Danfoss KP 15 User manual

This manual suits for next models

4

Other Danfoss Switch manuals

Danfoss MBC 5000 User manual

Danfoss

Danfoss MBC 5000 User manual

Danfoss PVG 32 User manual

Danfoss

Danfoss PVG 32 User manual

Danfoss KP 34 User manual

Danfoss

Danfoss KP 34 User manual

Danfoss RT 6AEW User manual

Danfoss

Danfoss RT 6AEW User manual

Danfoss KP 1 User manual

Danfoss

Danfoss KP 1 User manual

Danfoss CWH1000 Manual

Danfoss

Danfoss CWH1000 Manual

Danfoss MP 55 User manual

Danfoss

Danfoss MP 55 User manual

Danfoss RT 260A User manual

Danfoss

Danfoss RT 260A User manual

Danfoss KP 1 User manual

Danfoss

Danfoss KP 1 User manual

Danfoss BCP1H User manual

Danfoss

Danfoss BCP1H User manual

Danfoss KP 15 User manual

Danfoss

Danfoss KP 15 User manual

Danfoss KP 44 User manual

Danfoss

Danfoss KP 44 User manual

Danfoss KP 15 User manual

Danfoss

Danfoss KP 15 User manual

Danfoss KPS 35 User manual

Danfoss

Danfoss KPS 35 User manual

Danfoss RT 260A User manual

Danfoss

Danfoss RT 260A User manual

Danfoss KP 1 User manual

Danfoss

Danfoss KP 1 User manual

Danfoss KPU 1 User manual

Danfoss

Danfoss KPU 1 User manual

Danfoss AKS 38 User manual

Danfoss

Danfoss AKS 38 User manual

Danfoss RT 112 User manual

Danfoss

Danfoss RT 112 User manual

Danfoss LLS 4000 User manual

Danfoss

Danfoss LLS 4000 User manual

Danfoss TS715 Si Assembly Instructions

Danfoss

Danfoss TS715 Si Assembly Instructions

Danfoss RT 262A User manual

Danfoss

Danfoss RT 262A User manual

Danfoss MP 54 User manual

Danfoss

Danfoss MP 54 User manual

Danfoss LLS 4000 Installation and maintenance instructions

Danfoss

Danfoss LLS 4000 Installation and maintenance instructions

Popular Switch manuals by other brands

SMC Networks SMC6224M Technical specifications

SMC Networks

SMC Networks SMC6224M Technical specifications

Aeotec ZWA003-S operating manual

Aeotec

Aeotec ZWA003-S operating manual

TRENDnet TK-209i Quick installation guide

TRENDnet

TRENDnet TK-209i Quick installation guide

Planet FGSW-2022VHP user manual

Planet

Planet FGSW-2022VHP user manual

Avocent AutoView 2000  AV2000BC AV2000BC Installer/user guide

Avocent

Avocent AutoView 2000 AV2000BC AV2000BC Installer/user guide

Moxa Technologies PT-7728 Series user manual

Moxa Technologies

Moxa Technologies PT-7728 Series user manual

Intos Electronic inLine 35392I operating instructions

Intos Electronic

Intos Electronic inLine 35392I operating instructions

Cisco Catalyst 3560-X-24T Technical specifications

Cisco

Cisco Catalyst 3560-X-24T Technical specifications

Asante IntraCore IC3648 Specifications

Asante

Asante IntraCore IC3648 Specifications

Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Siemens

Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Edge-Core DCS520 quick start guide

