manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Danfoss
  6. •
  7. Controllers
  8. •
  9. Danfoss ERC 213 User manual

Danfoss ERC 213 User manual

© Danfoss | DCS (ADAP-KOOL®) | 2018-11
Quick Start Guide
ERC 213
DKRCE.PD.RL0.A3.02 | 1
Overview
The ERC 213 is designed to be an easy, universal replacement control. We encourage users to employ one of five predefined applications that meet the
needs of most systems. If users need to modify specific parameters, it should be done after installing the predefined application that most closely meets
system needs.
For more information, including detailed instructions, error codes, parameters, and more,
visit www.danfoss.com/erc or download the Koolcode app from iTunes or Google Play.
For a video guide of the quick set-up, visit http://bit.ly/ERC213 or use the QR code located to the right.
STEP Action Screen Display
STEP 1 Wire control, to include power and sensors
STEP 2
Power up control
Energize control
Control turns on, goes through start up,
then shows the current temperature reading
STEP 3
Enter Quick Configuration Menu and Select app
Press ”<”for more than three seconds within one minute of power up to enter Quick Configuration Menu. o61 appears on screen
Press“set” while o61 is on screen AP0 flashes on screen
Select appropriate app using App Selection section below by pressing “ ” or “ ”, then press “set”. o06 appears on screen
STEP 4
Select Sensor
Press“set” while o06 is on screen n10 flashes on screen
If using included sensor, leave default value “n10”. If using another sensor, select using Sensor Resistance
section on opposing page or cycle through steps 2 – 4 changing the sensor type until the temperature reading
on the main screen is accurate. As above, cycle between options by pressing “ ” or “ ” and press “set” to save.
o06 appears on screen, then control resets
STEP 5
Set Temperature
From main screen, quickly press “set” (1 second). Current temp. setting appears on screen
Cycle to intended temperature by pressing“ ” or “ ” and press “set” to save. Screen returns to main screen
Quick Set-up
Control
Application
Code
Application Defrost
Type*
Defrost
Termination
Sensors
Default
Temp. [°F]
[r00]
Temp. Range
min./max.
[°F]
[r02/r03]
Default Dif.
[°F] [r01]
Defrost
Interval
[hrs]
[d03]
Max.
Defrost
Time [mins]
[d04]
Defrost
Termination
Temp. [°F]
[d02]
AP0 (Default) No preset application - full menu 2 36 -31/22 4 6 30 43
AP1 Refrigeration Natural Time 1 39 36/43 4 4 30 –
AP2 Refrigeration Electric Time 1 36 32/39 4 6 15 –
AP3 Freezing Electric Time 1 -11 -15/-4 4 6 15 –
AP4 Refrigeration Electric Temp. 2 36 32/39 4 6 30 43
AP5 Freezing Electric Temp. 2 -11 -15/-4 4 6 30 43
AP6 No preset application - simplified menu 2 36 -31 – 122 4 6 30 43
* Hot gas defrost is an option available in full menu (d01).
Key Functions
Press and hold at power up:
FACTORY RESET (“FAC” is
displayed)
Press for one second: UP
Press and hold: ON/OFF
Press for one second: DOWN
Press and hold: DEFROST
Press for one second: BACK
Press and hold: PULL-DOWN
Press for one second: TEMP. SETPOINT/OK
Press and hold: MENU
SET
Display Icons
Night mode (Energy saving) Fan running
Compressor running (Flashes
in pull-down mode) Active alarm
Defrost °C Unit (°C or °F)
Key Functions and Display Icons
– Sair Control sensor
– S5 Defrost (evaporator) sensor
– SC Condenser sensor
– DI1 Digital input – configurable to the functions listed under
menu code o02
– DI2 Digital input – configurable to the functions listed under
menu code o37
Connection Diagram
DO1
12
SairS5Sc/DI1 DI2
DO2 DO3
GND GND
Pr
ogramming key – EKA 183B (080G9741)
3L 4N 5678
910
15 16 17 18
11 12 13 14
~~~~
Power supply
(according to the product code number)
GND TX RX +5V
App Selection
Select application based on application and wiring configuration (i.e., refrigeration vs. freezing, and number of temperature sensors). The Typical Wiring
Configurations diagram on the reverse side of this document may be used to assist with selection. All parameters can be modified using the full menu.
Some parameters have min and max set points which may need to be changed for less common configurations.
© Danfoss | DCS (ADAP-KOOL®) | 2018-11
Quick Start Guide, ERC 213
2 | DKRCE.PD.RL0.A3.02
Sensor Resistance: Using an ohmmeter, you can measure resistance of a sensor to identify sensor type or to troubleshoot a potentially faulty sensor.
