Damar D450 User manual

Important Safeguards
When using electrical equipment, basic safety precau-
tions should always be followed including the
following: READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
All servicing should be performed by qualified personnel only.
To prevent high voltage from being on red & yellow output
leads prior to installation, battery connector must be open. Do
not join battery connector until installation is complete and AC
power is supplied to the emergency ballast.
Do not use this equipment outdoors.
This product is designed for use in UL Listed indoor fixtures
except in air handling, heated air outlet or hazardous locations.
Do not let power supply cords touch hot surfaces.
Do not mount near gas or electric heaters.
Do not mount near open flames or sparks.
Do not install equipment in areas of excessive moisture.
Do not use this equipment for other than intended use.
Do not attempt to service battery. Contact manufacturer for
information on service.
This product is for use with most 20W through 40W single pin
or bipin fluorescent lamps, including standard, energy saving,
circline, U-shaped, and most 26W-39W rapid-start (4pin), long
compact fluorescent lamps.
An unswitched AC power source is required. (120 or 277 VAC)
The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
This emergency ballast is for factory or field installation in
either the ballast channel or on top of the fixture.
To reduce the risk of electrical shock, disconnect both normal
and emergency power supplies before servicing by discon-
necting all AC inputs to the fixture and by disconnecting the
battery.
SAVE THESE INSTRUCTIONS
INSTALLATION INSTRUCTIONS
WARNING
To prevent high voltage from being present on red and
yellow output leads prior to installation, battery connector must
be open. Do not join battery connector until installation is
complete and AC power is supplied to the emergency ballast.
NOTE: Make sure that the necessary branch circuit
wiring is available. An unswitched source of power is required.
The emergency ballast must be fed from the same branch cir-
cuit as the AC ballast.
1. Disconnect AC power from the fixture. Remove the
ballast channel cover and install the emergency ballast either
in the ballast channel (see illustrations 1&2) or on top of the fix-
ture. *(See illustration 3).
2. Select the appropriate wiring diagram to
connect the emergency ballast to the AC ballast and lamp.
Make sure all connections are in accordance with the National
Electrical Code and any local regulations.
EMERGENCY FLUORESCENT
LIGHTING BALLAST
INSTALLATION AND OPERATING
INSTRUCTIONS
CONTAINS NICKEL-CADMIUM
RECHARGEABLE BATTERY.
MUST BE RECYCLED OR
DISPOSED OF PROPERLY.
UL
LISTED
LISTED
Ni - Cd
BALLAST CHANNEL
COVER
TEST SWITCH
CHARGING INDICATOR
LIGHT
EMERGENCY
BALLAST
ILLUSTRATION 1
PAGE 1 Item No. 00418I
®
Worldwide 4 LLC
D450
BY

D450 EMERGENCY FLUORESCENT LIGHTING BALLAST
WIRE BUNDLE COVER
EMERGENCY
BALLAST
1/2" STD KNOCKOUT
7/8" HOLE W/BUSHING
DRILL 1/8"
HOLE FOR
MOUNTING
SCREWS
ILLUSTRATION 3
3. Install the test switch through the ballast channel cover
of a troffer or through the side of a strip fix- ture. Drill a 1/2”
hole and install the switch as shown. (See illustrations 1,2,&
3). Wire the test switch so that it removes AC power from
both the emergency ballast and the AC ballast at the same
time. (See illustration 5).
4. Refer to illustration 6 and install the charging indicator light
so that it will be visible after the fixture is installed.
NOTE:
After installing the charging indicator light and test switch,
mark each with the appropriate label. If a detached charging
indicator light is used, connect by matching wire colors and
install as shown in Illustration 6.
5. In a readily visible location, attach the label “Caution-This
Unit Has more Than one Power Connection Point. To
Reduce The Risk Of Electric Shock, Disconnect Both The
Branch Circuit Or Fuses And Emergency Power Supplies
Before Servicing.”
TROFFER STYLE FIXTURE
EMERGENCY
BALLAST
BALLAST
CHANNEL
COVER
7/8 " PUNCH
PLASTIC TUBING
(PLEASE CUT TO
NECESSARY
LENGTH)
CHARGING INDICATOR LIGHT FIXTURE LENS
LEADS TO CHARGING
INDICATOR LIGHT
7/8" BUSHING
INSERTED INTO
BALLAST CHANNEL COVER
1/2" WHITE BUSHING
TO HOLD CHARGING
INDICATOR LIGHT
STRIP STYLE FIXTURE
FIXTURE FIXTURE
INDICATOR
LIGHT
INDICATOR
LIGHT
1/2" WHITE
BUSHING 1/2" WHITE
BUSHING
VIOLET(+)
BROWN(-)
5/8" BLACK
BUSHING
5/8" BLACK
BUSHING
1/2" PUNCH
VIOLET(+)
BROWN(-)
HOT BLACK BLACK BLACK
BLACK 120V
WHITE
WHITE
ORANGE 277V
(CAP UNUSED LEAD)
COMMON
OR
AC
BALLAST
EMERGENCY
BALLAST
TEST
SWITCH
TEST
UNSWITCHED FIXTURE
HOT BLACK
TEST
SWITCH
BLACK BLACK
TEST WALL SWITCH WHITE
WHITE
COMMON
BLACK 120V
ORANGE 277V
(CAP UNUSED LEAD)
AC
BALLAST
EMERGENCY
BALLAST
OR
SWITCHED FIXTURE
ILLUSTRATION 6
ILLUSTRATION 5
TEST
SWITCH
CHARGING INDICATOR
LIGHT
EMERGENCY BALLAST
ILLUSTRATION 2
PAGE 2 Item No. 00418I
Momentary Test Switch
FIXTURE
TEST BUTTON
HEX NUT
LEADS
TEST SWITCH
HEX NUT
ILLUSTRATION 4

