7. Highlighted area indicates digit selected for
change.
8. Press [Cancel] to disregard change, or press [OK]
to accept change and enter the new setting.
Example of changing parameter data
Assume that parameter 22-60 Broken Belt Function is set to
[0] O. To monitor the fan-belt condition, non-broken or
broken, follow this procedure:
1. Press [Quick Menu].
2. Press [▼] to select Function Set-ups.
3. Press [OK].
4. Press [▼] to select Application Settings.
5. Press [OK].
6. Press [OK] again for Fan Functions.
7. Press [OK] to select Broken Belt Function.
8. Press [▼], to select [2] Trip.
If a broken fan belt is detected, the frequency converter
trips.
Select Q1 My Personal Menu to display personal
parameters
For example, an AHU or pump OEM may have pre-
programmed personal parameters to be in My Personal
Menu during factory commissioning to make on-site
commissioning/ne-tuning simpler. These parameters are
selected in parameter 0-25 My Personal Menu. Up to 20
dierent parameters can be programmed in this menu.
Select Changes Made for information about:
•The last 10 changes. Press [▲] and [▼] to scroll
between the last 10 changed parameters.
•The changes made since default setting.
Loggings
Loggings show information about the display line
readouts. The information is shown as graphs.
Only display parameters selected in parameter 0-20 Display
Line 1.1 Small and parameter 0-24 Display Line 3 Large can
be viewed. Up to 120 samples can be stored in the
memory for later reference.
Quick set-up
Ecient parameter set-up for refrigeration applications
The parameters can easily be set up for most refrigeration
applications only by using the Quick Set-up.
After pressing [Quick Menu], the dierent options in the
Quick Menu are listed. See also Illustration 2.14.
Example of using the quick set-up
To set the ramp-down time to 100 s, follow this procedure:
1. Select Quick Set-up. Parameter 0-01 Language in
Quick Set-up appears.
2. Press [▼] repeatedly until parameter 3-42 Ramp 1
Ramp Down Time appears with the default setting
of 20 s.
3. Press [OK].
4. Press [◀] to highlight the third digit before the
comma.
5. Change 0to 1by pressing [▲].
6. Press [▶] to highlight the digit 2.
7. Change 2to 0by pressing [▼].
8. Press [OK].
The new ramp-down time is now set to 100 s.
130BP064.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
40.0% 4.84 A 1(1)
Quick Menus
Illustration 2.14 Quick Menu View
Access the 18 most important set-up parameters of the
frequency converter via Quick Set-up. After programming,
the frequency converter is ready for operation. The 18
Quick Set-up parameters are shown in Table 2.1.
Parameter [Units]
Parameter 0-01 Language –
Parameter 1-03 Torque Characteristics –
Parameter 1-20 Motor Power [kW] [kW]
Parameter 1-21 Motor Power [HP] [hp]
Parameter 1-22 Motor Voltage [V]
Parameter 1-23 Motor Frequency [Hz]
Parameter 1-24 Motor Current [A]
Parameter 1-25 Motor Nominal Speed [RPM]
Parameter 1-39 Motor Poles –
Parameter 4-12 Motor Speed Low Limit [Hz] [Hz]
Parameter 4-14 Motor Speed High Limit [Hz] [Hz]
Parameter 3-02 Minimum Reference –
Parameter 3-03 Maximum Reference –
Parameter 3-41 Ramp 1 Ramp Up Time [s]
Parameter 3-42 Ramp 1 Ramp Down Time [s]
Parameter 3-13 Reference Site –
Parameter 5-10 Terminal 18 Digital Input –
Parameter 1-29 Automatic Motor Adaptation (AMA) –
Table 2.1 Quick Set-up Parameters
How to Program VLT®Refrigeration Drive FC 103
18 Danfoss A/S © 05/2016 All rights reserved. MG16H202
22