Danfoss KPU Series User manual

Danfoss
60-1408.11
Installation guide
Pressure switch
KPU
060R9768
060R9768
© Danfoss | DCS (jmn) | 2017.01 DKRCC.PI.CD0.C6.02 | 520H11521 | 1
Application
KPU dual pressure switches are for use on commercial
refrigeration and air conditioning systems to protect
compressor against excessively low suction pressure or
excessively high discharge pressure.
KPU dual pressure switches are compatible with refrigerants
listed below. KPU16W and KP16B are fail safe switches for high
pressure refrigerants. Standard enclosure is ~ NEMA 1.
Refrigerants:
R22, R134a, R404A, R407A, R407C, R407F, R410A*), R422B, R422D,
R438A, R448A, R449A, R450A, R452A, R507A, R513A
replace with:
For complete list of approved refrigerants, visit www.products.danfoss.
com and search for individual code numbers, where refrigerants are
listed as part of technical data. /
*) R410A only for KPU 16W and KPU 16B
KPU dual pressure switches are tted with the Single-Pole,
Single-Throw (SPST) or Single-Pole Double-Throw (SPDT)
switches, suitable for direct as well as indirect (with acontactor)
control.
Three versions of switch operation are available:
– automatic on LP and HP sides
– automatic on LP and manual reset on HP
– convertible manual or automatic on LP and HP sides.
Manual reset
The manual reset mechanism does not allow the pressure
switch to automatically reset after the switch has cut out. So the
pressure switch must be manually reset by the user to enable
restart of the equipment. Manual reset is possible to operate
only after return of pressure to cut in level. Before releasing
the reset it is recommended to investigate what caused the
shutdown.
Convertible reset
The convertible reset feature allows to change the operation
from automatic to manual by turning the selecting plate.
The selecting plate is located between two push buttons at the
top of the switch.
Please refer to instruction below demonstrating how to select
reset function.
Product Specication
Type
Code no. Low pressure (LP) High pressure (HP) Reset
Contact system
1⁄4in
male are
36 in cap.
tube w. 1⁄4in
are nut
Regulating
range
[inHg] [psig]
Dierential
Δp
[psi]
Regulating
range
[psig]
Dierential
Δp
[psi]
Low
pressure
High
pressure
KPU 15 060-5247 060-5248 6 in – 108 10 – 60 100 – 465 60 Automatic Automatic SPST
(NO + NC)
KPU 15B 060-5249 060-5250 6 in – 108 10 – 60 100 – 465 60 Automatic Man (Max.)
KPU 16W 060-5251 060-5252 6 in – 108 10 – 60 100 – 600 60 Automatic Automatic SPDT with
LP/HP signal
KPU 16B 060-5253 060-5254 6 in – 108 10 – 60 100 – 600 60 Convertible Convertible
Max. working pressure: LP side: 250 psig HP side KPU 15: 510 psig HP side KPU 16: 675 / 610* psig
Max. test pressure: LP side: 290 psig HP side KPU 15: 530 psig HP side KPU 16: 725 psig
* 610psig - MWP for products used according to 2014/68/EU PED directive Ambient temperature: -40 – 122 °F (175 °F for max. 2 hours)
Convertible reset:
Selection of reset function on dual pressure switches with convertible
reset – turn plate to desired reset conguration.Insert a screwdriver into
the slot on the lock disc and turn it to desired reset conguration. Do not
turn the screw on the lock disc as it may damage the convertible reset
mechanism.
Danfoss
60-763.14
Danfoss
60-763.14
Danfoss
60-763.14
Danfoss
60-763.14
LP man. LP auto. LP auto. LP man.
HP man. HP man. HP auto. HP auto.
Danfoss
60-1259.11
© Danfoss | DCS (jmn) | 2017.01
2 | 520H11521 | DKRCC.PI.CD0.C6.02
Installation
Select an accessible location, where the switch and pressure
connection line will not be subject to damage.
Recommended
mounting position
Mount the KPU pressure switch on a bracket or on acompletely
