Cumberland Evolution 3000 User manual

Part No. 4801-5307 Rev 2-15 Owners Manual Evolution 3000 and 3001
CUMBERLAND Assumption, IL 62510 • Phone 217-226-4421 • Fax 217-226-4420
Evolution 3000 and 3001
Environmental Controller
Cumberland
Date: 05-18-15 1004 E. Illinois St.
Assumption, IL 62510
Controller Software Version V0.37

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 Table of Contents
Table of Contents
Section Title Page
1. Warranty........................................................................................................................................................4
2. Warnings........................................................................................................................................................5
3. Ratings and Specifications.............................................................................................................................5
4. Introduction....................................................................................................................................................6
5. Evolution Front Panel ....................................................................................................................................6
5.1 Navigator Panel.......................................................................................................................................8
5.2 Editor Panel ............................................................................................................................................8
5.3 Main Display Contrast ............................................................................................................................9
5.4 Inlet Stages..............................................................................................................................................9
5.5 Status Display .......................................................................................................................................10
5.6 Stage Switch..........................................................................................................................................10
5.7 Locks.....................................................................................................................................................10
6. Viewing Navigator Status Screens...............................................................................................................11
6.1 Current Conditions................................................................................................................................11
6.2 Target Conditions..................................................................................................................................12
6.2.1 Target Conditions - Standard Screen With Optimum Mode OFF.................................................12
6.2.2 Target Conditions –Optimum Screen With Optimum Mode ON.................................................13
6.3 Minimum Vent......................................................................................................................................14
6.4 Stage Conditions...................................................................................................................................15
6.4.1 Inlet Conditions.............................................................................................................................15
6.4.2 On/Off Stages................................................................................................................................16
6.4.3 Natural Ventilation Stages ............................................................................................................16
6.4.4 Variable Stages .............................................................................................................................17
6.5 Historical Data......................................................................................................................................17
6.5.1 Room Temperature .......................................................................................................................17
6.5.2 Humidity #1 (Room) & Humidity #2 (Cooler) .............................................................................18
6.5.3 Water Usage (#1 or #2).................................................................................................................18
6.5.4 Ventilation Mode ..........................................................................................................................18
6.5.5 Feed History..................................................................................................................................19
6.5.6 Belt Run Times .............................................................................................................................19
6.5.7 Stage Run Times...........................................................................................................................19
6.5.8 Power Track Run Times................................................................................................................19
6.5.9 Alarm Log.....................................................................................................................................20
6.5.10 Cooler Temp .................................................................................................................................20
6.6 Back-Up Status .....................................................................................................................................20
6.7 Alarm Status..........................................................................................................................................21
6.7.1 High Temperature Alarm Details..................................................................................................22
6.7.2 Low Temperature Alarm Details...................................................................................................23
6.7.3 Tunnel Vent Alarm Details ...........................................................................................................23
6.8 Network Status......................................................................................................................................24
6.9 Program Set-Up ....................................................................................................................................24
7. Setting Programming Functions...................................................................................................................25
7.1 General Settings....................................................................................................................................25
7.2 Temperature Sensors.............................................................................................................................25
7.3 Feed Level Sensors ...............................................................................................................................26
7.4 Ventilation Inlets...................................................................................................................................26
7.5 Natural Ventilation................................................................................................................................27
7.6 Growout Curve......................................................................................................................................28
7.6.1 Growout Curve With Optimum Mode OFF ..................................................................................28
7.6.2 Growout Curve With Optimum Mode ON....................................................................................30
7.7 Tunnel Ventilation ................................................................................................................................33
7.8 ON/OFF Stages.....................................................................................................................................34
7.8.1 On/Off Stage Details.....................................................................................................................35
7.9 Variable Stage Outputs .........................................................................................................................35

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 Table of Contents
7.10 Stage Properties ....................................................................................................................................36
7.10.1 Heat Properties..............................................................................................................................36
7.10.2 Cool Stir Properties.......................................................................................................................36
7.10.3 Cool Negative Properties ..............................................................................................................36
7.10.4 Cool Negative Tunnel Properties..................................................................................................37
7.10.5 Cool Tunnel Properties .................................................................................................................37
7.10.6 Cool Evaporative Properties .........................................................................................................38
7.10.7 Natural Ventilation Properties.......................................................................................................38
7.11 Feed Clock Setup..................................................................................................................................39
7.11.1 Feed Clock Schedules...................................................................................................................39
7.12 Light Clock Setup .................................................................................................................................40
7.12.1 Light Clock Details.......................................................................................................................40
7.13 Seasonal Programs & Password Setup..................................................................................................40
7.14 Diagnostics............................................................................................................................................41
8. Fail-Safe Relay Operation............................................................................................................................43
9. Wiring Diagrams..........................................................................................................................................44
9.1 Connections of Evolution 3000 & 3001 Enclosure...............................................................................44
9.2 Setting Address Switches & LEDs on PCB 168 Stage Board...............................................................45
9.3 Connecting Temperature Sensor to Evolution 3000 & 3001 ................................................................46
9.4 Connecting Static Pressure Sensor to Evolution 3000 & 3001 .............................................................47
9.5 Connecting Humidity Sensor to Evolution 3000 & 3001......................................................................47
9.6 Connecting PC Network to Evolution 3000 & 3001.............................................................................48
9.7 Connecting Alarm Device to Evolution 3000 & 3001 ..........................................................................48
9.8 Connecting Water Meter to Evolution 3000 & 3001 ............................................................................49
9.9 Connecting Stage Jumpers of Evolution 3000 & 3001 .........................................................................50
9.10 Connecting the PowerTrak to the Evolution 3000 & 3001 ...................................................................51
9.11 Connecting the PowerTrak and S-3 Back-Up to the Evolution 3000 & 3001.......................................52
9.12 Connecting the PowerTrak and EV Back-Up to the Evolution 3000 & 3001.......................................53
9.13 Connecting the PowerTrak Power Auxiliary Switches to Evolution 3000 & 3001...............................54
9.14 Connecting PowerTrak Natural Auxiliary Switches to Evolution 3000 & 3001...................................55
9.15 Power Supply Connection.....................................................................................................................56
9.16 Evolution 3000 & 3001 Power Connection ..........................................................................................57
9.17 Connecting Local Network & Backup to the Evolution 3000 & 3001..................................................58
10. Temperature vs. Sensor Resistance Table....................................................................................................59
11. Parts List......................................................................................................................................................60
Poultry House Layout and Specification ..............................................................................................................64
1. House Specification.....................................................................................................................................64
2. Stage Programming......................................................................................................................................65
3. Temperature Curve ......................................................................................................................................66
4. Static Pressure Settings................................................................................................................................66
5. Minimum Vent.............................................................................................................................................66
6. Tunnel Settings ............................................................................................................................................66
7. Lighting Program.........................................................................................................................................67
8. Feed Program...............................................................................................................................................67
9. Back-up Specifications ................................................................................................................................68
10. Alarm Specifications....................................................................................................................................68
11. Notes............................................................................................................................................................69

