EnglishDeutsch
 logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Danfoss
  6. •
  7. Switch
  8. •
  9. Danfoss KP 1 User manual

Danfoss KP 1 User manual

This manual suits for next models

4

Other Danfoss Switch manuals

Danfoss LLS 4000 User manual

Danfoss

Danfoss LLS 4000 User manual

Danfoss KP 21 User manual

Danfoss

Danfoss KP 21 User manual

Danfoss KP 15 User manual

Danfoss

Danfoss KP 15 User manual

Danfoss RT 30AW User manual

Danfoss

Danfoss RT 30AW User manual

Danfoss KPU Series User manual

Danfoss

Danfoss KPU Series User manual

Danfoss KPU 1 User manual

Danfoss

Danfoss KPU 1 User manual

Danfoss MP 55 User manual

Danfoss

Danfoss MP 55 User manual

Danfoss KP 1 User manual

Danfoss

Danfoss KP 1 User manual

Danfoss TS715 Si Assembly Instructions

Danfoss

Danfoss TS715 Si Assembly Instructions

Danfoss RT 260A User manual

Danfoss

Danfoss RT 260A User manual

Danfoss KP 1A User manual

Danfoss

Danfoss KP 1A User manual

Danfoss AMV 410 User manual

Danfoss

Danfoss AMV 410 User manual

Danfoss KP 7ABS User manual

Danfoss

Danfoss KP 7ABS User manual

Danfoss MBC 5000 User manual

Danfoss

Danfoss MBC 5000 User manual

Danfoss PVG 32 User manual

Danfoss

Danfoss PVG 32 User manual

Danfoss AKS 38 User manual

Danfoss

Danfoss AKS 38 User manual

Danfoss LLS 4000 User manual

Danfoss

Danfoss LLS 4000 User manual

Danfoss KPI 34 User manual

Danfoss

Danfoss KPI 34 User manual

Danfoss KP 34 User manual

Danfoss

Danfoss KP 34 User manual

Danfoss LLS 4000 Installation and maintenance instructions

Danfoss

Danfoss LLS 4000 Installation and maintenance instructions

Danfoss KPU Series User manual

Danfoss

Danfoss KPU Series User manual

Danfoss KP 15 User manual

Danfoss

Danfoss KP 15 User manual

Danfoss KP 1E User manual

Danfoss

Danfoss KP 1E User manual

Danfoss KPS 35 User manual

Danfoss

Danfoss KPS 35 User manual

Popular Switch manuals by other brands

TRENDnet TK-401R null

TRENDnet

TRENDnet TK-401R null

TRENDnet TK-200K null

TRENDnet

TRENDnet TK-200K null

TRENDnet TE100-S8 null

TRENDnet

TRENDnet TE100-S8 null

URC Total Control MFS-8 installation manual

URC

URC Total Control MFS-8 installation manual

Azbil HPQ-D11 user manual

Azbil

Azbil HPQ-D11 user manual

Sony DFS-900M operating instructions

Sony

Sony DFS-900M operating instructions

SICK i17S operating instructions

SICK

SICK i17S operating instructions

F&F SZR-277 quick start guide

F&F

F&F SZR-277 quick start guide

Shure UAMS/BK user guide

Shure

Shure UAMS/BK user guide

Dräger X-zone Switch Off Instructions for use

Dräger

Dräger X-zone Switch Off Instructions for use

Asco Joucomatic 349 Series manual

Asco

Asco Joucomatic 349 Series manual

BT Mini Hub user guide

BT

BT Mini Hub user guide

D-Link DES-1226G manual

D-Link

D-Link DES-1226G manual

Johnson Controls FS80-C installation instructions

Johnson Controls

Johnson Controls FS80-C installation instructions

MicroNet SP1200A user manual

MicroNet

MicroNet SP1200A user manual

Ruijie RG-PF2920 Series Hardware  installation and reference guide

Ruijie

Ruijie RG-PF2920 Series Hardware installation and reference guide

Altinex DA1914SX user guide

Altinex

Altinex DA1914SX user guide

RJM MASTERMIND PBC/6X user manual

RJM

RJM MASTERMIND PBC/6X user manual

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

INSTRUCTIONS
KP 1, KP 2,
KP 5, KP 7W, KP 7B
060R9746
RI.05.1A.22 ®RI.5A.J1.22 01-1999
Types
The controls can be used with CFC, HFC
and HCFC refrigerants.
CAUTION: Do not install these controls on
ammonia systems.