at surface. Mounting to an uneven surface might cause
improper switch operation.
IMPORTANT:
Mount the pressure switch in a position that will allow
drainage of liquids away from switch bellows. Pressure
connection of the switch must always be located on the
top side of the refrigerant line. This reduces the possibility
of oil, liquids, or sediment collecting in the bellows, which
could cause theswitch malfunction.
IMPORTANT:
Ensure the ambient temperature for the dual pressure
switch on LP side is higher than the refrigeration line as
that will prevent liquid migration and accumulation in
the bellows.
IMPORTANT:
Pressure pulsations in the refrigeration system reduce life
time of the bellows and might disturb switch function.
Pressure pulsations should always be eectively damped
e.g. by connection thepressure switches to the
refrigeration system through acapillarytube.
Recommendations for capillary tube and are connections:
1. Ensure self-draining of the capillary tube to minimize
clogging.
2. Coil excess capillary tube into smooth, circular coils (approx.
3 inch diameter). The coiled tube should be securely fastened
in order to prevent possible damage due to vibration.
3. Leave a little slack in the capillary tube as it helps to damp
mechanical vibrations.
4. Avoid sharp bends as well as re-bending of the capillary tube
on the same point as it weakens the material, increasing the
risk of crack.
5. Never allow for contact between the capillary tube and sharp
or abrasive objects as during vibrations the tube could be
damaged due to friction.
6. Purge the piping before connecting pressure switches.
7. Always use two wrenches
tightening the are nut on
the pressure switch. One
wrench should support the
connector while the second
wrench isused to tighten the
nut.
8. Do not over tighten are nuts as it may damage the threads
causing leaks.
9. Protect the capillary tube from damage caused by vibrations
from compressor:
–
when the switch unit is mounted directly on the compressor,
the capillary must be secured to the compressor so that
everything vibrates as a whole.
– when the switch is mounted remote from the compressor,
make the pressure connections away from thecompressor.
– when the switch is mounted remote from the compressor
and the pressure connections have to be on the compressor,
then damping coils must be used between the compressor
and the pressure switch.
NOTE:
After installing the pressure switch, evacuate theplant in
accordance with applicable EPA and other regulations,
to remove air, moisture, and other contaminants.
Screws for
bracket mounting Mounting holes
for at surfaces
Use only the mounting holes provided; no other holes
are to be added to the switch.
For bracket mounting use only the 10-32x3/16 screws provided
with the switch. If other screws are used, function of the pressure
switch might be disturbed (they should not protrude into the
switch more than ⁄in).
© Danfoss | DCS (jmn) | 2017.01 DKRCC.PI.CD0.C6.02 | 520H11521 | 3
Wiring Option A:
– KPU 15 Pressure Switch (SPST (NO + NC))
Wiring Option B:
– KPU 16 Pressure Switch (SPDT with LP/HP signal)
Wiring
Electrical ratings according to UL regulations
European electrical ratings according to EN 60947
The terminal block as well as grounding screw are accessible
after dismounting of the front cover.
Contacts Motor ratings 120 V AC 240 V AC
A – B
A – C
FLA 24 24
AC LRA make only 144 144
NIA 24 24
Pilot Duty 12 W, 120/240 V DC
A – D Pilot Duty 50 VA, 240 V AC
AC1 AC3 AC15 LR DC13
16 A 16 A 10 A 112 A 12 W
400 V 220 V
A: Manual reset button (available only on switches with manual/