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 4 of 70
Limited Warranty
1. Warranty
The GSI Group, LLC. (“GSI”) warrants products which it manufactures to be free of defects in materials and workmanship under
normal usage and conditions for a period of 12 months after sale to the original end-user or if a foreign sale, 14 months from
arrival at port of discharge, whichever is earlier. The end-user’s sole remedy (and GSI’s only obligation) is to repair or replace,
at GSI’s option and expense, products that in GSI’s judgment, contain a material defect in materials or workmanship. Expenses
incurred by or on behalf of the end-user without prior written authorization from the GSI Warranty Group shall be the sole
responsibility of the end-user.
Warranty Extensions: The Limited Warranty period is extended for the following products:
Product
Warranty Period
AP Fans and
Flooring
Performer Series Direct Drive
Fan Motor
3 Years
All Fiberglass Housings
Lifetime
All Fiberglass Propellers
Lifetime
AP/Cumberland
Flex-Flo/Pan Feeding Systems
2 Years
Cumberland
Feeding/Watering
Systems
Feeder System Pan Assemblies
5 Years **
Feed Tubes (1.75" & 2.00")
10 Years *
Centerless Augers
10 Years *
Watering Nipples
10 Years *
Grain Systems
Grain Bin Structural Design
5 Years
Grain Systems
Farm Fans
Zimmerman
Portable & Tower Dryers
2 Years
Portable & Tower Dryer Frames
and Internal Infrastructure †
5 Years
GSI further warrants that the frame, basket and excluding all auger and auger drive components of the portable and
tower dyer shall be free from defects in materials for a period of time beginning on the twelth (12th) month from the date
of purchase and continuing until the sixtieth (60th) month from the date of purchase (extended warranty period). During
the extended warranty period, GSI will replace the frame or basket components that prove to be defective under
normal conditions of use without charge, excluding the labor, transportation, and/or shipping costs incurred in the
performance of this extended warranty.
Conditions and Limitations:
THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE LIMITED WARRANTY DESCRIPTION SET FORTH
ABOVE. SPECIFICALLY, GSI MAKES NO FURTHER WARRANTY OF ANY KIND, EXPRESS OR IMPLIED,
INCLUDING, WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE OR USE IN CONNECTION WITH: (i) PRODUCT MANUFACTURED OR SOLD BY GSI OR (ii) ANY
ADVICE, INSTRUCTION, RECOMMENDATION OR SUGGESTION PROVIDED BY AN AGENT, REPRESENTATIVE
OR EMPLOYEE OF GSI REGARDING OR RELATED TO THE CONFIGURATION, INSTALLATION, LAYOUT,
SUITABILITY FOR A PARTICULAR PURPOSE, OR DESIGN OF SUCH PRODUCTS.
GSI shall not be liable for any direct, indirect, incidental or consequential damages, including, without limitation, loss of
anticipated profits or benefits. The sole and exclusive remedy is set forth in the Limited Warranty, which shall not
exceed the amount paid for the product purchased. This warranty is not transferable and applies only to the original
end-user. GSI shall have no obligation or responsibility for any representations or warranties made by or on behalf of
any dealer, agent or distributor.
GSI assumes no responsibility for claims resulting from construction defects or unauthorized modifications to products
which it manufactured. Modifications to products not specifically delineated in the manual accompanying the
equipment at initial sale will void the Limited Warranty.
This Limited Warranty shall not extend to products or parts which have been damaged by negligent use, misuse,
alteration, accident or which have been improperly/inadequately maintained. This Limited Warranty extends solely to
products manufactured by GSI.
Prior to installation, the end-user has the responsibility to comply with federal, state and local codes which apply to the
location and installation of products manufactured or sold by GSI.
* Warranty prorated from list price:
0 to 3 years –no cost to end-user
3 to 5 years –end-user pays 25%
5 to 7 years –end-user pays 50%
7 to 10 years –end user pays 75%
** Warranty prorated from list price:
0 to 3 years –no cost to end-user
3 to 5 years –end-user pays 50%
†Motors, burner components and
moving parts not included. Portable
Dryer screens included. Tower Dryer
screens not included.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 5 of 70
2. Warnings
Warning!
Before connecting power to the controller, be sure to check the position of the
voltage selector switch located next to the transformer on the EVI/O board.
Improper positioning of this switch will cause system failure.
Warning!
Maximum operating temperature of controller is 50C (122F).
Use adequate ventilation to reduce the risk of overheating of controller!
Warning!
When this controller is used in a life support heating and ventilation system
where failure could result in loss or injury, the user should provide adequate
back-up, or accept the risk of such loss or injury!
3. Ratings and Specifications
HHI Part
Number
Model
Power Supply
Curtain Output
Stage Output
6607-8015
EV-Back-up
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
12V, 3A
6607-8016
EV-16-Expansion
120/230 VAC 50/60 Hz
NA
1 HP @ 240VAC
6607-8020
EV-3000-R1-00
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
N/A
6607-8021
EV-3000-16-00
120/230 VAC 50/60 Hz
N/A
1 HP @ 240 VAC
6607-8022
EV-3000-16-01
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8023
EV-3000-16-02
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8024
EV-3000-16-03
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8025
EV-3001-16-00
120/230 VAC 50/60 Hz
N/A
1 HP @ 240 VAC
6607-8026
EV-3001-16-01
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8027
EV-3001-16-02
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8028
EV-3001-16-03
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8201
EV-3000-16-S0 Spanish
120/230 VAC 50/60 Hz
N/A
1 HP @ 240 VAC
6607-8202
EV-3000-16-S1 Spanish
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8203
EV-3000-16-S2 Spanish
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8204
EV-3000-16-S3 Spanish
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8205
EV-3001-16-S0 Spanish
120/230 VAC 50/60 Hz
N/A
1 HP @ 240 VAC
6607-8206
EV-3001-16-S1 Spanish
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8207
EV-3001-16-S2 Spanish
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
6607-8208
EV-3001-16-S3 Spanish
120/230 VAC 50/60 Hz
½ HP @ 240 VAC
1 HP @ 240 VAC
NOTE: Room Temperature Must Be Kept Between 32F/0C and 122F/50C.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 6 of 70
EVOLUTION 3000 FRONT PANEL
Navigator
Buttons
Optional Natural Stages
Stage switches
(ON, OFF,
AUTO)
'Stage On'
Indicators
White spaces
are for stickers
to identify stage
operations
Editor Buttons
Main Display
Optional
Ventilation
Stages
4. Introduction
The Evolution 3000 Controller is the first member of Cumberland's new environmental controller line. The
Evolution 3001 Controller has the same operational features as the 3000 except the 3001 has a larger
display. The Evolution 3000 and 3001 Controllers have 16 stages standard. The Evolution 3000 and 3001
Controllers can be expanded up to 64 stages. (i.e. 16, 32, 48 and 64 stages).
Features:
Input Device Options
8 inside temperature sensors
1 outside temperature sensor
2 humidity sensors
1 static pressure transducer
2 digital water meter input
HHNet connection for PC compatibility
6 PowerTrak auxiliary switch inputs
Feed Management (Optional)
2 Feed Bin Level Sensors
2 Auger Runtime Sensors
4 Belt Runtime Sensors
Output Devices (Standard)
16 On/Off output stages with manual override switches
(2) 0-10 Vdc Analog Outputs
Open/Off/Close PowerTrak stages with manual override (Depending On Model)
1 Alarm relay with both N.O. and N.C. contacts
Output Devices: (Optional)
2 sets of Open/Off/Close PowerTrak stages with manual override
Variable speed output drive
16 On/Off output stages with manual override switches
Patented integrated Evolution Back-up
5. Evolution Front Panel
The Evolution Controller is divided into two main areas. On the left is the Main Control Panel containing
the Main Display, Editor, Navigator and the Inlet Stage Controls. On the right are the Stage Switches. The
Navigator is used to select the information to be displayed in the Main Display. Once the desired
information is selected in the Navigator, the Editor is used to scan and modify the data.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 7 of 70
EVOLUTION 3000 EXPANSION STAGES FRONT PANEL
EVOLUTION 3001 FRONT PANEL
Navigator
Buttons
Optional
Natural
Stages
Stage switches
(ON, OFF,
AUTO)
'Stage On'
Indicators
White spaces
are for stickers
to identify stage
operations
Editor Buttons
Main Display
(Larger Scrolling Area)
Optional
Ventilation
Stages

