Dantherm CC 3000 User manual

CC 3000 controller
SERVICE MANUAL
en Rev. 1.4 • 2019-W48-2


3
Introduction
Table of contents
This service manual covers the following main topics:
Introduction .....................................................................3
Table of contents......................................................................3
About this manual ....................................................................4
Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Declaration of Conformity .............................................................6
Product description ..............................................................7
Overall description ....................................................................7
Electronic control .....................................................................8
System operation strategy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Transport and unwrapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Unwrapping .........................................................................12
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Mounting of the unit .................................................................13
Conguration of output ..............................................................14
Installation options - air conditioner ..................................................15
Conguration of digital input (NO/NC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
External Connections.................................................................17
Starting up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Modes and settings (overview) .......................................................21
Display and menu overview ..........................................................22
Home menu level ....................................................................24
Sub-menu: System setting level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Sub-menu: Alarm cong. level ........................................................31
Access via WEB interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Service ........................................................................ 33
Firmware, datalog & communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Maintenance .........................................................................35
Appendix ...................................................................... 36
Technical Data .......................................................................36
Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Enclosure dimensions ................................................................38
en

4
Introduction: About this manual
About this manual
This document is a technical user manual for the CC 3000 free cooling controller intended for
trained personnel only.
This manual uses the following abbreviations for ventilation terminologies.
Abb. Description
GUI/ UI Graphical User Interface / User Interface
NO/NC Normally opened (NO)
• a contact that does not ow current in its normal state. Switching it on will
close the contact, causing it to allow current ow.
Normally closed (NC)
• a contact that does ow current in its normal state. Switching it on will open
the contact and disconnect the ow.
NOC Network Operation Center
SELV Safety Extra Low Voltage
SNMP Simple Network Management Protocol is an internet standard protocol for col-
lecting and organizing information about devices on IP networks and for modify-
ing that information to change device behaviour.
TCP/IP Transmission Control Protocol/ Internet Protocol
TTL link Hardware interface based on the electrical properties of TTL (Transistor-Transistor
Logic)
Following symbols are used in this manual in order to draw attention to danger risks and ad-
ditional information of high relevance.
Symbols used
Warning
Caution
WARNING
This symbol in connection with the word“Warning”warns of a risk
involving severe injury.
Warning
Caution
CAUTION
This symbol in connection with the word“Caution” warns of a risk of
minor or moderate injury and material damage.
!NOTICE
In connection with this symbol you will nd further tips and information
concerning the use of the device.
Warning and caution symbols are described in the following way:
Type and source of hazard
Further elaboration, if relevant.
• Measures to avert danger or immediate measures if the risk occurs are described in this
way
Copying of this service manual, or part of it, is forbidden without prior written permission
from Dantherm.
Dantherm reserves the right to make changes and improvements to the product and the
service manual at any time without prior notice or obligation.
This unit is designed for long term durability. When total lifetime ends, the unit should be
recycled according to national rules and with high environmental protection considerations.
Target group
Abbreviations in
this manual
Symbols in
this manual
Warning
Caution
WARNING/
CAUTION
Copyright
Reservations
Recycling

5
Introduction: Safety
Safety
It is important to acknowledge the correct operating procedures for the free cooling unit and
all of its safety precautions. Dantherm accepts no liability with regards to loss of business or
personal injury as a consequence of failing to abide by safety procedures.
Read the entire manual before using the controller.
Risk of damaging equipment and human injuries
• Digital inputs must be connected to potential free contacts only (internal 12V pull up)
• Do NOT connect 230VAC or 48VDC
• Comply to SELV (Safety Extra Low Voltage) safe level.
• Alarm outputs are potential free contacts (connect max. 60V DC / 100mA)
• Do NOT connect 230 VAC on alarm output
• Comply to SELV (Safety Extra Low Voltage) safe level.
Safety precautions
Warning
Caution
CAUTION
en

6
Introduction: Declaration of Conformity
Declaration of Conformity
Dantherm hereby, declare that the unit mentioned below:
No.: 091210 Type: CC 3000
- complies with the following directives:
2014/35/EU Low Voltage Directive
2014/30/EU EMC Directive
2011/65/EU RoHS Directive (Restriction of hazardous substances)
- and is manufactured in compliance with the following harmonized standards:
EN 60950-1:2006 Information technology equipment - Safety - Part 1
EN 61000-6-2:2019 Electromagnetic compatibility (EMC). Generic standards. Immunity
standard for industrial environments
EN 61000-6-3:2007 Electromagnetic compatibility (EMC). Generic standards. Emission
standard for residential, commercial and light-industrial environments
Skive, 12.08.2019