Sensor Type Code Resistance [ohm] at Temperature [°F]
0 20 32 75
PTC Ptc 690 761 807 980
PTC 1000 Pt1 931 974 1000 1093
NTC 10000 * n10 70317 40411 29481 10459
NTC 5000 n5 42664 23110 16325 5251
* Included in kit
Common Functions
Adjust Temperature Set Point
From main screen, quickly press “set” (one second). The current temperature setting will appear on screen. Cycle to intended temperature by pressing
“^” or “^” and press“set” to save. The display will return to the main screen.
Adjust Differential
From main screen, press“set” for more than three seconds. Cycle to“r--”submenu by pressing “ ” or “ ” and press “set.” Cycle to “r01” and press “set.” Cycle to
preferred differential setting, and press “set” to save.“r01”will appear on screen. Press“<” twice to return to main screen.
Manual Defrost
From main screen, press defrost for more than three seconds to initiate defrost. The DEFROST icon is shown during defrost. Press defrost key for at least
three seconds to stop manual defrost.
Factory Reset
Press and hold“ ” and “ ” simultaneously at power up.
Unlock Keypad
After 5 minutes of no activity, the keypad will lock if P76 = yes (by default it is set to no). When the keypad is locked any key press shows“LoC”
in the display. Press“ ” and “ ” simultaneously for three seconds to unlock the keyboard.“unl” is displayed for three seconds.
Typical Wiring Configurations
Sair
(Control Sensor)
DI1DI2
Sair
(Control Sensor)
DI1DI2
Sair
(Control
Sensor)
DI1DI2
S5
(Defrost)
DO1
115 V AC
230 V AC
115 V AC
230 V AC
115 V AC
230 V AC
DO2 DO3 DO1 DO3DO2 DO1DO3DO2
ERC 213 - APP 1 ERC 213 - APP 2-3 ERC 213 - APP 4-5
Troubleshooting
Power Supply Code Description Remedy (applicable parameter code in parenthesis)
Common Alarm
/
Error Codes
A01 High temperature alarm Bring down temperature or increase high limit alarm limit (A13)
A02 Low temperature alarm Increase temperature or low temperature alarm limit (A14)
E27 Defrost sensor error Verify that defrost sensor is wired into terminals 10 and 11
Verify that correct sensor type is selected (o06)
E29 Air temperature sensor error Verify that control sensor is wired into terminals 9 and 10 – 8 is not used
Verify that correct sensor type is selected
Common
Problems/
Resolution
Problem Likely Cause Remedy (applicable parameter number in parenthesis)
Compressor does
not start
Waiting for compressor delay timer
Check compressor minimum off time (
CO2
)
Defrost in progress Check defrost interval (d03)
Check defrost on demand (temp. initiated defrost) (d19)
Defrost does not start
Controller in pull down mode Check pull-down duration (r96)
Wrong temperature
is displayed
Wrong type of sensor selected Verify that correct sensor type is selected (o06)
Sensor installed into incorrect terminals Verify that control sensor is wired into terminals 9 and 10 – 8 is not used
Evaporator icing Defrost interval too long Reduce defrost interval (d03)
Defrost time too short Increase max. defrost time (d04)
Need additional help with programming, parameters, or error codes? Download Danfoss’ Koolcode app.