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 8 of 70
5.1 Navigator Panel
The Navigator buttons are used to select a controller function. Press up or down button to toggle between
functions. LED (light emitting diode) lights when a function is selected and the associated data is displayed
in the Main Display.
5.2 Editor Panel
The Editor buttons are used to select functions that appear in the Main Display screen. The arrow buttons
are used to scroll to variables that appear within the current screen of the Main Display. The plus (+) and
minus (-) buttons are used to change or modify a variable's value. The Enter button is used to link to a new
display screen of a selected variable. NOTE: To return to the main function screen, press either Up () or
Down () Navigator button.
Minus button
(Use to decrease
value of variable)
Enter Button
(Links to other
screens)
Plus button
(Use to increase
value of variable)
Scroll Buttons
Function Modes
Up Select Button
Down Select
Button
Light Emitting
Diode Indicator

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 9 of 70
5.3 Main Display Contrast
The main display contrast can be adjusted to adapt to various lighting conditions. The Contrast Control is
located on the opposite side of the front panel. Use the Contrast Control potentiometer and a small flat-
head screw-driver to manually darken or lighten the screen. Turn clockwise to darken the display;
Counter-clockwise to lighten the display.
CAUTION: DO NOT CONTACT OTHER COMPONENTS OR WIRES.
5.4 Inlet Stages
Optional inlet stages may be added to control vents & curtains. Up to 4 inlet stages may be added per
controller unit. When Auto/Manual toggle switch is placed in Auto position, inlet opens and closes
according to programmed instructions. Use the Open/Close toggle switch to manually open or close inlet
when Auto/Manual toggle switch is placed in Manual position. The Notation area is for labeling the inlet.
Under normal circumstances the machines should be left in automatic (Auto) as shown above.
Notation Area
Manually opens or
closes inlet
Toggle switch
(Auto or Manual
operation)
Controller opens or
closes inlet
Contrast Control

