Danfoss EPS VLT User manual

MAKING MODERN LIVING POSSIBLE
Quick Reference Guide
VLT®HVAC Drive

*
91 (L1)
92 (L2)
93 (L3)
PE
88 (-)
89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24V OUT)
13 (+24V OUT)
18 (D IN)
20 (COM D IN)
15mA 200mA
(U) 96
(V) 97
(W) 98
(PE) 99
(COM A OUT) 39
(A OUT) 42 0/4-20 mA
03
0-10Vdc
+10Vdc
0-10Vdc
0/4-20 mA
240Vac, 2A
24Vdc
02
01
05
04
06 240Vac, 2A
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
19 (D IN)
24V (NPN)
0V (PNP)
27
24V
0V
(D IN/OUT)
0V (PNP)
24V (NPN)
(D IN/OUT)
0V
24V
29
24V (NPN)
0V (PNP)
0V (PNP)
24V (NPN)
33 (D IN)
32 (D IN)
1 2
ON
S201
ON
21
S202
ON=0-20mA
OFF=0-10V
95
400Vac, 2A
P 5-00
(R+) 82
(R-) 81
37 (D IN)
+ - + -
130BA544.11
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0V
5V
S801
RS-485
RS-485
21
ON
S801
3 Phase
power
input
DC bus Switch Mode
Power Supply
Motor
Analog Output
Interface
relay1
relay2
ON=Terminated
OFF=Open
Brake
resistor
(NPN) = Sink
(PNP) = Source
Illustration 2.1 Diagram showing all electrical terminals. (Terminal 37 present for units with Safe Stop Function only.)
VLT®HVAC Drive Quick Reference Guide

2 How to Programme
2.1 Local Control Panel
2.1.1 How to Operate Graphical LCP (GLCP)
The following instructions are valid for the GLCP (LCP 102).
The GLCP is divided into four functional groups
1. Graphical display with Status lines.
2. Menu keys and indicator lights (LEDs) - selecting
mode, changing parameters and switching
between display functions.
3. Navigation keys and indicator lights (LEDs).
4. Operation keys and indicator lights (LEDs).
Graphical display
The LCD-display is back-lit with a total of 6 alpha-numeric
lines. All data is displayed on the LCP which can show up
to five operating variables while in [Status] mode.
Display lines
a. Status line Status messages displaying icons and
graphics.
b. Line 1-2Operator data lines displaying data and
variables defined or chosen by the user. By
pressing the [Status] key, up to one extra line can
be added.
c. Status line Status messages displaying text.
Auto
on Reset
Hand
on O
Status Quick
Menu
Main
Menu
Alarm
Log
Back
Cancel
Info
OK
Status 1(0)
1234rpm 10,4A 43,5Hz
Run OK
43,5Hz
On
Alarm
Warn.
130BA018.13
1
2
3
4
b
a
c
Illustration 2.1
The display is divided into 3 sections
Top section (a) shows the status when in status mode or
up to 2 variables when not in status mode and in the case
of Alarm/Warning.
The number of the Active Set-up (selected as the Active
Set-up in 0-10 Active Set-up) is shown. When programming
in another Set-up than the Active Set-up, the number of
the Set-up being programmed appears to the right in
brackets.
The Middle section (b) shows up to 5 variables with related
unit, regardless of status. In case of alarm/warning, the
warning is shown instead of the variables.
VLT®HVAC Drive Quick Reference Guide