convertible reset function)
B: HP Manual trip. Press the lever up. Use screwdriver only!
C: Terminal block
D: Grounding screw
E: LP Manual trip. Press the lever up. Use ngers only!
Wire dimensions: 10 AWG max.
Cable entry: 7⁄8 inch cable entry for 1⁄2inch male pipe thread
connection (conduit boss) or similar (Pg 13.5 or Pg 16) screwed
cable entry.
LOAD ~ LINE ~ LINE
LOAD
LP signal
HP signal
CAUTION:
Disconnect power supply before wiring connections
are made or service to avoid possible electrical shock or
damage to equipment.
Do never touch live parts with your ngers or with
anytool.
NOTE:
All wiring should conform to the National Electrical Code
and local regulations.
Use copper wire only.
Use terminal screws furnished in the contact block.
Do not exceed tightening torque 20 lb. in (2.3 Nm).
Do not exceed electrical ratings for the switch.
Contact function test (Manual trip)
When the electrical leads are connected the contact function
can be manually tested regardless of pressure conditions in the
system. For LP side testing use the trip lever located in the left
side of the dual KPU. The lever must be operated with ngers
only. Do not use screwdriver as it will damage the switch. For HP
side testing use lever located at bottom of right side of the dual
KPU. The lever must be carefully operated with a screwdriver.
NOTE:
While operating the manual trip on KPU switches with
manual reset it is necessary to push the reset knob.
Danfoss
60-1262f.11
A
B
C
D
E
NOTE:
Cut Out set point must be above absolute vacuum!
If the Dierential is set too high then the switch will
not stop the compressor.
© Danfoss | DCS (jmn) | 2017.01
4 | 520H11521 | DKRCC.PI.CD0.C6.02
Adjustment
A: HP Range adjusting screw
B: Cover screw
C: LP Dierential adjusting screw
D: Locking plate
E: LP Range adjusting screw
Low Pressure Side Setting
Cut Out on pressure fall.
Scale plate directly indicates the Cut In
and the Dierential set points.
Before adjustment, loosen the locking plate.
For setting use the Universal Refrigeration Wrench.
Set Cut In/ Cut Out by adjusting range screw:
– On LP Side turn the range screw clockwise to lower theCut In.
– On HP Side turn the range screw clockwise to rise theCutOut.
Set dierential by adjusting dierential screw:
– On LP Side turn the dierential screw clockwise to increase the
dierential.
NOTE:
Adjust the pressure switch with settings specied by the
manufacturer of the controlled equipment.
Do not exceed the pressure ratings of the controlled
equipment or any of its components when checking
pressure switch operation or operating the controlled
equipment.
Do not adjust pointers beyond the highest or lowest
indicator marks on the scale plate, as this may cause
inaccurate swich operation.
IMPORTANT:
The scale plate is only for reference and for more
precise setting a pressure gauge should be used.
IMPORTANT:
After installing and adjusting pressure switch run the
controlled equipment several times (at least three
cycles) at normal operating conditions.
Danfoss
60-1265f.11
1
Danfoss
60-1264f.11
1
2
Danfoss
60-1263.11
B
A
C
D
E
1. Turn the range screw to adjust the Cut Out set point.
2. The Cut In setting equals the Cut Out less the Dierential:
CUT IN = CUT OUT - 60 psi
High Pressure Side Setting
Cut Out on pressure rise.
Scale plate directly indicates the Cut Out set point.
There is no pointer for the Dierential.
The Dierential pressure value is xed and printed on the scale
plate.
1. Turn the range screw to adjust the Cut In set point.
2. Then turn the dierential screw to adjust the Dierential
3. The Cut Out setting equals the Cut In less the Dierential:
CUT OUT = CUT IN - DIFFERENTIAL

