
VoCALL Compact Installation & Maintenance Manual
PLANNING THE WIRING
All System wiring should be installed to meet the appropriate parts of BS5839-9 (2003) and BS 7671
(Wiring Regulations). Other national standards of installation should be adhered to where applicable.
Do not test wiring with an insulation tester (Megger) with any equipment or speakers connected, as the
500 Volt test voltage will destroy these devices totally.
You must observe local wiring regulations. Do not run SELV and LV cables in the same enclosure
without adequate insulation between them.
Mains Connection
>3mm
3A
Main
Distribution
Board
>0.75mm2<2.5mm2
UNITY
VoCALL
Compact
Each VoCALL Compact requires a 3A spur, returning to a breaker clearly marked “EVCS DO NOT
TURN OFF”. If the units are distributed around a site it is essential all units are on the same mains
phase, as they are classified TEN 230V, powering from different phases can mean a 440V potential can
be present in a unit during a major fault incident.
Batteries
The VoCALL Compact requires one number 12V 3.2AH sealed lead acid batteries to provide backup
power in the event of mains failure as defined in BS5839pt8 for 24 hours standby and 30 minutes
operation.
For 72hour standby and 1 hour operation one number 12V 17AH battery is required, these will need to
be fitted in an external battery enclosure, the monitored charger in the VoCALL Compact is capable of
charging and monitoring these batteries.
Safety Information:
Sealed Lead acid batteries contain sulphuric acid which can cause burns if
exposed to the skin, the low internal resistance of these batteries means large
currents will flow if they are accidentally short circuited, causing burns and a risk
of fire- exercise caution when handling batteries.
Power Up Procedure:
Always apply mains power before connecting batteries, do not commission
VoCALL Compact on batteries, as the high inrush current required by the power
supply may rupture the battery fuse.
Always connect the Positive (Red +) terminal first.
Power Down Procedure
Disconnect the batteries before removing the mains power; always remove the
negative (Black – terminal) first.
Document DCC VCC 7001-01 Rev 1 August 2007 Page 7 of 12