7
Product description: Overall description
Product description
Overall description
The CC 3000 is designed as a single board controller, including all connections needed to sup-
port free cooling products with or without additional air conditioner. The CC3000 controller is
enclosed in a special designed plastic casing, with UL rating 94-V0, dedicated for wall mount.
Embedded micro controller is a 32 bit Cortex M3 core.
The CC 3000 controller supports basic temperature and relative humidity control in enclo-
sures - always attempting to minimize energy consumption.
The controller is able to operate following equipment simultaneously:
• two free cooling units
• two motorized exhaust dampers/TC damper
• two AC/DC air conditioners (via 0-24 V DC output)
• one heater (via another 0-24 V DC output)
This illustrates the dierent parts of the CC 3000 controller.
• C1: PCB cover
• C2: Terminal cover
• C3: Main casing
• C4: Wall mount
Front Rear
Fig. 1
Pos. Description Pos. Description
1 Display 5 Main casing xation wholes
2 Control buttons 6 Cover lock
3 Memory (SD) card slot 7 Wall mounting wholes
4 TTL link (J6) 8 Recess for cable outlet
Function
description
Product
illustration
1
2
8
7
5
6
3
4
C2 C3 C4C1
en

8
Product description: Electronic control
Electronic control
The control circuit of the CC 3000 is all made of low voltage connections and is designed ac-
cording to EN/UL 60950.
This illustrates the overall system control architecture:
TCP/IP
Room +
hotspot sensor
A/C1 & A/C2
24V AUX
Alarm 1-10
Heat
2.4” color
display
SD card reader
Keypad
TTL Link
Damper 1
Damper 2
Flexibox 1
Flexibox 2
3X dig
Ic port
Fig. 2
This illustration gives an overview of the electrical connections. All connections are done with
multi connectors using spring loaded terminations.
See detailed connecting-specications in the section “External Connections”on page 17.
Flexibox 1
Flexibox 2
Damper 2
Damper 1
A/C 1
A/C 2
Alarm 1-5
Alarm 6-10
Heater
24V DC Aux.
EthernetDigital 1-3 T.Sensor
I2C Comm.
J.1
J.33 J.13
J.2
J.4 J.40 J.5 J.11 J.38
J.15J.35J.3
J.9
J.17
Fig. 3
Pos. Terminal rail Description
1 J.33 + J.1 Connecting up to two free cooling units
2 J.13 + J.2 Connecting up to two motorized dampers
3 J.4 + J.9 Connecting up to two air conditioner
4 J.40 + J.3 Alarm outputs
5J.5 Digital input (e.g. connecting re/smoke alarm, door switch
etc.)
6 J.11 + J.35 Connecting a temp. sensor and humidity sensor
7 J.38 + J.15 Connecting a heater and equipment using 24 V DC
8 J.17 Connecting ethernet/ LAN
Introduction
Block schematic
External
Connections
(overview)

9
Product description: System operation strategy
System operation strategy
This section describes the operation strategy according to the possible operation modes: Free
cooling mode, Standard mode, Energy save mode and Air Con mode.
The basic operation strategy of the CC 3000 can be described in the following way:
• Connected heater (optional) starts, when temperature is too low (on/o set points for
heater can be adjusted).
• Free cooling unit(s) start(s) up slowly, when temperature rises above Min °C set point and
fan will increase speed gradually (according to P-band) until Max °C set point is reached.
• P-band starts at Min °C set point and stops at Max °C set point.
• Most setups will only need a P-band, which continues from Min °C to Max °C without
interruption. The set point for Mid1and Mid2will in this case be exactly the same.
• The P-band can be separated into two parts, interrupted by Mid1and Mid2as illustrated
in Fig. 4.
• Air Conditioner(s) is/are activated, when the set point for A/C on is reached and stops
again, when temperature drops below set point for A/C o.
• Emergency operation is a special boost operation, where all connected cooling units
(both free cooling and A/C) starts up at the same time, until temperature drops below
emergency o.
Fig. 4
This table describes the diferent settings, which can be adjusted with the CC 3000 controller.
Abbr. Description
OFF Temperature when fan stops
ON Temperature when fan starts
Heat Temperature where heater will be active (optional)
Set point Desired indoor temperature
• fan speed will be adjusted between min °C and max °C
Min °C Temperature at bottom of P-band
Mid1Top of P-band 1
Mid2Bottom of P-band 2
Max °C Temperature at top of P-band
P-band (1 & 2) Regulating fan speed proportionally according to indoor temperature
A/C 1 on External Air con unit 1 starts up if connected
A/C 1 o External Air con unit 1 stops if connected
A/C 2 on External Air con unit 2 starts up if connected
A/C 2 o External Air con unit 2 stops if connected
Emergency on Fan runs 100% (Free cooling and Air conditioner active, if installed)
Emergency o Fan returns to nominal speed
Default values for the above set points can be found in the manual for the free cooling unit.
Introduction
Generic example
en

