STANDARD RECOMMENDED PROCEDURE 003-876-QSG | ISSUE 4 | OCTOBER 2017 | PAGE 1 OF 2
Closet Connector Housings
(CCH) 1U/2U/3U Quick
Start Guide
Visit http://www.corning.com/opcomm/Resources/Standard Recommended Procedures for the in-depth
installation manual and other language versions. Search for part number 003-876.
1. CARTON CONTENTS
2. MOUNTING THE HOUSING
1Sliding cover
2
Sliding tray
3Mounting bracket
4Door latch
5Blank adapter panel
8Internal strain-relief assembly
9
Slack management clip
10 External strain-relief assembly
11 Jumper guide
7
6
Label card
Transitional strain-relief holder
TPA-3873
1
3
3
4
4
6
8
7
10
11
11
9
55
2
2b 2c
2a Install two #12-24 x 0.5
Phillips-head screws
at desired height.
Leave gap behind head.
Slide mounting bracket notch
over screw heads.
Install next two screws in
center notch of mounting
bracket; tighten all screws.
TPA-3874
2a 2b
2c
3. ACCESSING THE HOUSING
4. INSTALLING CABLE FOR FIELD TERMINATION
WARNING: Never look directly into the end of a ber that may be carrying laser light.
Laser light can be invisible and can damage your eyes. Viewing it directly does not cause pain.
The iris of the eye will not close involuntarily as when viewing a bright light. Consequently,
serious damage to the retina of the eye is possible. Should accidental eye exposure to laser
light be suspected, arrange for an eye examination immediately.
4.1. Accessing the Cable for Field Termination
3a Open front and rear doors.
Pull covers with moderate force
in opposite directions to remove.
3b Lift plunger on internal strain-relief assembly.
Push bracket to rear to disengage and remove
it from the housing.
3d Set tray and strain-relief assembly on work
surface for next operations.
TPA-3875
3c Slide tray toward rear of housing.
Press latches on both sides to release tray
and pull it completely out of housing.
Plunger
Press here.
22 inches (internal strain-relief)
24 inches (external strain-relief)
22 inches (internal strain-relief)
24 inches (external strain-relief)
Fan-out body legs available
in 25 - 48 inches lengths
Strip to 48 inches
Direct Termination
OSP, FREEDM®
CABLE
MIC®, UMIC Cable or Subunit
Strip Lengths for 1U, 2U, 3U Housings
Strain-relief
Point
TPA-3876
4.2. Sheath Retention
4.3. Strain-relieving to the Transitional Strain-Relief Holder
TPA-3883
4.3a
4.3a
4.3a
Replace blank panels with adapter
panels applicable for the
connectors being used.
4.3b Press buffer tube
fan-out bodies into
transitional holder.
OR Secure loose tube
cable to the transitional
holder with cable ties.
4.3c In 2U or 3U housings,
you may stack the
transitional holder to
accommodate more
fan-out bodies or cables.