2.3 bar
(33.5 psi)/rev.
0.7 bar (10 psi)/rev. 0.15 bar (2 psi)/rev.
6 mm
(⁄in)
© Danfoss | DCS (jmn) | 2016.10
2 | 520H11518 | DKRCC.PI.CD0.A6.02
LP, aut. reset LP, man. reset HP
LP = Low Pressure LP = Low Pressure HP = High Pressure
LP side: A-C opens on pressure drop
HP side: A-C opens on pressure rise
Short circuit protection:
Fuse 16 Amp
Manual trip function
Adjustment
Convertible reset
KP 15: LP/HP convertible, KP 17WB: HP convertible
Insert a screwdriver into the slot on the lock disc and
turn it to desired reset conguration.
Do not turn the screw on the lock disc as it may damage
theconvertible reset mechanism.
LP man. LP auto. LP auto. LP man.
HP man HP man HP auto. HP auto.
Note: Do not select automatic reset if safety of the system
requires manual reset.
Note: Selected reset conguration may be protected against
unauthorized actions applying a seal.
TRIP:
use FINGERS ONLY!
(Do NOT use screwdriver)
Reset options
CAUTION:
Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage
to equipment. Do never touch live parts with your ngers or with any tool.
Electrical rating - General When used acc. to UL regulations
LR 112A
AC 1: 16 A
400 V
AC
DC 13
AC 3: 16 A 12 W
AC 15: 10 A 220 V
Listed refrigeration controller
61B5
Contacts
Voltage FL LR Resist.
load
Pilot
duty
AC DC A A
A - B
A - C
240 – 8 48 8 A 3 A
120 –16 96 16 A
–240 – – – 12 W
A - D 240 – – – – 50 VA
Use copper wire only
Tightening torque 20 lb. in
-1 bar (Pe)(30 inHg) -1 bar (Pe)(30 inHg)