10
Product description: System operation strategy
Use of free cooling unit(s) only. Free cooling unit will increase/ decrease fan speed gradually
between Min °C and Max °C.
Fig. 5
Free cooling unit starts when outdoor temperature is min. 3 °C colder than set point. If out-
door temperature is closer to or above set point and cooling is needed, A/C unit will operate
on its own.
Fig. 6
Free cooling mode
(default)
Standard mode

11
Product description: System operation strategy
Free cooling unit starts when outdoor temperature is min. 1 °C colder than indoor tempera-
ture. If outdoor temperature is closer to or above set point and cooling is needed, A/C unit
will operate on its own.
Fig. 7
The free cooling unit is not active. Only the connected Air conditioner is operating.
A/C Status
Fig. 8
Energy save mode
Air Con mode
en

12
Transport and unwrapping: Unwrapping
Transport and unwrapping
Unwrapping
Step Action
1 Report any obvious damage to the carrier, parcel service, postal service etc. immedi-
ately on delivery and note down the damage on the shipping document or carrier’s
document.
2 Check the content of the box.
3 Should any transport damage be detected after unpacking of the device, or should
the delivery be incomplete, contact your salesman in charge or specialised dealer
without delay.
The scope of delivery includes:
Amount Description Illustration
1 CC 3000 controller
1 bag incl.:
4 rawlplug (8x 40)
4 screws for brick wall
(pan head, pozidriv, A2 - ø4,8 x 38)
4 screws for metal wall
(self drilling sheet metal screw, pan head, pozidriv, ø4,8 x 32)
2 screws for mounting main casing to wall mount
(pan head, torx plus ø4,0 x 12)
Check for
transport damages
Content of the box

13
Installation: Mounting of the unit
Installation
Mounting of the unit
Step Action Illustration
1 Remove wall mount from the
main casing.
4x
2 Fix the wall mount to the wall.
3 Press cover lock on both sides in
order to release terminal cover.
4 Break away some blocks from
the wall mount in order to inte-
grate cable trays.
5 Lead the cables from the exter-
nal desired equipment through
the wall mount and into the
main casing.
6 Click the main casing on the wall
mount.
7 Fix the main casing to the wall
mount with the two screws,
which are part of delivery.
8 Connect the external equipment to the terminal rail. See section “External Connec-
tions”on page 17 for further connecting details.
• Check page 14 if you need to change the conguration of output (NO/NC).
Installation &
wall mounting
en

14
Installation: Conguration of output
Conguration of output
Access PCB in order to change conguration output:
1. Press cover lock on both sides in order to
release the terminal cover.
2. Pull out terminal cover
3. Press cover lock on both sides and at the top
in order to release the PCB cover.
4. Pull out PCB cover.
1
23
3
4
This illustrates the default jumper positions on the PCB and the possible congurations.
12 3 4 5
6 7 8
Fig. 9
Jumper 1-5: Cong. 1
• Moving the jumpers make it possible to change the conguration of the corresponding
outputs from normally opened (NO) to normally closed (NC).
Jumper 6-8: Cong. 2
• Removing the jumpers changes the conguration of the corresponding outputs from 24V
DC to dry contact. (For connection examples see“Installation options - air conditioner”on
page 15)
Contacts Jumper Cong. 1 Jumper Cong. 2
Alarm 1 1 Congurable as:
• NO (default)
• NC
-Dry contacts (xed)
Alarm 2 2
A/C 1
(air conditioner 1)
3 6 Congurable as:
• 24 V DC (default)
• Dry contact
A/C 2
(air conditioner 2)
4 7
Heater 5 8
Accessing PCB
Conguration
options