Technical Specifications
Power Supply 080G3411 115V AC 50/60 HZ;
080G3412 230V AC 50/60 Hz
Inputs 4 total; 2 analog, 1 analog/digital, 1 digital
Sensor Included in Kit NTC 10000
Output
D01 Compressor Relay
115 V (080G3268): 16 FLA/72 LRA
230 V (080G3269): 10 FLA/60 LRA
D02 Defrost Relay and/D03 Fan Relay
8A, 2 FLA, 12 LRA
Operating Conditions 14 – 131 °F
Storage Conditions -40 – 158 °F
Approvals UL Recognized/NSF
© Danfoss | DCS (ADAP-KOOL®) | 2018-11
DKRCE.PD.RL0.A3.02 | 3
Quick Start Guide, ERC 213
Parameter Name Menu Code Unit Min. Value Max. Value Default Value Value
Predefined applications o61 – – – App0 App0
Sensor type o06 – – – n10 n10
Temperature Setpoint r00 °C -100 200 2 2
Differential r01 K 0.1 20 2 2.7
Min. set point limit r02 °C -100 200 -35 -35
Max. set point limit r03 °C -100 200 50 50
Display offset r04 K -10 10 0 0
Display Unit r05 – – – °C °F
Calibration of Sair r09 K -20 20 0 0
Night Set back r13 K -50 50 0 0
Offset reference displacement r40 °C -50 20 0 0
Pull down duration r96 min.. 0 960 0 0
Pull down temp limit r97 °C -100 200 0 0
Alarm delay - Normal conditions A03 min. 0 240 30 30
Alarm delay - pulldown / startup / def
A12 min. 0 240 60 60
High temp alarm A13 °C -100 200 8 8
Low temp alarm A14 °C -100 200 -30 -30
DI1 delay A27 min. 0 240 30 30
DI2 delay A28 min. 0 240 30 30
Condenser High temp alarm A37 °C 0 200 80 80
Condenser High block limit A54 °C 0 200 85 85
Voltage protection A72 – – – No No
Min. cut-in voltage A73 V 0 270 0 0
Min. cut-out voltage A74 V 0 270 0 0
Max. voltage A75 V 0 270 270 270
Defrost Method d01 – – – Electric Electric
Defrost stop temperature d02 °C 0 50 6 6.5
Defrost Interval d03 hour 0 240 8 6
Max. defrost Time d04 min. 0 480 30 30
Defrost delay at power up d05 min. 0 240 0 0
Drip delay d06 min. 0 60 0 0
Fan delay after defrost d07 min. 0 60 0 0
Fan start temp after defrost d08 °C -50 0 -5 -5
Fan ON during defrost d09 – – – On On
Defrost stop sensor d10 – – – None None
Comp accumulated runtime d18 hour 0 96 0 0
Defrost on demand d19 K 0 20 20 20
Defrost delay after pulldown d30 min. 0 960 0 0
Fan at compressor cutout F01 – – – FFC FAo
Fan stop evaporator temp F04 °C -50 50 50 50
Fan ON time F07 min. 0 15 2 2
Fan OFF time F08 min. 0 15 2 2
Parameter sheet
© Danfoss | DCS (ADAP-KOOL®) | 2018-11
Quick Start Guide, ERC 213
4 | DKRCE.PD.RL0.A3.02
Parameter Name Menu Code Unit Min. Value Max. Value Default Value Value
Compressor min. ON time C01 min. 0 30 0 0
Compressor min. OFF time C02 min. 0 30 2 2
Comp OFF delay at open door C04 min. 0 15 0 0
Zero crossing C70 – – – yes yes
Delay of outputs at startup o01 sec 0 600 5 5
DI1 configuration o02 – – – Off Off
Serial address o03 – 0 247 0 0
Password o05 – 0 999 0 0
Display Resolution o15 – – – 0.1 1
Relay 1 counter o23 – – – – 0
Relay 2 counter o24 – – – – 0
Relay 3 counter o25 – – – – 0
DI2 configuration o37 – – – Off Off
Display during defrost o91 – – – -d- -d-
DO2 Config o71 – – – def def
DI1 polarity P73 – – – no no
DI2 polarity P74 – – – no no
Invert alarm relay P75 – – – Normal Normal
Keyboard lock P76 – – – No No
Main switch r12 – – – Off On
Controller status u00 – – – S25 S20
Air temperature (Sair) u01 °C – – – 321
Present regulation reference u02 – – – 0
Evaporator temperature (S5) u09 °C – – – 0
DI1 status u10 – – – Off Off
Night mode u13 – – – Off Off
DI2 status u37 – – – Off Off
Condenser temperature (Sc) U09 – – – 0
Compressor relay status u58 – – – Off Off
Fan relay status u59 – – – Off On
Defrost relay status u60 – – – Off Off
Firmware version u80 – – – – 4.16
Database version – – – – – 4.02
Order No Low – – – – – 3502
Air temperature sensor(Sair) error E29 – – – Off On
Defrost sensor (S5) error E27 – – – Off Off
Condensor sensor(Sc) error E30 – – – Off Off
High temperature alarm A01 – – – Off Off
Low temperature alarm A02 – – – Off Off