NOTE: After installing the charging indicator light and
test switch, mark each with appropriate label.
6. After installation is complete, supply AC power to the
emergency ballast and join the battery connector.
7. A short-term discharge test may be conducted after the
emergency ballast has been charging for one hour. Charge
for 24 hours before conducting a long-term discharge test.
Refer to OPERATION.
OPERATION
When AC power is applied, the charging indicator
light is illuminated, indicating that the battery is being
charged. When power fails, the emergency ballast automat-
ically switches to emergency power, operating 17W-40W
lamps at reduced illumination for at least 90 minutes
MAINTENANCE
Although no routine maintenance is required to keep the
emergency ballast functional, it should be checked peridical-
ly to ensure that it is working. The following schedule is rec-
ommended:
1. Visually inspect the charging indicator light monthly. It
should be illuminated.
2. Test the emergency operation of the fixture at 30-day
intervals for a minimum of 30 seconds. One lamp should
operate at reduced illumination.
3. Conduct a 90-minute dischare test once a year, either on
or two lamps should operate at reduced illumination for at
least 90 minutes.
D450 EMERGENCY FLUORESCENT LIGHTING BALLAST
LINE BLACK
WHITE
BLUE BLUE
BLUE/WHITE
YEL/GREEN
YELLOW
RED
BLUE
RED
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
AC
BALLAST
EMERGENCY LAMP
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
A. ONE (1) LAMP RAPID START BALLAST
LINE BLACK
WHITE
BLUE BLUE
BLUE/WHITE
YEL/GREEN
YELLOW
RED
BLUE
RED
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
AC
BALLAST
LAMP 1
LAMP 2 (EMERGENCY)
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
B. TWO (2) LAMP RAPID START BALLAST
YELLOW
YELLOW
WIRING DIAGRAMS
PAGE 3 Item No. 00418I

D450 EMERGENCY FLUORESCENT LIGHTING BALLAST
WIRING DIAGRAMS
LINE
BLACK
WHITE
BLUE
OR
RED
BLUE
BLUE/WHITE
YEL/GREEN
YELLOW
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
1 LAMP
INSTANT START
BALLAST
LAMP
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
C. ONE (1) LAMP INSTANT START SLIMLINE BALLAST
LINE BLACK
WHITE BLUE BLUE
BLUE/WHITE
YEL/GREEN
YELLOW
RED
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
AC
BALLAST
LAMP 1
LAMP 2 (EMERGENCY)
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
D. TWO (2) LAMP LEAD/LAG INSTANT START
SLIMLINE BALLAST
LINE
BLACK
WHITE BLUE BLUE
BLUE/WHITE
YEL/GREEN
YELLOW
RED
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
AC
BALLAST
LAMP 1
LAMP 2 (EMERGENCY)
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
E. TWO (2) LAMP SERIES SEQUENCE INSTANT START
BALLAST WITH FOUR (4) LEADS
PAGE 4 Item No. 00418I

D450 EMERGENCY FLUORESCENT LIGHTING BALLAST
WIRING DIAGRAMS
LINE BLACK
WHITE BLUE BLUE
BLUE/WHITE
YEL/GREEN
YELLOW
RED
BLUE
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
AC
BALLAST
LAMP 1
LAMP 2 (EMERGENCY)
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
F. TWO (2) LAMP INSTANT START ELECTRONIC BALLAST
LINE BLACK
WHITE
BLUE
BLUE
BLUE/WHITE
YEL/GREEN
YELLOW
RED
RED
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
AC
BALLAST
LAMP
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
G. ONE (1) LAMP CIRCLINE RAPID START BALLAST
LINE BLACK
BLUE
WHITE
BLUE
BLUE
BLUE/WHITE
YEL/GREEN
YELLOW
RED
RED
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
AC
BALLAST
LAMP 2
(EMERGENCY)
LAMP 1
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
H. TWO (2) LAMP CIRCLINE RAPID START BALLAST
WHITE
WHITE
RED
RED
PAGE 5 Item No. 00418I

D450 EMERGENCY FLUORESCENT LIGHTING BALLAST
WIRING DIAGRAMS
LINE BLACK
WHITE
BLUE BLUE
BLUE/WHITE
BLUE/WHITE
BLUE/WHITE YEL/GREEN
YELLOW
YELLOW
YELLOW
RED
BLUE
RED
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
AC
BALLAST
LAMP 1
LAMP 2
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
I. THREE (3) LAMP RAPID START ELECTRONIC BALLAST
LAMP 3 (EMERGENCY)
LINE BLACK
WHITE
BLUE BLUE
BLUE/WHITE
YEL/GREEN
YELLOW
RED
BLUE
RED
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
AC
BALLAST
LAMP
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
J. FOUR (4) LAMP INSTANT START ELECTRONIC BALLAST
LAMP
LAMP
LAMP (EMERGENCY)
YELLOW
YELLOW
BLUE
BLUE/WHITE
YEL/GREEN
YELLOW
RED
ORANGE
BLACK
WHITE
VIOLET+
BROWN-
RED WHITE
BATTERY CONNECTOR
277V
120V
COM
INDICATOR
LIGHT
EMERGENCY
BALLAST
LAMP
TO UNSWITCHED AC
USE PROPER TAP
INSULATE USED LEADS
K. ONE (1) WITHOUT AC BALLAST
CAP
CAP
EMERGENCY ONLY FIXTURES
PAGE 6 Item No. 00418I