15
Installation: Installation options - air conditioner
Installation options - air conditioner
Option 1
Option 2
Change jumper 6-8 (see“Conguration of output”on page 14) from 24V DC (default) to dry
contact, when connecting AC as illustrated in option 3 and 4.
Option 3
CC 3000 must be set in
energy save mode or
standard mode when A/C
is connected.
DC 3500 Split Air condi-
tioner must be congured
for COD when connected
to CC 3000.
Option 4
CC3000 AC1 or AC2
Dry contact output
Cong. 2:
24V DC (Default)
Cong. 2:
Dry contact
(altered)
en

16
Installation: Conguration of digital input (NO/NC)
Conguration of digital input (NO/NC)
In case the digital inputs are used together with external transducers like a re/ smoke alarm,
it may be necessary to change the input from normally opened (NO) to normally closed (NC).
The only way to do this is via the conguration le. Follow these steps:
Pos. Action Illustration
1 Put SD card into your PC SD card reader.
2 Open the .txt le with the le name that match your product.
• The .txt le can be opened with wordpad
3 Go to system control conguration section and change line 57/58/59 to match your
requirement:
• 57.Dig.1 NO/NC Type [0/1]: 0
• 58.Dig.2 NO/NC Type [0/1]: 0
• 59.Dig.3 NO/NC Type [0/1]: 0
Note: (NO=0 NC=1)
4 When required change is done, save and close the le.
5 Insert the SD card into the controller.
6 Go to“Product conguration”. (see
“Fig. 13”on page 23 for menu
overview) and select the le name
on the list. Press Enter.
New settings will now be uploaded.
Change from
NO to NC

17
Installation: External Connections
External Connections
Access connection terminals:
1. Press cover lock on both sides in order to
release the terminal cover.
2. Pull out terminal cover.
1
2
This illustration shows the terminals to be used for connecting the free cooling unit(s),
damper(s), air conditioner and alarm.
Flexibox 1
Flexibox 2
Damper 2
Damper 1
A/C 1
A/C 2
Alarm 1-5
Alarm 6-10
Heater
24V DC Aux.
EthernetDigital 1-3 T.Sensor
I2C Comm.
J.33 J.13 J.4 J.40
J.2 J.9 J.3
J.1
123
123 123
12312345678 12345678910
12345678910
12345678
Fig. 10
This illustration shows the terminals to be used for connecting accessory to the digital input,
temperature sensor/I2C comm. (humidity sensor), 24 V DC AUX/heater and ethernet.
Flexibox 1
Flexibox 2
Damper 2
Damper 1
A/C 1
A/C 2
Alarm 1-5
Alarm 6-10
Heater
24V DC Aux.
EthernetDigital 1-3 T.Sensor
I2C Comm.
J.5 J.11 J.38
J.15
J.35
J.17
123
123
1234
1234
123456
Fig. 11
Accessing
terminals
Flexibox 1
Flexibox 2
Damper 2
Damper 1
A/C 1
A/C 2
Alarm 1-5
Alarm 6-10
Heater
24V DC Aux.
EthernetDigital 1-3 T. Sensor
I2CComm.
Illustration
Detail 1
Illustration
Detail 2
en