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 10 of 70
** PASSWORD PROTECTED **
You must enter the current controller
Password to continue.
Press the ENTER button to proceed.
Password: XXXX
5.5 Status Display
The following is an example of Main Display screen displaying the standard Target Conditions status
screen. The Main Display screen displays both status and programming screens.
5.6 Stage Switch
The stage LED indicator lights when a stage is active. The stage switch is used to select Auto operation,
On, or Off. If switch is in Auto position, the stage operation is controlled by the controller. That is, the
stage may turn on and off according to settings selected from the Main Display screen. If switch is in the
On position, a stage is On continuously. If switch is in the Off position, a stage is Off with the exception of
Back-Up conditions.
The white space is used to affix a label indicating stage function (i.e. brooder, fan, light, cool, etc.)
NOTE: Stages 1-16 are marked on Main panel. For optional stages 17-64, use stick-on label to number
stages.
5.7 Locks
A lock feature has been included for additional
security to the Evolution 3000 and 3001 settings
with software versions V0.16 and higher. This
feature locks the Program Setup screens to
prevent changes. Locked screens are noted by a
lock symbol ( ) in the upper right of the
screen. The Target Conditions and Minimum
Vent screens are not lockable. When the lock
feature is disabled ( ), all screens will show
unlocked until the password is changed. See
Section 7.13.
NOTE: The Diagnostics screen can only be unlocked using the HHI Service Code; Contact your local
dealer for assistance.
1
1
Stage number
(Use labels to denote
stages 17-64)
ON, OFF, AUTO
Switch positions
Stick Icon label onto
white area or use for
notation
LED Indicator (lights
when stage is ON)
Icon labels are provided to
affix to white area of stage
control. Icon symbols are
shown at right.
Heater Negative Fan
Light StirFan
Neg./Tun. Feed Evap. Cooling Tunnel Fan
The Scroll Symbol is a
flashing down arrow () that
indicates more text outside
of display screen. Use
up/down editor arrow keys
to scroll text.
The Link Symbol () is a right
pointing arrow and indicates a
link to another display screen.
To change
parameter:
Select parameter
using editor
arrow keys. Use
+ and - keys to
change value.
(1)Target Temp =
77.5°
(2)Ramping:
On
(3)Target Press =
0.04 wc
(4)Ramping:
Off
(5)Tunnel Press =
0.00 wc
(6)Target Humidity
< 60%
(7)Light Schedule
(8)Feed
Schedule
77.5°
NOTE: If Optimum Mode is turned On, the Target Conditions screen
will have differences from the standard screen shown above.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 11 of 70
NOTE: In this manual, Reference
numbers refer to descriptions given in
text. These numbers do not appear
on display.
Mon 14 Jun 2007 5:00 p
(1) Vent Mode:
Minimum
(6) Growout Day:
40
(2) Room Temp:
71.4°
(7) Water Consumption
Target:
70.0°
1. 240
(10/hr)
(3) Outside:
77.0°
2. 280
(10/hr)
(4) Pressure:
0.00 wc
(8) Feed Levels
Target:
0.04 wc
1. 11.2ft
( 60%)
(5) Humidity:
0%
2. 5.0ft
( 23%)
(9)
* Sensor 1: 71.6°
* Sensor 2: 71.2°
* Sensor 3: 71.4°
Sensor 4:---.-°
Sensor 5:---.-°
Sensor 6:---.-°
Sensor 7:---.-°
Sensor 8:---.-°
Sensor is enabled
* Sensor used in Room Temp Calculation
6. Viewing Navigator Status Screens
The following nine screens are available: Current Conditions, Target Conditions, Minimum Vent, Stage
Conditions, Historical Data, Back-Up Status, Alarm Status, Network Status, Program Setup. The Navigator
selects the desired status screen by pressing the up and down SELECT arrows. The first eight screens
display status information and various setup options. The last screen is the Program Screen. To change
program parameters the Program Setup Screen must be selected.
6.1 Current Conditions
The current environmental conditions of the building are shown here. Below is a table describing the
variables that can appear in the Current Conditions status screen.
The numbers in brackets e.g. (1) refer to the descriptions below the sample screen displays.
(1) Vent Mode –Indicates the current ventilation mode: either Minimum, Natural, Power, Transition or
Tunnel.
(2) Room Temp –The average temperature of the sensors for display. Target –Target Temperature.
(3) Outside (Temperature) –The outside temperature as indicated by the outside sensor.
(4) Pressure –The current atmospheric pressure internal to the building. Target –Target Pressure.
(5) Humidity –The percent of water vapor of the air inside the building.
VENT MODE
Definition
Minimum
Heat stages or timer fans operating. None of the negative stages are on because of
temperature.
Natural
The main curtains are open.
Power
The curtains are up and there are negative fans on because of temperature.
Transition
The control is transitioning into tunnel ventilation from either power or natural
ventilation. The control is making the adjustments needed to go into tunnel.
Tunnel
The tunnel signal has been activated and the system has entered into tunnel.
(6) Growout Day –The current day in the growout period. The Current Conditions LED on the Navigator
panel will blink if the growout day is later then the current date.
(7) Water Consumption –Water consumed for the current day; The total for the day is listed first then the
units per hour is shown inside ( ). Two water meters may be monitored (Water Meter 1 & Meter
2).
(8) Feed Level –The Feed level is shown in number of feet from the bottom first then the percentage of
feed remaining in the feed bin is shown inside ( ). Two feed bins may be monitored (Bin #1 & Bin
#2).
(9) Sensor 1 through 8 –The current temperature read by each sensor.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 12 of 70
(1)Target Temp =
77.5°
(2)Ramping:
On
(3)Target Press =
0.04 wc
(4)Ramping:
Off
(5)Tunnel Press =
0.00 wc
(6)Target Humidity
< 60%
(7)Light Schedule
(8)Feed Schedule
Cooler Conditions
(9)Temp:
76.1°
(10)Target=
70.5°
(11)Humidity:
43%
(12)Range=
30%-35%
6.2 Target Conditions
The current target environmental conditions of the building are shown below. The specific Target
Conditions screen features and setting options will depend on whether Optimum Mode is ON or OFF.
Examples and details for both the Standard screen and Optimum screen are shown in the following two
subsections.
6.2.1 Target Conditions - Standard Screen With Optimum Mode OFF
(1) Target Temp - This is the desired temperature of
the building.
(2) Ramping –Indicates if ramping of the Target
Temperature is turned On or Off. You are also
allowed to turn the temperature ramping on or off
in the program set up screen. You use the
Navigator to reach the Program Setup screen and
then navigate down to "Temperature Ramp" and
press enter. See Section 7.6.
(3) Target Press - This is the desired negative
pressure in the building. See Section 7.4.
(4) Ramping –Indicates if ramping for the Target
Pressure is turned on: On or Off. You are also
allowed to turn the pressure ramping on or off in
the program setup screen. See Section 7.4.
(5) Tunnel Pressure –Indicates the desired negative
pressure in the building while in the Tunnel
Mode. See Section 7.4.
(6) Target Humidity –The desired humidity inside
the building (Humidity Sensor # 1) is less than
this set number. For every percentage increase in
humidity over the set %, the timer percentage
will increase.
EXAMPLE:
Target Humidity < 65%
Timer Percentage is set to 20% of 5 minutes.
If Humidity in building is at 70%, the timer
percentage will be at 25%.
NOTE: This only affects the variable timer %.
Min1% and Min2% are unaffected.
(7) Light Schedule –View Light Clock Setup. See
Section 7.12.
(8) Feed Schedule –View Feed Clock Setup. See
Section 7.11.
(9) Cooler Conditions Temp –This is the current
temperature inside the cooler.
(10) Cooler Conditions Temp Target –This is the
desired temperature of the cooler.
(11) Cooler Conditions Humidity –This is the
current humidity inside the cooler (Humidity
Sensor # 2).
(12) Cooler Conditions Humidity Range –This is
the desired humidity range of the cooler.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 13 of 70
Optimum Settings
Adjustments
(1)Target Temp =
77.5°
(2)Adjust =
+0.0°
(3)Optimum Run%:
10%
(4)Adjust =
+00%
(5)Target Press =
0.04 wc
(6)Tunnel =
0.00 wc
(7)Opt. Timer:
--6-4---
(8)Humidity <
60%
(9)Light Schedule
(10)Feed Schedule
Cooler Conditions
(11)Temp:
76.1°
(12)Target=
70.5°
(13)Humidity:
43%
(14)Range=
30%-35%
6.2.2 Target Conditions –Optimum Screen With Optimum Mode ON
The target conditions screen shown below represents the display and options when the Optimum Mode is
turned On. Refer to Section 7.1 for turning the Optimum Mode On or Off and Section 7.6.2 for the
Optimum Mode Growout Curve.
(1) Target Temp –Displays the desired temperature of the building for the current growout day.
(2) Adjust –Adjusts the programmed Target Temperature by this amount until set otherwise. The displayed Target
Temp to the left will increase or decrease as this number is adjusted.
(3) Optimum Run% –Displays the minimum vent run % for the current growout day. The Run % is the percentage
of the Minimum Timer Cycle that the stage will run.
(4) Adjust –Adjusts the programmed Optimum Run% by this amount until set otherwise. The displayed Optimum
Run% to the left will increase or decrease as this number is adjusted.
(5) Target Press - This is the desired negative pressure in the building. See Section 7.4.
(6) Tunnel Pressure –Indicates the desired negative pressure in the building while in the Tunnel Mode. See
Section 7.4.
(7) Opt. Timer –Displays the current optimum timer active determined by the growout curve.
(8) Humidity –The desired target humidity inside the building (Humidity Sensor # 1) is less than this set number.
For every percentage increase in humidity over the set %, the timer percentage will increase.
EXAMPLE:
Target Humidity < 65%
Timer Percentage is set to 20% of 5 minutes.
If Humidity in building is at 70%, the timer percentage will be at 25%.
NOTE: This only affects the variable timer %. Min1% and Min2% are unaffected.
(9) Light Schedule –View Light Clock Setup. See Section 7.12.
(10) Feed Schedule –View Feed Clock Setup. See Section 7.11.
(11) Cooler Conditions Temp –This is the current temperature inside the cooler.
(12) Cooler Conditions Temp Target –This is the desired temperature of the cooler.