5.5.1 Quick Menu Structure
Q3-1 General Settings 0-24 Display Line 3 Large 1-00 Configuration Mode Q3-31 Single Zone Ext. Set Point 20-70 Closed Loop Type
Q3-10 Adv. Motor Settings 0-37 Display Text 1 20-12 Reference/Feedback Unit 1-00 Configuration Mode 20-71 PID Performance
1-90 Motor Thermal Protection 0-38 Display Text 2 20-13 Minimum Reference/Feedb. 20-12 Reference/Feedback Unit 20-72 PID Output Change
1-93 Thermistor Source 0-39 Display Text 3 20-14 Maximum Reference/Feedb. 20-13 Minimum Reference/Feedb. 20-73 Minimum Feedback Level
1-29 Automatic Motor Adaptation
(AMA)
Q3-2 Open Loop Settings 6-22 Terminal 54 Low Current 20-14 Maximum Reference/Feedb. 20-74 Maximum Feedback Level
14-01 Switching Frequency Q3-20 Digital Reference 6-24 Terminal 54 Low Ref./Feedb.
Value
6-10 Terminal 53 Low Voltage 20-79 PID Autotuning
4-53 Warning Speed High 3-02 Minimum Reference 6-25 Terminal 54 High Ref./Feedb.
Value
6-11 Terminal 53 High Voltage Q3-32 Multi Zone / Adv
Q3-11 Analog Output 3-03 Maximum Reference 6-26 Terminal 54 Filter Time
Constant
6-12 Terminal 53 Low Current 1-00 Configuration Mode
6-50 Terminal 42 Output 3-10 Preset Reference 6-27 Terminal 54 Live Zero 6-13 Terminal 53 High Current 3-15 Reference 1 Source
6-51 Terminal 42 Output Min Scale 5-13 Terminal 29 Digital Input 6-00 Live Zero Timeout Time 6-14 Terminal 53 Low Ref./Feedb. Value 3-16 Reference 2 Source
6-52 Terminal 42 Output Max Scale 5-14 Terminal 32 Digital Input 6-01 Live Zero Timeout Function 6-15 Terminal 53 High Ref./Feedb.
Value
20-00 Feedback 1 Source
Q3-12 Clock Settings 5-15 Terminal 33 Digital Input 20-21 Setpoint 1 6-22 Terminal 54 Low Current 20-01 Feedback 1 Conversion
0-70 Date and Time Q3-21 Analog Reference 20-81 PID Normal/ Inverse Control 6-24 Terminal 54 Low Ref./Feedb. Value 20-02 Feedback 1 Source Unit
0-71 Date Format 3-02 Minimum Reference 20-82 PID Start Speed [RPM] 6-25 Terminal 54 High Ref./Feedb.
Value
20-03 Feedback 2 Source
0-72 Time Format 3-03 Maximum Reference 20-83 PID Start Speed [Hz] 6-26 Terminal 54 Filter Time Constant 20-04 Feedback 2 Conversion
0-74 DST/Summertime 6-10 Terminal 53 Low Voltage 20-93 PID Proportional Gain 6-27 Terminal 54 Live Zero 20-05 Feedback 2 Source Unit
0-76 DST/Summertime Start 6-11 Terminal 53 High Voltage 20-94 PID Integral Time 6-00 Live Zero Timeout Time 20-06 Feedback 3 Source
0-77 DST/Summertime End 6-12 Terminal 53 Low Current 20-70 Closed Loop Type 6-01 Live Zero Timeout Function 20-07 Feedback 3 Conversion
Q3-13 Display Settings 6-13 Terminal 53 High Current 20-71 PID Performance 20-81 PID Normal/ Inverse Control 20-08 Feedback 3 Source Unit
0-20 Display Line 1.1 Small 6-14 Terminal 53 Low Ref./Feedb.
Value
20-72 PID Output Change 20-82 PID Start Speed [RPM] 20-12 Reference/Feedback Unit
0-21 Display Line 1.2 Small 6-15 Terminal 53 High Ref./Feedb.
Value
20-73 Minimum Feedback Level 20-83 PID Start Speed [Hz] 20-13 Minimum Reference/Feedb.
0-22 Display Line 1.3 Small Q3-3 Closed Loop Settings 20-74 Maximum Feedback Level 20-93 PID Proportional Gain 20-14 Maximum Reference/Feedb.
0-23 Display Line 2 Large Q3-30 Single Zone Int. Set Point 20-79 PID Autotuning 20-94 PID Integral Time 6-10 Terminal 53 Low Voltage
VLT®HVAC Drive Quick ReferenceGuide

