EKC 414A Manual RS8CK502 © Danfoss 05-2005 15
Function Para
meter Min. Max. Factory
settings
Normal display
Shows the temperature at the selected
sensor
Define view in O17
-°C
If you wish to see selected defrost stop
temperature, give the lower button a brief
push (1 sec.)
no= stop on temperature not selected
-°C
Thermostat
Differential r01 0.1 K 10.0 K 2.0
Max. limitation of thermostat’s setting
temperature r02 -49°C 50°C 50.0
Min. limitation of thermostat’s setting
temperature r03 -50°C 49°C -50.0
Temperature unit (°C/°F) r05 °C °F 0/°C
Correction of signal from S4 (Sout) r09 -10.0 K 10.0 K 0.0
Correction of signal from S3 (Sin) r10 -10.0 K 10.0 K 0.0
Start/Stop of refrigeration r12 OFF ON OFF
Reference displacement during night opera-
tion r13 -20.0 K 20.0 K 0.0
Define thermostat function
1=ON/OFF, 2=Modulating r14 1 2 1
Definition and weighting, if applicable, of
thermostat sensors
100%=S4 (Sout), 0%=S3 (Sin).
The thermostat temperature can be seen
in U17
r15 0% 100% 100
Time between melt periods r16 0 h 10 h 1
Duration of melt periods r17 0 min 10 min. 5
Alarm
Alarm time delay A03 0 min. 120 min 30
Door alarm time delay A04 0 min. 90 min. 60
Time delay during cooling A12 0 min. 240 min 120
High alarm limit A13 -50°C 50°C 5.0
Low alarm limit A14 -50°C 50°C -30.0
Compressor
Min. ON-time c01 0 min 50 min 0.0
Min. OFF-time c02 0 min 50 min 0.0
Defrost
Defrost stop temperature d02 0 25°C 6.0
Interval between defrost starts d03 OFF 48 h 8
Max. defrost duration d04 0 180 min 45
Time displacement of defrost cut-ins during
start-up d05 0 240 min 0
Drip-off time d06 0 60 min 0
Fan start delay after defrost d07 0 60 min 0
Fan start temperature d08 -15 0°C -5.0
Fan cut-in during defrost (yes/no) d09 no yes no
Defrost sensor
0=S4 (Sout) , 1=S5 (Sdef), 2=non. Stop on time d10 0 2 2
Defrost at power up d13 no yes no
RTC module (if installed)
see RTC instructions
t01 to
t16
Injection control function
Max. value of superheat reference n09 3.0 K 15.0 K 12.0
Min. value of superheat reference n10 3.0 K 10.0 K 3.0
MOP temperature n11 -50.0°C 15°C/off 15°C
AKV valve’s time period
Should only be changed to OFF by trained
staff
n13 3 sec. 6 sec. 6
Adaptive control
Should only be changed to OFF by trained
staff
n14 OFF ON on
Average opening degree
Should only be changed by trained staff n16 10% 75% 30.0
SW: 1.1x
Menu survey
Start-up time for signal reliability
Should only be changed by trained staff. n17 5% 70% 30.0
Stability factor for superheat control.
Changes should only be made by trained
staff
n18 0 10 4
Forced closing.. AKV valve shut in pos. ON n36 OFF ON OFF
Fan
Fan stop on compressor cut out F01 no yes no
Delayed fan stop when compressor is cut out F02 0 min 30 min 0
Safety function. The fan stops if the S5 tem-
perature reaches this value F04 -50.0 50.0/off 50.0
Miscellaneous
Delay of output signal after start-up o01 0 sec. 600 sec 5
Define digital input signal (DI:
OFF=not used, 1=Door alarm, 2=defrost
start, 3=Night operation, 4=External start/
stop, 5 = Coordinated defrost with cable
connections
o02 OFF 5 0
Network address (range = 0-60) o03 0 990 0
ON/OFF switch (service-pin message) o04 OFF ON OFF
Access code o05 OFF 100 OFF
Used sensor type for S3, S4 and S5 (Pt / PTC) o06 Pt Ptc 0/Pt
Set supply voltage frequency o12 50 Hz 60 Hz 50
Define digitalt output signal (DO:
0=not used
Coordinated defrost with cable connections:
1=Master, 2= Slave
o13 0 2 0
Max. standby time after coordinated defrost o16 1 min 30 min 20
Display S4 % (Sout)
0%=S3 (Sin)
100%=S4 (Sout)
o17 0% 100% 100
Manual control of outputs:
OFF=No override
1: Compressor reay is ON
2: Defrost relay is ON
3: Fan relay is ON
4: Alarm relay is OFF
5: DO output is ON
6: AKV output is ON
7: Light relay is ON
When manual control is terminated, the set-
ting must be changed to OFF
o18 OFF 7 OFF
Pressure transmitter working range – min.
value 020 -1 bar 5 bar -1
Pressure transmitter working range – max.
value 021 6 bar 36 bar 12
Inject-ON definition
When the ON input is cut out refrigeration
is stopped.
Here you define how the fan relay and the
alarm function are to act:
1 = Fan relay = ON, alarm monitoring active
2 = Fan relay = OFF, alarm monitoring active
3 = Fan relay = OFF, no alarm monitoring
4 = Fan relay = ON, no alarm monitoring
5 to 8= as 1 to 4, but without connection to
terminal 40-41.
o29 1 8 5
Refrigerant setting
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717.
6=R13. 7=R13b1. 8=R23. 9=R500.
10=R503. 11=R114. 12=R142b. 13=User
defined. 14=R32. 15=R227. 16=R401A.
17=R507. 18=R402A. 19=R404A. 20=R407C.
21=R407A. 22=R407B. 23=R410A. 24=R170.
25=R290. 26=R600. 27=R600a. 28=R744.
29=R1270. 30=R417A
o30 0 30 0