Danfoss KP 15 User manual

Pressure Controls
KP 15, KP 17W, KP 17B, KP 25
©Danfoss A/S RI5AK222 - 520H0146
060R9747
060R9747
Instructions
Types
The controls can be used with CFC, HFC, HCFC refrigerants.
CAUTION: Do not install these controls on
ammonia systems
KP 15 man. (LP) / man. (HP) reset KP 15, KP 17B auto. (LP) / man. (HP) reset KP 15, KP 17W, KP 25 auto. (LP) / auto (HP) reset
Ambient temperatures Test pressure (pTEST)
ptest max.
505 psig
(35 bar pe)
ptest max.
285 psig
(20 bar pe)
t1min. KP 15, KP 25: –40°F (–40°C)
KP 17W, KP 17B: –13°F (–25°C)
t1max. 150°F (65°C)
CAUTION: Do not mount the control in a position where dirt, sediment,
or oil will affect the operation of the control.
Enclosure
CAUTION: The mounting panel must be plane to avoid damage of control.
2 RI5AK222 - 520H0146
Connections
Wiring
CAUTION: Disconnect power supply before
wiring connections are made to avoid possible
electrical shock or damage to equipment.
All wiring should conform to the National
Electrical Code and local regulations.
SPDT
Controls with low pressure (LP) signal
Terminal block
CAUTION: Use terminal screws furnished in the
contact block.
Use tightening torque 20 lb. in (2.3 Nm).
Use copper wire only.
Low pressure (LP) side:
A-C close on LP rise
A-C open on LP drop
High pressure (HP) side.
A-C open on HP rise
A-C close on HP drop
LP signal option:
A-B close on LP drop
See label for current wiring inside cover
Controls with low pressure (LP) and high
pressure (HP) signal)
KP 15 and KP 17W. Only code nos.:
060-2024060-2027 060-2030
060-2026060-2029 060-2031
(stamped on top of control)
Terminal block
CAUTION: Use terminal screws furnished in
the contact block.
Use tightening torque 20 lb. in (2.3 Nm).
Use copper wire only.
Low pressure (LP) side:
A-C close on LP rise
A-C open on LP drop
High pressure (HP) side.
A-C open on HP rise
A-C close on HP drop
LP signal option:
A-B close on LP drop
HP signal option:
A-D close on HP rise
Contact load ratings
See label inside cover
Function
Note!
M= Load
x= Signal option
= Bellows movement on pressure rise
¬ = Bellows movement on pressure
drop
120 V a.c. 16 FLA, 96 LRA
240 V a.c. 8 FLA, 48 LRA
240 V d.c. 12 W pilot duty
RI5AK222 - 520H0146 3
Manual tripping
(Electrical contacts/wiring test)
LP side HP side
TRIP
use FINGERS
ONLY!
(Do NOT use
screwdriver)
Note:
On controls with LP and/or HP man. reset, push
corresponding LP and/or HP man. reset knob during
tripping.
Manual tripping
To resume control operation after safety cut-
out, push man. reset knob as indicated.
Note:
LP man. reset is possible only after system
pressure has risen above cut-in value.
HP man. reset is possible only after system
pressure has dropped below cut-out value.
Convertible reset
KP 15, code nos.: 060-2025, 060-2028
Reset options
Turn plate to desired LP man. LP-auto. LP-auto. LP-man.
reset configuration HP-man. HP-man. HP-auto. HP-auto.
Adjustment spindle(s) location
KP 15 KP 15, KP 17B KP 15, KP 17W, KP 25
A. MAN./MAN. RESET B. AUTO/MAN. RESET C. AUTO./AUTO. RESET
4 RI5AK222 - 520H0146
©Danfoss A/S IC-MC/mr 02-2005
Setting
Low pressure (LP) side setting High pressure (HP) side setting
KP 15, KP 17W, KP 17B and KP 25 KP 15 with LP man. reset only KP 15, KP 17W, KP 17B and KP 25
with LP auto. reset only KP 15 with convertible LP auto.) with HP auto. or man. reset
man. reset
LP LP
scale scale
1. Adjust range spindle to 1. Adjust range spindle to 1. Adjust range spindle to
desired CUT-IN value. desired CUT-OUT value. desired CUT-OUT value.
2. Adjust differential 2. DIFFRENTIAL (DIFF.) 2. DIFFERENTIAL (DIFF.)
spindle to desired is fixed. is fixed.
DIFFERENTIAL Value printed on Value printed on
(DIFF.) value. scale plate. scale plate.
CUT-IN minus DIFFERENTIAL equals CUT-IN equals CUT-OUT plus CUT-OUT minus DIFFERENTIAL equals
CUT-OUT DIFFERENTIAL CUT-IN
Example: Example: Example:
CUT-IN – DIFF. = CUT-OUT CUT-OUT + DIFF. = CUT-IN CUT-OUT – DIFF. = CUT-IN
30 psig – 10 psi = 20 psig 12 psig + 10 psi = 22 psig 203 psig – 58 psi = 145 psig
(2.1 bar) (0.7 bar) (1.4 bar) (0.8 bar) (0.7 bar) (1.5 bar) (14 bar) (4 bar) (10 bar)
Adjustment
Note:
Remove lockplate before adjustment.
Replace lockplate after adjustment (if desired).
KP 15:
10 psi (0.7 bar)/rev
KP 25:
7 psi (0.5 bar)/rev
KP 15:
2 psi (0.15 bar)/rev
KP 25:
1.5 psi (0.1 bar)/rev