CAUTION: Do not mount the control in a position where dirt,
sediment, or oil will affect the operation of the control.
Mounting requirements Ambient temperatures
Auto reset: KP 1, KP 2, KP 5, KP 7W Manual reset: KP 1, KP 5, KP 7B
CAUTION: The mounting panel must be plane to avoid damage of control.
Enclosure
Test pressure (pTEST) Connections
060R9746
© Danfoss A/S
t1min. KP 1, 2, 5: –40°F (–40°C)
KP 7: –13°F (–25°C)
t1max. 150°F (65°C)
ptest max.:
KP 1, 2: 285 psig (20 bar pe)
KP 5, 7: 505 psig (35 bar pe)
Electrical contacts/wiring test
TRIP (main lever)
use FINGERS ONLY!
(Do NOT use screwdriver)
Note:
KP 1, KP 5 and KP 7B w/man. reset:
Push manual reset knob during manual
tripping.
Wiring
CAUTION: Disconnect power supply before
wiring connections are made to avoid
possible electrical shock or damage to
equipment.
All wiring should conform to the National
Electrical Code and local regulations.
Terminal block
CAUTION: Use terminal screws furnished
in the contact block.
Use tightening torque 20 lb. in (2.3 Nm).
Use copper wire only.
Contact load ratings
Load Option A
CUT-OUT on pressure drop
Wire terminals 1-4:
CUT-IN = High Set Point (HSP)
see “Setting”
CUT-OUT = Low Set Point (LSP)
see “Setting”
Terms 1-4 close on pressure rise
Terms 1-4 open on pressure drop
Example: CUT-IN = 30 psig
CUT-OUT = 10 psig
This means CUT-IN = HSP = 30 psig
CUT-OUT = LSP = 10 psig
Note:
= Bellows movement on pressure rise
Ø= Bellows movement on pressure drop
The free terminal can be used for signal
purpose.
Load Option B
CUT-OUT on pressure rise
Wire terminals 1-2:
CUT-IN = Low Set Point (LSP)
see “Setting”
CUT-OUT = High Set Point (HSP)
see “Setting”
Terms 1-2 close on pressure drop
Terms 1-2 open on pressure rise
Example: CUT-IN = 250 psig
CUT-OUT = 350 psig
This means CUT-IN = LSP = 250 psig
CUT-OUT = HSP = 350 psig
120 V a.c. 16 FLA, 96 LRA
240 V a.c. 8 FLA, 48 LRA
240 V d.c. 12 W pilot duty
Manual reset
To resume control operation after safety
cutout, push reset knob as indicated.
Note:
KP 1, man. reset is possible only after a
pressure rise of 10 psi (0.7 bar).
KP 5 and KP 7B, man. reset is possible only
after a pressure drop of respectively 43 psi
(3.0 bar) and 58 psi (4.0 bar)
RI.5A.J1.22 © Danfoss A/S
Bellows Bellows
Diff. (fixed)
KP 1: 10 psi (0.7 bar
KP 5: 43 psi (3 bar)
KP 7B: 58 psi (4 bar)
Adjustment spindle(s) location
Auto reset Manual reset
KP 1, 2, 5, 7W KP 1, 5, 7B
Setting
(se also “Wiring”)
KP 1 (auto reset), KP 2, KP 5, KP 7W and KP 7B KP 1 (manual reset ONLY)
1. Adjust range spindle to desired 1. Adjust range spindle to desired
HIGH SET POINT (HSP) LOW SET POINT (LSP)
2. Adjust differential spindle to 2. DIFFERENTIAL is fixed.
desired DIFFERENTIAL (DIFF.) Value printed on scale plate
Note:
KP 5 (manual reset) and KP 7B have fixed diff.
Value printed on scale plate.
HIGH SET POINT minus DIFFERENTIAL equals LOW SET POINT LOW SET POINT plus DIFFERENTIAL equals HIGH SET POINT
Example: Example:
HSP – DIFF. = LSP LSP + DIFF. = HSP
30 psig – 20 psi = 10 psig 12 psig + 10 psi = 22 psig
(2.1 bar) (1.4 bar) (0.7 bar) (0.8 bar) (0.7 bar) (1.5 bar)
If terminals 1-4 are used: CUT-IN = HSP
CUT-OUT = LSP
If terminals 1-2 are used: CUT-IN = LSP
CUT-OUT = HSP
RI.5A.J1.22 © Danfoss A/S
10 psi (0.7 bar) /
rev. KP 1
7 psi (0.5 bar) /
rev. KP 2
33 psi (2.3 bar) /
rev. KP 5, 7W, 7B 3 psi (0.2 bar) / rev. KP 1
1.5 psi (0.1 bar) / rev. KP 2
4 psi (0.3 bar) / rev. KP 5
7 psi (0.5 bar) / rev. KP 7W
Adjustment
See instruction printed on top of control
Note:
Remove lock plate before adjustment.
Replace lock plate after adjustment (if desired).
© Danfoss A/S (AC-SP,jp) 01-1999RI.5A.J1.22