(13) Cooler Conditions Humidity –This is the current humidity inside the cooler (Humidity Sensor # 2).
(14) Cooler Conditions Humidity Range –This is the desired humidity range of the cooler.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 14 of 70
(1) MINIMUM TIMERS:
(2)Cycle = 5 m ( 300s)
(6)VARIABLE SPEED:
(3)Min1 % = 40% ( 215s)
(7)V1 Minimum % = 50%(55%)
(4)Min2 % = 20% ( 108s)
(8)V2 Minimum % = 40%(100%)
(5)Var % = 20% ( 108s)
(9)VARIABLE TIMER:
(10)Sensors = Outside
(11)Max Run % = 65%
(12)Max Temp = 85.0°
(13)Min Run % = 20%
(14)Min Temp = 70.0°
(15)COOL TIMER:
(16)Max Run % = 100%
(17)Cycle = 10 m ( 600s)
(18)Min Run % = 55%
NOTE: Cycle in seconds
NOTE: Run Time in seconds
6.3 Minimum Vent
The Minimum Vent status screen display:
(1) Minimum Timer 1 - The Minimum timer one and
two both share the same cycle time. Different timer
percentages may be set for minimum 1 vs.
minimum 2. If the vent anticipation is being used,
the vents will start opening before a negative
ventilation stage turns on and will adjust until the
vent opening necessary for the desired target
pressure is achieved.
(2) Cycle - The length of Timer 1 cycle. Cycle = 1 to
20 minutes.
(3) Min1 % - The percentage of the Timer 1 cycle that
the stage will run.
(4) Min2 % - The percentage of the Timer 2 cycle that
the stage will run.
(5) Var % - The percentage of time a stage is
currently running using the variable timer based off
the temperature.
NOTE: The Minimum timer one and two both share
the same cycle time. Different timer percentages
may be set for Minimum 1 and Minimum 2. If the
vent anticipation is being used, both Minimum 1
and Variable will start the vents open before a stage
comes on.
(6) Variable Speed: These settings are used to set up
variable speed fan operation.
(7) V1 Minimum - The minimum speed or minimum
percentage of light intensity for V1; The value
inside the parenthesis shows the current
percentage.
(8) V2 Minimum -The minimum speed or minimum
percentage of light intensity for V2; The value
inside the parenthesis shows the current percentage.
(9) Variable Timer - The variable timer is similar to
the expanded timer found in the System 2000 PC-8.
The variable timer will vary the timer based on
temperature. See chart shown below.
(10) Sensors - The sensors used to determine the run
time. Active sensors will be indicated by a number
starting with #1 from right to left. Inactive sensors
will be indicated by a - or hyphen. When "outside-"
is displayed, outside sensor is active. For example,
If sensors 1, 2 and 3 are being used, "-----321" will
be displayed. When “outside” is displayed, the
outside sensor is active.
NOTE: When any of the temperature sensors #1-8 are
selected, the “Max Temp” and “Min Temp”
settings will float with the Target Temperature.
When “outside” is selected, the variable timer
strictly uses the “Max Temp” and “Min Temp”
values selected and are not associated with the
Target Temperature (will not float with Target).
(11) Max Run % - The maximum Run Time
percentage.
(12) Max Temp - The temperature at which the timer
will run Maximum Run time % percentage.
(13) Min Run % - The minimum Run Time
percentage.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 15 of 70
Inlet Conditions
#
STATUS
MODE
PRESS
OPENED
CLOSED
U1
Close
Vent
0.00
No
No
U2
Close
Tun
0.00
No
No
#
STATUS
MODE
RTEMP
ON
OFF
TIME
-----------
TARGET
70°
---------
V1
0%
CTUN
79.4°
89.4
89.0
Ramp
V2
0%
Cstir
79.6°
89.4
89.0
None
1
On
Light
Ramp
2
On
Cstir
79.6°
76°
95°
None
.
.
.
.
.
.
.
16
On
Cstir
79.6°
76°
95°
Min1
Inlet Conditions
(1)#
(2)STATUS
(3)MODE
(4)PRESS
(5)OPENED
(6)CLOSED
U1
Open
Vent
0.04
No
No
U2
Close
Tun
0.04
No
Yes
.
.
.
.
.
.
.
.
.
.
.
.
.
.
(14) Min Temp - The minimum temperature. The
timer will be at minimum Run %.
(15) Cool Timer: Cool timer is also allowed a
different timer cycle if needed. This can be used
for foggers or cool cell systems.
(16) Max Run - The Cool Timer Maximum Run Time
percentage.
(17) Cycle - Cycle Time in Minutes. Cool timer is
also allowed a different timer cycle if needed.
This will be used for foggers or cool cell systems.
(18) Min Run - The Cool Timer Minimum Run Time
percentage.
6.4 Stage Conditions
When the Stage Conditions screen is selected by using the Navigator Select arrows, the following menu
screen is shown. Use the up and down arrows in the Editor to view the desired information. Notice that the
Light Clock and Feed Clock Stages are listed after the Inlet Conditions section. The Heat Stages are then
displayed in order of increasing ON Temperatures. The Cool stages, including the Variable Output stages,
are listed below the Target Line in order of increasing ON Temperatures.
6.4.1 Inlet Conditions
The Inlet Conditions part of the Stage Conditions screen is used to control Power Trak operation for power
ventilation. U1 is normally for baffle boards and U2 controls tunnel inlets.
(1) #- The stage bank either U1 or U2.
(2) Status - Indicates if the Stage is Off, Opening or Closing.
(3) Mode –The mode column tells you how the machine will be operating. If it will be a vent machine
"VENT" or a tunnel machine "TUN" machine.
(4) Pressure –Indicates the pressure in the building.
(5) Opened –Indicates if the machine is fully open (Yes or No). When the machine is fully open on the
open auxiliary switch, this column will indicate a “Yes”.
(6) Closed –Indicates if the machine is fully closed (Yes or No). When the machine is fully closed on the
closed auxiliary switch, this column will indicate a “Yes”.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 16 of 70
.
.
.
.
.
.
.
.
.
.
.
.
.
.
(1)#
(2)STATUS
(3)MODE
(4)RTEMP
(5)ON
(6)OFF
(7)TIME
TUN
OFF
CTUN
79.4°
85°
80°
1
On
Light
Ramp
2
On
Cstir
79.6°
76°
95°
None
.
.
.
.
.
.
.
-----------
(8)TARGET
70°
---------
.
.
.
.
.
.
.
16
On
Cstir
79.6°
76°
95°
Min1
(1)#
(2)STATUS
(3)MODE
(4)RTEMP
(5)ON
(6)OFF
(7)TIME
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
U1
On
NAT
CLOSE
73.0°
72.0°
CLOSED: NO
U2
On
N&T
CLOSE
73.0°
72.0°
CLOSED: NO
Min1
U1
Off
NAT
OPEN
73.0°
74.0°
CLOSED: NO
U2
Off
N&T
OPEN
73.0°
74.0°
CLOSED: NO
.
.
.
.
.
.
.
.
.
.
.
.
.
.
6.4.2 On/Off Stages
The On/Off stages are used for devices that do not need a variable speed capability. This portion of the
Stage Conditions screen shows how the On/Off Stages and are set.
(1) # - Identifies the On\Off stage number
or Tunnel and lists them in the order
of priority. Tunnel is not a stage like
the Stage Master and Vent Master.
This parameter is set in the tunnel
ventilation of Program Setup screen.
See Section 7.7, Tunnel
Ventilation.
(2) Status - Indicates if the stage is currently
Timed, On, or Off.
(3) Mode - This column indicates how the
stage is programmed. Any stage can
be set to any of these modes. The
available stage options are: Off,
Heat, CSTIR, CNEG, CNEGT,
CTUN, LIGHT, FEED or CEVAP.
(4) Rtemp - The Rtemp column will indicate the
current temperature from which the stage is
operating.
(5) On –The current temperature setting for the on
point temperature of the stage.
(6) Off - The current temperature setting for the off
point temperature of the stage.
(7) Time - This column indicates if a stage is on a
timer and shows the different timers you are
allowed to put a stage on. The timer options
are: None, Min1, Min2, Var, Cool, or Opt
xx.
(8) Target –Target Temperature.
6.4.3 Natural Ventilation Stages
Natural Ventilation stages are used to open and close side curtains to allow natural ventilation.
(1) #- The stage bank either U1 or U2.
(2) Status - This column will indicate whether the machine is Off, Opening or Closing.
(3) Mode –The mode column indicates how the machine will be operating. It will be a natural curtain
"NAT" or a natural and tunnel "N&T" machine(U2 only). OPEN or CLOSE will be shown beside
the mode to show whether the specific line refers to the Open or Close function.
(4) Rtemp –The Rtemp column will indicate the current temperature the curtain machine is operating from.
(5) ON –The temperature at which the stage operates.
(6) OFF and (7) TIME –This column indicates if the machine is fully closed. When the machine is on the
closed auxiliary switch, this column will display “Yes”.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 17 of 70
(1)#
(2)STATUS
(3)MODE
(4)RTEMP
(5)ON
(6)OFF
(7)TIME
.
.
.
.
.
.
.
V1
50%
Light
Ramp
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
V2
75%
CStir
88.7°
76.4°
74.0°
None
Min1
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Select and Press ‘Enter’:
Room TemperatureStage 1 –16 RunTimes
HumidityStage 17 –32 RunTimes
Water Usage #1Stage 33 - 48 RunTimes
Water Usage #2Stage 49 –64 RunTimes
Ventilation ModePowerTrack RunTimes
Feed HistoryAlarm Log
Belt RuntimesCooler Temp
(1)DAY (2)HIGH TEMP (3)AVE (4)LOW TEMP
21 71.0°-12:34p 66.3° 61.6°–12:34a
20 71.0°-12:34p 66.3° 61.6°–12:34a
. . . . . .
. . . . . .
1 71.0°-12:34p 66.3° 61.6°–12:34a
6.4.4 Variable Stages
The Variable stages are used to control devices (i.e. fans & lights) with a variable capability.
(1) # - The Stage bank either V1 or V2.
(2) Status - This is the current run percentage that the device is operating.
(3) Mode –Indicates how the stage is programmed: CSTIR, CNEG, CNEGT, CTUN or LIGHT.
(4) Rtemp –The Rtemp column indicates the current temperature from which the stage is operating.
(5) ON –The ON column indicates the maximum ON temperature at which the variable speed fan will reach
full speed.
(6) OFF -The OFF column indicates the minimum ON temperature at which the fan will run at minimum
speed.
(7) Time –None, Min1, Min2, Var or Always ON (ON). Always ON when Rtemp is below MIN ON.
6.5 Historical Data
This screen provides access to historical data. Highlight the selection and press the ENTER button on the
EDITOR panel.
6.5.1 Room Temperature
This screen shows the highest and lowest
room temperature for each day for up to 99
days. The last day reported will appear at the
top of the list. The list can contain data up
to 99 days. After displaying 99 days, oldest
data will be deleted.
(1) Day –The specific day in the growout
period. Values = 1 day to 99 days.
(2) High Temp –The high recorded temperature and the time of day that it occurred.
(3) AVE –The average recorded temperature for the day.
(4) Low Temp - The low recorded temperature and the time of day low temperature occurred.
NOTE: The High and Low temperature readings are taken from the Sensors for Display in "Sensor Setup"
of the Program Setup Screen.