This manual suits for next models

3

Other Danfoss Control Unit manuals

Danfoss EV220BW 15-50 User manual

Danfoss

Danfoss EV220BW 15-50 User manual

Danfoss SVA-S User manual

Danfoss

Danfoss SVA-S User manual

Danfoss PVG 32 Manual

Danfoss

Danfoss PVG 32 Manual

Danfoss EVR 2 User manual

Danfoss

Danfoss EVR 2 User manual

Danfoss AFQM User manual

Danfoss

Danfoss AFQM User manual

Danfoss VX Solo II Series User manual

Danfoss

Danfoss VX Solo II Series User manual

Danfoss SFV Series User manual

Danfoss

Danfoss SFV Series User manual

Danfoss ASV-I User manual

Danfoss

Danfoss ASV-I User manual

Danfoss CHV-X 15-125 User manual

Danfoss

Danfoss CHV-X 15-125 User manual

Danfoss GBC 6s H User manual

Danfoss

Danfoss GBC 6s H User manual

Danfoss VHX-DUO Installation instructions manual

Danfoss

Danfoss VHX-DUO Installation instructions manual

Danfoss AV210 NC/NF User manual

Danfoss

Danfoss AV210 NC/NF User manual

Danfoss ESMD User manual

Danfoss

Danfoss ESMD User manual

Danfoss EVR 2 User manual

Danfoss

Danfoss EVR 2 User manual

Danfoss TCBE User manual

Danfoss

Danfoss TCBE User manual

Danfoss VLT MCD 200 User manual

Danfoss

Danfoss VLT MCD 200 User manual

Danfoss VMV 15 User manual

Danfoss

Danfoss VMV 15 User manual

Danfoss ICF 15 User manual

Danfoss

Danfoss ICF 15 User manual

Danfoss TWA-Z Gen. 2011 User manual

Danfoss

Danfoss TWA-Z Gen. 2011 User manual

Danfoss OPTYMA User manual

Danfoss

Danfoss OPTYMA User manual

Danfoss PN 16 User manual

Danfoss

Danfoss PN 16 User manual

Danfoss MSV-I User manual

Danfoss

Danfoss MSV-I User manual

Danfoss TUA User manual

Danfoss

Danfoss TUA User manual

Danfoss HPV User manual

Danfoss

Danfoss HPV User manual

Popular Control Unit manuals by other brands

Dungs DMK 5040 Operation and assembly instructions

Dungs

Dungs DMK 5040 Operation and assembly instructions

TP-Link kasa smart KE100 quick start guide

TP-Link

TP-Link kasa smart KE100 quick start guide

Areva MiCOM C232 Technical manual

Areva

Areva MiCOM C232 Technical manual

Quectel Smart Wi-Fi Module Series user manual

Quectel

Quectel Smart Wi-Fi Module Series user manual

Copley Controls XenusPlus EtherCAT manual

Copley Controls

Copley Controls XenusPlus EtherCAT manual

Waeco MagicTouch MT2000 installation manual

Waeco

Waeco MagicTouch MT2000 installation manual

Sony HDCU-1700 Operation manual

Sony

Sony HDCU-1700 Operation manual

Isenberg TVH.2691 installation manual

Isenberg

Isenberg TVH.2691 installation manual

Tektronix ECO8000 Series user manual

Tektronix

Tektronix ECO8000 Series user manual

ARAG IBX100 4679004 Installation - use - maintenance

ARAG

ARAG IBX100 4679004 Installation - use - maintenance

ElectroDacus SBMS100 user manual

ElectroDacus

ElectroDacus SBMS100 user manual

iO HVAC Controls ZP3-HPS-ESP Installation and operation instructions

iO HVAC Controls

iO HVAC Controls ZP3-HPS-ESP Installation and operation instructions

Grundfos OHJEET CIM 500 manual

Grundfos

Grundfos OHJEET CIM 500 manual

National Instruments 9861 Getting started guide

National Instruments

National Instruments 9861 Getting started guide

Quectel EC200A Series Hardware design

Quectel

Quectel EC200A Series Hardware design

Siemens SIMOTION D4 5-2 Series manual

Siemens

Siemens SIMOTION D4 5-2 Series manual

Johnson Controls GS Series manual

Johnson Controls

Johnson Controls GS Series manual

schmersal AES 1185 operating instructions

schmersal

schmersal AES 1185 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.