RampX5-X6(TemperaturerampingfromtimeX5
toX6
RampX7-X8(TemperaturerampingfromtimeX7
toX8
10903
10904
Settingthenumberofstepsforthechangeofthedesiredflow
temperatureinselectedperiod.
OFF:Thestepwisechangeisdisabled
Value:Theperiodisdividedinthenumberofsteps
Example:
"X5"timeissetto100
"X5"temperatureissetto25°
"X6"timeissetto150
"X6"temperatureissetto35°
"RampX5-X6"issetto5
Result:
PeriodbetweenX5andX6is50hours.Temperaturechangeis10K.
Theprocesswillbe:
Starttemperature:25°,after10hoursthetemperaturechanges
to27°.Afterfurther10hoursthetemperaturechangesto29°
andsoon.
Appl.continue(Applicationcontinue10912
SelectionhowtheCLComfortcontrollermustcontinueafter
havingfinishedthefloordryingprocess.
OFF:Thedesiredflowtemperaturewillbethevaluesetat
"X8"time
ON:Thecontrollercontinueswiththeselectedapplication
andthesetmodeofthefunctionselector
Whenusingonly"Functionalheating"andnodemandforcontrolafter
thefloordryingprocess,itisimportanttosetthedesiredtemperature
atX8.
(ommoncontroller>MENU>Floordrying>uringheating>
"DesiredflowT">Graph'srightpoint).
Afterpowerfail.(Afterpowerfailure10913
SelectionhowtheCLComfortcontrollermustcontinueaftera
powerfailure(powerhasbeenawayformorethanacceptedtime,
setin"Max.pwr.failure",ID10514).
Ifpowerfailurehappensin"Functionalheating"process,thefloor
dryingcanberestartedaccordingtotimeandtemperaturesetting
forX1orstopped.Ifstopped,thedesiredflowtemperatureis
maintainedatthevalue,setforX1.
Ifpowerfailurehappensin"Curingheating"process,thefloor
dryingcanberestartedaccordingtotimeandtemperaturesetting
forX4.Ifstoppedthedesiredflowtemperatureismaintainedat
thevalue,setforX1.
STOP:Thecontrollerstopsthefloordryingprocessand
maintainsthetemperature,setatX1
START:Thecontrollerstartsthefloordryingprocessfrom
settingsinX1orX4
Torestartthefloordryingprocess:
Iftheparameter"Afterpowerfail. "(ID10913)issettoSTOP ,the
"Prog.execution"mustbesettoOFFandthentoON.
Afterapowerfailure,thealarmisindicated.
Thealarmcanbereset.
10|©Danfoss|2017.08VI.JM.P2.02
ECLComfort210/296/310,Floor(ScreedDryingProgram