4 Menu operation RC8CE202 © Danfoss 03/2013 AK-PC 781 Version 4.1x
Main settings
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. ctrl. temp °C Actual temperature for control sensor (Po or S4)
Comp. ctrl. ref. °C Actual reference temp. for compressor capacity
(incl. external reference signal, if any)
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Compr. Cap % Reference for compressor capacity (deviations may be due to time delays)
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Ss Suction gas °C Actual suction gas temperature
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external contributions, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Pc Bar Condensing pressure (measured with the pressure transmitter)
Tc °C Condensing pressure in °C. (measured with the pressure transmitter)
Gc status Actual gas cooler operation:
0=O. 1=Standby. 2=Max COP operation. 3=Heat recovery. 4=Extra capacity.
5=Manual control.
Pgc Bar Actual gas cooler pressure
Pgc reference bar Actual reference for gas cooler pressure
Sd discharge gas °C Actual discharge gas temperature
Sgc °C Actual temperature at outlet from the gas cooler
External Main Switch Status of input “Extern Main Switch”. In pos.“OFF”the regulation is stopped by force
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Conguration lock Lock of conguration.
In order to select quick setup or select refrigerant type, the conguration lock must
be “open”. Note: ”Main switch”must be OFF in order to set conguration lock in “open”
position
0: Open
1: Locked
Refrigerant type Po Select refrigerant type
0= not selected, 1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1.
8=R23. 9=R500. 10=R503. 11=R114. 12=R142b. 13=User dened 14=R32. 15=R227.
16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B.
23=R410A. 24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A.
31=R422A. 32=R413A. 33=R422D. 34=R427A. 35=R438A. 36=XP10. 37=R407F.
Suction capacity control
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. ctrl. temp °C Actual temperature for control sensor (Po or S4)
Comp. ctrl. ref. °C Actual reference temp. for compressor capacity
(incl. external reference signal, if any)
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Compr. Cap % Reference for compressor capacity (deviations may be due to time delays)
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Ss Suction gas °C Actual suction gas temperature
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external contributions, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Pc Bar Condensing pressure (measured with the pressure transmitter)
Tc °C Condensing pressure in °C. (measured with the pressure transmitter)
Gc status Actual gas cooler operation:
0=O. 1=Standby. 2=Max COP operation. 3=Heat recovery. 4=Extra capacity.
5=Manual control.
Pgc Bar Actual gas cooler pressure
Pgc reference Bar Actual reference for gas cooler pressure
Sd discharge gas °C Actual discharge gas temperature
Sgc °C Actual temperature at outlet from the gas cooler
MC dP0 oset K Actual displacement value for the suction pressure in connection with a “P0
Optimiser” function (Master control function in AKA gateway)