Edge-Core

Edge-Core DCS520 quick start guide

RGBLE S00203 user manual

RGBLE

RGBLE S00203 user manual

Thrustmaster FLIGHT SIMULATOR X quick guide

Thrustmaster

Thrustmaster FLIGHT SIMULATOR X quick guide

Southwire SURGE GUARD 41390 RVC troubleshooting guide

Southwire

Southwire SURGE GUARD 41390 RVC troubleshooting guide

Buhler Nivotemp NT 61 Brief instructions

Buhler

Buhler Nivotemp NT 61 Brief instructions

Kramer VS-41HDCP user manual

Kramer

Kramer VS-41HDCP user manual

Techly IDATA AU-270 user manual

Techly

Techly IDATA AU-270 user manual

Belkin F1U109 user manual

Belkin

Belkin F1U109 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

15% Ag
Installation guide
Pressure switch
KP 15, KP 15A, KP 17W, KP 17B, KP 17WB
060R9753
060R9753
© Danfoss | Climate Solutions | 2021.05 AN211686434433en-000701 | 1
Ambient temperatures / Mounting requirements
KP 15, KP 17 KP 15, KP 17 KP 15A
Connections Mounting
t1 min. KP 15: -40 °C (-40 °F)
t1 min. KP 17: -25 °C (-13 °F)
t1max.: 65 °C (149 °F)
Relative humidity RH: 30 – 98%
Vibrations resistance: 4 g (10 – 1000 Hz)
Type
Regulation range
Max. working pressure PS/MWP
KP 15 LP: -0.2 – 7.5 bar
HP: 8 – 32 bar
17 bar/245 psig
35 bar/510 psig
KP 15
LP man.
reset
LP: -0.9 – 7 bar
HP: 8 – 32 bar
17 bar/245 psig
35 bar/510 psig
KP 17 LP: -0.2 – 7.5 bar
HP: 8 – 32 bar
17 bar/245 psig
35 bar/510 psig
Test pressure (Ptest)
Enclosure
max. 3 mm
(⁄in)
C: Enclosure IP44
(EN 60529)
B: Enclosure IP30
(EN 60529)
A: 8 – 32 UNC (M4)
Max. 100 °C
(212 °F)
ptest max.
20 bar (285 psig)
PS/MWP
ptest max.
35 bar (510 psig)
PS/MWP
Refrigerants:
R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D,
R448A, R449A, R450A, R452A, R507A, R513A, R717*)
For complete list of approved refrigerants, go to
http://products.danfoss.com/all-products/
*) only for KP 15A
14 mm
(⁄in)
14 mm
(⁄in)
17 mm
(⁄in)
12 (⁄in)
KP 15, KP 17KP 15A
2.3 bar
(33.5 psi)/rev.
0.7 bar (10 psi)/rev. 0.15 bar (2 psi)/rev.
6 mm
(⁄in)
© Danfoss | Climate Solutions | 2021.05
2 | AN211686434433en-000701
LP, aut. reset LP, man. reset HP
LP = Low Pressure LP = Low Pressure HP = High Pressure
LP side: A-C opens on pressure drop
HP side: A-C opens on pressure rise
Short circuit protection:
Fuse 16 Amp
Manual trip function
Adjustment
Convertible reset
KP 15: LP/HP convertible, KP 17WB: HP convertible
Insert a screwdriver into the slot on the lock disc and
turn it to desired reset conguration.
Do not turn the screw on the lock disc as it may damage
theconvertible reset mechanism.
LP man. LP auto. LP auto. LP man.
HP man HP man HP auto. HP auto.
Note: Do not select automatic reset if safety of the system
requires manual reset.
Note: Selected reset conguration may be protected against
unauthorized actions applying a seal.
TRIP:
use FINGERS ONLY!
(Do NOT use screwdriver)
Reset options
CAUTION:
Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage
to equipment. Do never touch live parts with your ngers or with any tool.
Electrical rating - General When used acc. to UL regulations
LR 112A
AC 1: 16 A
400 V
AC
DC 13
AC 3: 16 A 12 W
AC 15: 10 A 220 V
Listed refrigeration controller
61B5
Contacts
Voltage FL LR Resist.
load
Pilot
duty
AC DC A A
A - B
A - C
240 – 8 48 8 A 3 A
120 –16 96 16 A
–240 – – – 12 W
A - D 240 – – – – 50 VA
Use copper wire only
Tightening torque 20 lb. in
-1 bar (Pe)(30 inHg) -1 bar (Pe)(30 inHg)
Voltage Current range Power factor
(cos phi) Frequency
250V AC ≤ 4.0 A PF ≥ 0,400 50Hz/60Hz
250V AC > 4.0 to 6.0 A PF ≥ 0,594 50Hz/60Hz
250V AC > 6.0 to 16,0 A PF ≥ 0,780 50Hz/60Hz
CAUTION:
Only for selected A2L refrigerants: R455A, R454C, R1234yf, R1234yz, R1234ze
For complete list of approved A2L refrigerants, go to http://products.danfoss.com/all-products/
Safety requirements
1. KP pressure switches shall only be employed in the units/systems which comply with the requirements for charge limits and
requirements for avoiding ignition sources of IEC 60335-2-24, IEC 60335-2-40, IEC 60335-2-89, ISO 5149, EN378-1 or equivalent.
2. Applying the overload on the KPs must be prevented. If by any chance it was damaged, the system / unit shall be stopped and
KP shall be replaced as necessary.
3. Electrostatic discharge protection and Electrical leakage protection shall be surely implemented by grounding or other
measures.
4. Only trained personnel are authorized to handle ammable refrigerants systems and may do the installation, maintenance and
exchange of the switch by using appropriate tools.
5. It is recommended to regularly check the function of KP switch.
6. The KP pressure switches shall be used as built-in devices that cannot be accessible from outside and protected against
mechanical impact.
7. The KPs shall be installed in water free environment. In addition, protection of the KP switches against corrosion shall be taken
into consideration when using them in corrosive environment.
8. Cables shall not be in contact with sharp edges. The cables shall be connected with adequate stress relieve in order to prevent
that pulling forces can be carried thorough the cable to the terminal.
9. In the event of pressure pulsation in the system, where switch is connected, these must be eectively dumped to prevent
failure of the bellows. The cycle frequency of KP switch shall be kept as low as possible.
10. The KP switches shall not be installed in places where high level of vibration is present.
Disclaimer
The user is responsible for ensuring that third parties also comply with this Notice, e.g. in case that the KP switches are supplied to
third parties, and e.g. that all installation guides are available with the KP switches during installation. It is required that all
conditions of this guide are being met and secured when using KP pressure switches.
Danfoss shall not be responsible for any kind of direct and indirect or consequential damage or loss, including, but not limited to,
loss of property, production, loss of prot, human injury arising out of the explosion or re caused by the ammable nature of
refrigerant.
IMPORTANT NOTICE
Electrical rating
AC-3: 16 A / 250 V AC
AC-15: 10 A / 250 V AC
© Danfoss | Climate Solutions | 2021.05
3 | AN211686434433en-000701