6-11 Terminal 53 High Voltage 20-21 Setpoint 1 22-22 Low Speed Detection 22-21 Low Power Detection 22-87 Pressure at No-Flow Speed
6-12 Terminal 53 Low Current 20-22 Setpoint 2 22-23 No-Flow Function 22-22 Low Speed Detection 22-88 Pressure at Rated Speed
6-13 Terminal 53 High Current 20-81 PID Normal/ Inverse Control 22-24 No-Flow Delay 22-23 No-Flow Function 22-89 Flow at Design Point
6-14 Terminal 53 Low Ref./Feedb.
Value
20-82 PID Start Speed [RPM] 22-40 Minimum Run Time 22-24 No-Flow Delay 22-90 Flow at Rated Speed
6-15 Terminal 53 High Ref./Feedb.
Value
20-83 PID Start Speed [Hz] 22-41 Minimum Sleep Time 22-40 Minimum Run Time 1-03 Torque Characteristics
6-16 Terminal 53 Filter Time Constant 20-93 PID Proportional Gain 22-42 Wake-up Speed [RPM] 22-41 Minimum Sleep Time 1-73 Flying Start
6-17 Terminal 53 Live Zero 20-94 PID Integral Time 22-43 Wake-up Speed [Hz] 22-42 Wake-up Speed [RPM] Q3-42 Compressor Functions
6-20 Terminal 54 Low Voltage 20-70 Closed Loop Type 22-44 Wake-up Ref./FB Difference 22-43 Wake-up Speed [Hz] 1-03 Torque Characteristics
6-21 Terminal 54 High Voltage 20-71 PID Performance 22-45 Setpoint Boost 22-44 Wake-up Ref./FB Difference 1-71 Start Delay
6-22 Terminal 54 Low Current 20-72 PID Output Change 22-46 Maximum Boost Time 22-45 Setpoint Boost 22-75 Short Cycle Protection
6-23 Terminal 54 High Current 20-73 Minimum Feedback Level 2-10 Brake Function 22-46 Maximum Boost Time 22-76 Interval between Starts
6-24 Terminal 54 Low Ref./Feedb.
Value
20-74 Maximum Feedback Level 2-16 AC brake Max. Current 22-26 Dry Pump Function 22-77 Minimum Run Time
6-25 Terminal 54 High Ref./Feedb.
Value
20-79 PID Autotuning 2-17 Over-voltage Control 22-27 Dry Pump Delay 5-01 Terminal 27 Mode
6-26 Terminal 54 Filter Time Constant Q3-4 Application Settings 1-73 Flying Start 22-80 Flow Compensation 5-02 Terminal 29 Mode
6-27 Terminal 54 Live Zero Q3-40 Fan Functions 1-71 Start Delay 22-81 Square-linear Curve Approxi-
mation
5-12 Terminal 27 Digital Input
6-00 Live Zero Timeout Time 22-60 Broken Belt Function 1-80 Function at Stop 22-82 Work Point Calculation 5-13 Terminal 29 Digital Input
6-01 Live Zero Timeout Function 22-61 Broken Belt Torque 2-00 DC Hold/Preheat Current 22-83 Speed at No-Flow [RPM] 5-40 Function Relay
4-56 Warning Feedback Low 22-62 Broken Belt Delay 4-10 Motor Speed Direction 22-84 Speed at No-Flow [Hz] 1-73 Flying Start
4-57 Warning Feedback High 4-64 Semi-Auto Bypass Set-up Q3-41 Pump Functions 22-85 Speed at Design Point [RPM] 1-86 Trip Speed Low [RPM]
20-20 Feedback Function 1-03 Torque Characteristics 22-20 Low Power Auto Set-up 22-86 Speed at Design Point [Hz] 1-87 Trip Speed Low [Hz]
VLT®HVAC Drive Quick Reference Guide
Table of contents
Other Danfoss Air Conditioner Accessories manuals
Popular Air Conditioner Accessories manuals by other brands

Mitsubishi Electric
Mitsubishi Electric PAC-SNH11HS-E installation manual

Unitary products group
Unitary products group 2CE Series installation instructions

Qlima
Qlima EU-ODZ104 user manual

Tecnosystemi
Tecnosystemi smart clima SCD500163 user manual

Waeco
Waeco AirCon Service Center ASC 5300 G operating manual

American Standard
American Standard BAYSQRD001AA Installer's guide

Bimar
Bimar AP11 Instruction booklet

Mitsubishi
Mitsubishi PAC-SJ41TM-E installation manual

Tecnosystemi
Tecnosystemi Smart Clima SCD500084 user manual

Samsung
Samsung MIM-H04U User & installation manual

Waeco
Waeco AirConServiceCenter ASC 3500 G LE operating manual

Fujitsu
Fujitsu UTZ-KXGC installation manual