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 18 of 70
Water Meter 1
(1)DAY (2)HIGH RATE (3)DAILY TOTALS
41 24/hr-12:00p 240
40 20/hr-12:34p 210
. . . .
35 10/hr-11:15p 200
. . . .
. . . .
24 15/hr-12:05p 130
. . . .
. . . .
1 5/hr-1:00p 50
6.5.2 Humidity #1 (Room) & Humidity #2 (Cooler)
This screen shows the highest room humidity
& cooler humidity for each day for up to 99
days. The last day reported will appear at the
top of the list. The list can contain data up to
99 days. After displaying 99 days, oldest data
will be deleted.
(1) Day –The specific day in the growout
period. Values = 1 day to 99 days.
(2) High Room –The highest recorded room humidity (Humidity #1) and the time of day that it occurred.
(3) High Cooler - The highest recorded cooler humidity (Humidity #2) and the time of day that it occurred.
6.5.3 Water Usage (#1 or #2)
This screen gives the Water Usage of the
building per day of growout, high rate, and
water total. The screen display format is the
same for either water usage #1 or #2.
(1) Day–The specific day in the growout
period. Values = 1 day to 99 days.
(2) High Rate –The highest recorded water
rate and the time of day that it
occurred.
(3) Total For Each Day –The total water
usage for each day of growout.
6.5.4 Ventilation Mode
This screen shows the length of time in
hours and minutes that the Control is in
different ventilation modes. NOTE:
Natural mode is when the system is in
natural ventilation and the main curtains
are open.
Transition mode is when the control is
between power and tunnel ventilation. The
control is making the adjustments needed
to go into tunnel. Tunnel mode is when
the tunnel signal has been activated and
the system has entered into tunnel.
(1) Minimum Ventilation –The time spent in minimum mode. Heaters & timer fans running.
(2) Power Ventilation –The time spent in the Power Ventilation mode.
(3) Natural Ventilation –The time the side wall curtains are open.
(4) Transition to Tunnel –The time required to transit to tunnel mode. (3 minutes per transition)
(5) Tunnel Ventilation –The time spent in the Tunnel mode.
(1)DAY (2)High Room (3)High Cooler
21 70%-12:34p 65-12:34p
20 70%-12:34p 65-12:34p
. . . . .
. . . . .
1 70%-12:34p 65–12:34p
Today Yesterday
(1)Minimum Ventilation 6:07 10:31
(2)Power Ventilation 1:10 6:29
(3)Natural Ventilation 2:00 1:00
(4)Transition to Tunnel 0:03 0:09
(5)Tunnel Ventilation 0:45 4:51

