation guide

Minuteman RS232 user manual

Minuteman

Minuteman RS232 user manual

D-Link DIR-505 user manual

D-Link

D-Link DIR-505 user manual

Siemens SIMATIC NET operating instructions

Siemens

Siemens SIMATIC NET operating instructions

Data-Tronix DT-ATSC-IP-8 User guide & installation manual

Data-Tronix

Data-Tronix DT-ATSC-IP-8 User guide & installation manual

CTI 2500P-JACP Installation and operation guide

CTI

CTI 2500P-JACP Installation and operation guide

HP Compaq NC6133 Quickspecs

HP

HP Compaq NC6133 Quickspecs

Me Bell-555 TX Operating and assembly instruction

Me

Me Bell-555 TX Operating and assembly instruction

Genexis FiberTwist FTU-100 installation guide

Genexis

Genexis FiberTwist FTU-100 installation guide

Belkin F1DNUSB-BLK Quick installation guide

Belkin

Belkin F1DNUSB-BLK Quick installation guide

Moxa Technologies MRC-1002 Series Easy setup guide

Moxa Technologies

Moxa Technologies MRC-1002 Series Easy setup guide

Juniper WX 100 quick start

Juniper

Juniper WX 100 quick start

Paradyne Hotwire 8785 installation instructions

Paradyne

Paradyne Hotwire 8785 installation instructions

Edge-Core SAF4100I quick start guide

Edge-Core

Edge-Core SAF4100I quick start guide

Noontec Giga Link N5 manual

Noontec

Noontec Giga Link N5 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.