4
VD.KH.C6.02 © Danfoss 01/2014
SMT/SI
Reset
Data sheet Actuators for modulating control AME 110 NL, AME 120 NL
DIP Switch Setting
(for service purposes only)
TheactuatorhasafunctionselectionDIPswitch
under the removable cover.
Theswitchprovidesthefollowingfunctions:
• SW1:
U/I - Input signal type selector
IfsettoOFFposition,voltageinputis
selected. If set to ON position, current input is
selected.
• SW2:
0/2 - Input signal range selector
IfsettoOFFposition,theinputsignalisin
the range from 2-10 V (voltage input) or from
4-20 mA (current input). If set to ON position,
the input signal is in the range from 0-10
V (voltage input) or from 0-20 mA (current
input).
• SW3:
D/I - Direct or inverse acting selector
IfsettoOFFposition,theactuatorisdirect
acting (stem contracts as voltage increases). If
the actuator is set to ON position, the actuator
is inverse acting (stem extracts as voltage
increases).
• SW4:
---/Seq - Normal or sequential mode
selector
IfsettoOFFposition,theactuatorisworking
in the range 0(2)-10 V or 0(4)-20 mA. If set
toONposition,theactuatorisworkingin
sequentialrange;0(2)-5(6)Vor
(0(4-0(12) mA) or (5(6)-10 V) or
(10(12)-20 mA).
• SW5:
0-5/5-10 V - Input signal range in
sequential mode
IfsettoOFFposition,theactuatorisworking
inthesequentialrange0(2)
-
5(6) V or
0(4)
-
10(12) mA.
If set to ON position, the
actuatorisworkinginthesequentialrange;
5(6)-10 V or 10(12)-20 mA.
• SW6:
LIN/LOG - Linear or equal percentage flow
through valve selector
If set to ON position, the flow through the
valveisequalpercentage-wiseequalsthe
controlsignal.IfsettoOFFposition,thevalve
position is linear acc. to the control signal.
• SW7:
---/ASTK
- Anti-blocking function
Exercisesthevalvetoavoidblockingin
periodswhentheheating/coolingiso.
IfsettoONposition(ASTK),thevalvemotion
is switched on. The actuator opens and closes
the valve every 7 days.
IfsettoOFFposition(---),thefunctionis
disabled.
• SW8:
Reset switch and reset button on PCB
Changing this switch position will cause the
actuatortogothroughaselfstrokingcycle.
Note: Reset switch and reset button on
PCBhave the same function. The reset
switchmustbeinOFFpositiontomake
reset
button function active ( press it for 2 sec. ).
Remark:
Factory setting: All switches (except switch 2 which is in ON position) are in OFF positions.
I
0-10
INV
SEQ
5-10
LOG
ASTX
RESET
ON
OFF
U
2-10
DIR
---
0-5
LIN
---
RESET