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 19 of 70
(1)Day (2)Belt1 Belt2 Belt3 Belt4
(3)Status On On On On
141 2:24 2:24 2:24 2:24
140 2:24 2:24 2:24 2:24
. . . . .
. . . . .
1 2:24 2:24 2:24 2:24
6.5.5 Feed History
This screen shows the estimated daily
amount of feed used and the total time
that the feed line motors have been
running.
(1) Day –The specific day in the
growout period. Values = 1
to 99 days.
(2) Usage –The amount of feed used
from Bin #1 and Bin #2
combined for each day of
growout. Measurements =
pounds (lb.).
(3) Run 1 –The total amount of run-time feed line #1 was running for each day of growout. Measurements
= Hours and minutes.
(4) Run 2 –The total amount of run-time feed line #2 was running for each day of growout. Measurements
= Hours and minutes.
(5) Status –The status of the auger current sensor whether the sensor is On or Off. ON indicates the motor
is running and OFF indicates the motor is not running.
6.5.6 Belt Run Times
This screen shows the history of the Belt
runtimes. It keeps track of the last 100 days.
(1) Day –The specific day in the growout
period.
(2) Belt 1 thru Belt 4 –The length of time in
hours and minutes that the Belt has run
on the current day.
(3) Status –The status of the belt current sensor whether the sensor is On or Off. ON indicates the motor is
running and OFF indicates the motor is not running.
6.5.7 Stage Run Times
This screen shows the length of time in hours and
minutes that the individual stages have run, on
the current day and previous day.
(1) Stage –Identifies the stage number.
(2) Current Day –The length of time in hours
and minutes that the stage has run on the
current day.
(3) Previous Day - The length of time in hours and minutes that the stage has run on the previous day.
6.5.8 Power Track Run Times
This screen shows the length of time that
the Power Track equipment has been
running.
(1) Inlet #1 and #2 - The length of time
in hours and minutes that the
inlets have run on the current
and previous days.
(2) Natural #1 and #2 - The length of
time in hours and minutes that
the natural inlets have run on the
current and previous days.
(1)Day (2)Usage (3)Auger1 (4)Auger2
(5)Status On On
41 2100 lb 4:10 9:10
40 2000 lb 3:00 8:00
. . . .
35 1500 lb 3:00 8:00
. . . .
. . . .
24 1000 lb 1:30 6:30
. . . .
. . . .
1 150 lb 1:10 6:10
(1)Stage (2)Current Day (3)Previous Day
1 2:24 2:24
2 2:24 2:24
. . .
. . .
16 2:24 2:24
Stage Current Day Previous Day
(1)Inlet #1
Open 8:00 8:00
Close 10:00 10:00
(1)Inlet #2
Open 10:00 10:00
Close 10:00 10:00
(2)Nat #1
Open 1:00 1:00
Close 23:00 23:00
(2)Nat #2
Open 1:00 1:00
Close 23:00 23:00