This manual suits for next models

3

Other Danfoss Switch manuals

Danfoss LLS 4000 User manual

Danfoss

Danfoss LLS 4000 User manual

Danfoss RT 260A User manual

Danfoss

Danfoss RT 260A User manual

Danfoss LLS 4000 User manual

Danfoss

Danfoss LLS 4000 User manual

Danfoss MBC 5000 User manual

Danfoss

Danfoss MBC 5000 User manual

Danfoss RT 1AL User manual

Danfoss

Danfoss RT 1AL User manual

Danfoss KP 34 User manual

Danfoss

Danfoss KP 34 User manual

Danfoss KP 15 User manual

Danfoss

Danfoss KP 15 User manual

Danfoss KP 7ABS User manual

Danfoss

Danfoss KP 7ABS User manual

Danfoss KP 15 User manual

Danfoss

Danfoss KP 15 User manual

Danfoss KPS 35 User manual

Danfoss

Danfoss KPS 35 User manual

Danfoss KP 44 User manual

Danfoss

Danfoss KP 44 User manual

Danfoss RT 112 User manual

Danfoss

Danfoss RT 112 User manual

Danfoss BCP1H User manual

Danfoss

Danfoss BCP1H User manual

Danfoss CWH1000 Manual

Danfoss

Danfoss CWH1000 Manual

Danfoss RT 260A User manual

Danfoss

Danfoss RT 260A User manual

Danfoss TS715 Si Assembly Instructions

Danfoss

Danfoss TS715 Si Assembly Instructions

Danfoss RT 30AW User manual

Danfoss

Danfoss RT 30AW User manual

Danfoss RT 260A User manual

Danfoss

Danfoss RT 260A User manual

Danfoss PVG 32 User manual

Danfoss

Danfoss PVG 32 User manual

Danfoss MP 55 User manual

Danfoss

Danfoss MP 55 User manual

Danfoss KP 1E User manual

Danfoss

Danfoss KP 1E User manual

Danfoss KPU Series User manual

Danfoss

Danfoss KPU Series User manual

Danfoss AMV 410 User manual

Danfoss

Danfoss AMV 410 User manual

Danfoss KP 1 User manual

Danfoss

Danfoss KP 1 User manual

Popular Switch manuals by other brands

PCB Piezotronics IMI SENSORS EX686B11 Installation and operating manual

PCB Piezotronics

PCB Piezotronics IMI SENSORS EX686B11 Installation and operating manual

EUCHNER CES-A-C5H-01-EX operating instructions

EUCHNER

EUCHNER CES-A-C5H-01-EX operating instructions

SMC Networks SMC EZ Switch 10/100/1000 SMCGS8P-Smart Specifications

SMC Networks

SMC Networks SMC EZ Switch 10/100/1000 SMCGS8P-Smart Specifications

IPGARD DPMST-2S quick start guide

IPGARD

IPGARD DPMST-2S quick start guide

4O3A Antenna Genius manual

4O3A

4O3A Antenna Genius manual

Atlas ASL Series quick guide

Atlas

Atlas ASL Series quick guide

hager HIC4 G Series Installation

hager

hager HIC4 G Series Installation

Transition Networks SM24DPa user guide

Transition Networks

Transition Networks SM24DPa user guide

3Com 3CFSU05 datasheet

3Com

3Com 3CFSU05 datasheet

CHN SMART SMART HOME Series user manual

CHN SMART

CHN SMART SMART HOME Series user manual

D-Link DGS-1250-28X Quick installation guide

D-Link

D-Link DGS-1250-28X Quick installation guide

Vivotek AW-FCT-050A-250 Quick installation guide

Vivotek

Vivotek AW-FCT-050A-250 Quick installation guide

SMC Networks TigerSwitch SMC6128PL2 Specifications

SMC Networks

SMC Networks TigerSwitch SMC6128PL2 Specifications

GE MultiLink ML810 instruction manual

GE

GE MultiLink ML810 instruction manual

Pulsar PSB-24V5A quick start guide

Pulsar

Pulsar PSB-24V5A quick start guide

Jaycar AC-1707 user manual

Jaycar

Jaycar AC-1707 user manual

US Robotics USR997930 installation guide

US Robotics

US Robotics USR997930 installation guide

FSR Eagle 200 user guide

FSR

FSR Eagle 200 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.