High voltage alarm A99 – – – Off Off
Low voltage alarm AA1 – – – Off Off
High condenser temperature alarm A61 0 – – Off Off
Door alarm A04 0 – – Off Off
DI external alarm A15 0 – – Off Off

Other manuals for ERC 213

3

Other Danfoss Controllers manuals

Danfoss VLT DMS 300 User manual

Danfoss

Danfoss VLT DMS 300 User manual

Danfoss VLT AutomationDrive FC 300 User manual

Danfoss

Danfoss VLT AutomationDrive FC 300 User manual

Danfoss 140F1089 User manual

Danfoss

Danfoss 140F1089 User manual

Danfoss VLT 5000 Series User manual

Danfoss

Danfoss VLT 5000 Series User manual

Danfoss MCI 25 User manual

Danfoss

Danfoss MCI 25 User manual

Danfoss AVQM Series User manual

Danfoss

Danfoss AVQM Series User manual

Danfoss VLT AQUA Drive FC 202 User manual

Danfoss

Danfoss VLT AQUA Drive FC 202 User manual

Danfoss AMV 610 User manual

Danfoss

Danfoss AMV 610 User manual

Danfoss VLT MCD 600 User manual

Danfoss

Danfoss VLT MCD 600 User manual

Danfoss EKC 316A User manual

Danfoss

Danfoss EKC 316A User manual

Danfoss 5000 Flux User manual

Danfoss

Danfoss 5000 Flux User manual

Danfoss AME 23 SU User manual

Danfoss

Danfoss AME 23 SU User manual

Danfoss EKC 202A User manual

Danfoss

Danfoss EKC 202A User manual

Danfoss MCO 305 User manual

Danfoss

Danfoss MCO 305 User manual

Danfoss AME 130H User manual

Danfoss

Danfoss AME 130H User manual

Danfoss EKC 202 User manual

Danfoss

Danfoss EKC 202 User manual

Danfoss FH-WC User manual

Danfoss

Danfoss FH-WC User manual

Danfoss EKC 202B User manual

Danfoss

Danfoss EKC 202B User manual

Danfoss FT1555-BM User manual

Danfoss

Danfoss FT1555-BM User manual

Danfoss NovoCon Series User manual

Danfoss

Danfoss NovoCon Series User manual

Danfoss CF-MC User manual

Danfoss

Danfoss CF-MC User manual

Danfoss AME 20 User manual

Danfoss

Danfoss AME 20 User manual

Danfoss VLT AutomationDrive FC 301 User manual

Danfoss

Danfoss VLT AutomationDrive FC 301 User manual

Danfoss EKE 1B User manual

Danfoss

Danfoss EKE 1B User manual

Popular Controllers manuals by other brands

FunkTronic Major BOS 2b2 manual

FunkTronic

FunkTronic Major BOS 2b2 manual

Rittal RiLine SV 9635.400 Assembly and operating instructions

Rittal

Rittal RiLine SV 9635.400 Assembly and operating instructions

NeuroDigital Avatar VR quick start guide

NeuroDigital

NeuroDigital Avatar VR quick start guide

Parker Sporlan S3C Quick reference guide

Parker

Parker Sporlan S3C Quick reference guide

Texmate SG100 user manual

Texmate

Texmate SG100 user manual

MRC THROTTLEPACK 9900 user manual

MRC

MRC THROTTLEPACK 9900 user manual

IOT-Smart Solutions MKB02 user manual

IOT-Smart Solutions

IOT-Smart Solutions MKB02 user manual

Extron electronics MLC Plus 84 D Setup guide

Extron electronics

Extron electronics MLC Plus 84 D Setup guide

Full Gauge TC-970E+ECO Faston manual

Full Gauge

Full Gauge TC-970E+ECO Faston manual

Spartan Power SpartanStart Instruction guide

Spartan Power

Spartan Power SpartanStart Instruction guide

Bticino F470/1 Instructions for use

Bticino

Bticino F470/1 Instructions for use

Watlow PC1X-N20 user manual

Watlow

Watlow PC1X-N20 user manual

RDZ 6600200 Technical sheet

RDZ

RDZ 6600200 Technical sheet

LK Armatur 150  SmartSol instruction manual

LK Armatur

LK Armatur 150 SmartSol instruction manual

Sigma Controls 100 Series instruction manual

Sigma Controls

Sigma Controls 100 Series instruction manual

ICP DAS USA 7188E Hardware user manual

ICP DAS USA

ICP DAS USA 7188E Hardware user manual

Bard LV1000-100 INSTALLATION SUPPORT MATERIALS

Bard

Bard LV1000-100 INSTALLATION SUPPORT MATERIALS

Mitsubishi Electric RJ71PB91V-U-IN-E user manual

Mitsubishi Electric

Mitsubishi Electric RJ71PB91V-U-IN-E user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.