Part No. 4801-5307 Rev 2-15 Evolution 3000 and 3001 20 of 70
(1)DAY (2)HIGH TEMP (3)LOW TEMP
21 71.0°-12:34p 61.6°–12:34a
20 71.0°-12:34p 61.6°–12:34a
. . . . .
. . . . .
1 71.0°-12:34p 61.6°–12:34a
6.5.9 Alarm Log
This screen shows the list of the past 20 alarms and status information starting with the most recent
occurrence.
(1) Alarm Description –
The alarm problem
area.
(2) Alarm Status –The
alarm status
(Failure or
Correted).
(3) Date of Alarm –The
date the alarm
occurred or was
corrected.
(4) Time of Alarm –The time the alarm occurred or was corrected.
6.5.10 Cooler Temp
This screen shows the highest and lowest
cooler room temperatures for each day for
up to 99 days. The last day reported will
appear at the top of the list. The list can
contain data up to 99 days. After displaying
99 days, oldest data will be deleted.
(1) Day –The specific day in the growout
period. Values = 1 to 99 days.
(2) High Temp –The high recorded temperature and the time of day that it occurred.
(3) Low Temp –The low recorded temperature and the time of day low temperature occurred.
NOTE: The Cooler High and Low temperature readings are recorded ONLY from Sensor 8 for display in
"Sensor Setup" of the Program Setup Screen.
6.6 Back-Up Status
The Back-Up status shows the status information concerning back-up operation.
NOTE: This is the high and low limit of the Evolution Back-Up system. These setting are set in the Back-
Up system.
(1) Back-up High Limit –The high temperature limit at which the Back-up stages will start turning on cool
stages.
(2) Target Temperature –Backup target temperature.
(3) Back-Up Low Limit - The low temperature limit at which the Back-up will turn on the heat stage.
(4) Back-Up Run % The Back-up timer percentage.
NOTE: This is the timer percentage of the Evolution Back-Up system. This setting is set in the Back-Up
system. This setting is automatically calculated based on the controller target temperature. If the
Back-Up fails to communicate with the Evolution 3000 control the Back-Up will display an LnE.
At this point the Back-Up will take over minimum ventilation by running all Cool 1 circuits on this
timer. This percentage is how long the fan will run out of five minutes.
** Alarm Log **
1 (1)Tunnel Vent (2)Corrected @ (3)2/ 5 (4)1:26p
2 Low Press Failure @ 2/ 5 1:09p
3 Lo Water Rate Corrected @ 2/ 3 3:39p
4 Cycle Press Failure @ 2/ 1 4:15a
5 Low Temp Corrected @ 1/ 30 3:09p
6 Lo Water Rate Corrected @ 1/ 27 12:38a
7 Lo Water Rate Corrected @ 1/ 21 7:45a
8 Lo Water Rate Corrected @ 1/ 17 9:52p
9 Low Pressure Failure @ 1/ 15 5:21p
10 Max Runtime1 Corrected @ 1/ 10 8:27a
(1)Back-Up High Limit: 86°
(2)Target Temperature: 70°
(3)Back-Up Low Limit: 60°
(4)Back-Up Run %: 0% (5)Cycle: 5 minutes
(6)Warning if Back-Up +/- 11° from Target
(7)Alarm if Back-Up +/- 12° from Target
This manual suits for next models
1
Table of contents
Other Cumberland Controllers manuals

Cumberland
Cumberland EDGE 074-11793 Quick start guide

Cumberland
Cumberland Evolution Variable Output User manual

Cumberland
Cumberland Evolution Back-Up User manual

Cumberland
Cumberland PNEG-881 User manual

Cumberland
Cumberland Evolution 4000 User manual

Cumberland
Cumberland Evolution 1200 Series User manual

Cumberland
Cumberland EDGE 2 User manual

Cumberland
Cumberland Evolution S3 User manual

Cumberland
Cumberland SPRKT2415 Specification sheet

Cumberland
Cumberland Smart-Flex FLX-4629 User manual