18
Installation: External Connections
The terminal rails J.33 and J.1 are to be used for connecting up to two free cooling units.
• Terminal type: Anytek KE161151A000G (Mating type Anytek KD161050A000G).
Pin J.33
Flexibox 1
J.1
Flexibox 2
Cable type
1 +48 V supply
(40-60 V DC from free cooling unit)
0,5 mm2
2 PWM
3 Tacho
4 GND
5 Filter
6 GND
7 Outdoor temp. sensor
8 GND
The terminal rails J.13 and J.2 are to be used for connecting up to two motorized dampers.
• Terminal type: Anytek KE061151A000G (Mating type Anytek KD061050A000G).
Pin J.13
Damper 2
J.2
Damper 1
Cable type
1 Closed signal 0,5 mm2
2 Open signal
3 Common (fused)
The terminal rails J.9 and J.4 are to be used for connecting up to two air conditioner.
• Terminal type: Anytek KE061151A000G (Mating type Anytek KD061050A000G).
Pin J.9
A/C 1
J.4
A/C 2
Cable type
1 24 V AC - 100 mA.
Output can be congured as dry contact or 0/24 V DC output.
For 0/24 V DC output, a jumper on PCB must be set (see page 14).
0,5 mm2
20/24 V DC
3 GND
The terminal rails J.40 and J.3 contain 10 dry contacts for the alarm output, fully congurable.
• Terminal type: Anytek KE201151A000G (Mating type Anytek KD201050A000G).
Pin J.40
Alarm 1-5
J.3
Alarm 6-10
Cable
type
1 Alarm 1
• mechanical relay with NO/NC contact
Alarm 6
• solid state type: NO contact
0,5 mm2
2
3 Alarm 2
• mechanical relay with NO/NC contact
Alarm 7
• solid state type: NO contact
4
5 Alarm 3
• solid state type: NO contact
Alarm 8
• solid state type: NO contact
6
7 Alarm 4
• solid state type: NO contact
Alarm 9
• solid state type: NO contact
8
9 Alarm 5
• solid state type: NO contact
Alarm 10
• solid state type: NO contact
10
Free cooling units
(Fig. 10)
Motorized
dampers
(Fig. 10)
Air Conditioner
(Fig. 10)
Alarm
(Fig. 10)

19
Installation: External Connections
The terminal rail J.5 is to be used for connecting other accessory as e.g. a re/smoke alarm or
door switch.
• Terminal type: FCI 20020110-C061A01LF (Mating type Anytek KD0610500000G).
Pin J.5
Digital 1-3
Cable type
1 DIG 1 (1K pull up to 12 V DC) 0,5 mm2
2 GND
3 DIG 2 (1K pull up to 12 V DC)
4 GND
5 DIG 1 (1K pull up to 12 V DC)
6 GND
The terminal rail J.11 is to be used for connecting one or two temperature sensors.
The terminal rail J.35 is to be used for connecting a humidity sensor.
• Terminal type: Anytek KE081151A000G (Mating type Anytek KD081050A000G).
Pin J.11
T. sensor
J.35
I2C Comm. (humidity sensor)
Cable type
1 Room temp. sensor (NTC type) +3,3 V DC 0,5 mm2
2 GND SCL
3 Hotspot temperature sensor (NTC type) SDA
4 GND GND
The terminal rail J.38 is to be used for connecting a heater.
The terminal rail J.15 is to be used for connecting other equipment using 24 V DC.
• Terminal type: Anytek KE061151A000G (Mating type Anytek KD061050A000G).
Pin J.38
Heater
J.15
24 V DC
Cable type
1Heat/ +24 V
Output can be congured as dry contact or 0/24 V DC
output, set jumper on PCB (see page 14).
24 V DC 100mA 0,5 mm2
2 Heat - 0/24 V DC NC
3 GND GND
J17 is a RJ45 LAN connector CAT5/CAT6 . PulseJack J00011D21BNL
Digital input
(Fig. 11)
Temp. sensor/
I2C Comm.
(humidity sensor)
(Fig. 11)
Heater/
24 V DC AUX
(Fig. 11)
Ethernet
(Fig. 11)
en

20
Installation: Starting up
Starting up
Step Action Illustration
1 Insert SD card into memory card
slot.
2 Switch power on.
Note: The CC 3000 controller
is powered via the free cooling
unit.
3 The CC 3000 controller will now
start up with a short delay and
automatically install newest
rmware and run a GFX update.
Wait while the rmware is
installed. Do NOT switch o the
power or remove the SD card
during this process.
4 When the installation process is nished, the display will automatically open the
product conguration menu.
Choose and conrm your product. The controller will now read the corresponding
conguration.
5 Default language pack is English. You can choose another language in the language
setting menu. (Follow procedure in section “Language settings”on page 29)
6 Save your customized conguration to the SD card, if you want a backup or want to
copy it to other controllers.
• Go to menu item“Other settings”on page 30(see “Fig. 13”on page 23 for
menu overview) →setting option: “Backup”.
• The controller will now save a backup on the SD card.
(Backup le is named cc_cfg.txt, but can be renamed with max 8 characters)
7Data log needed:
Leave SD card in the slot, if an operational data log is required. (See also section “Firm-
ware, datalog & communication” on page 33)
NO data log needed:
Remove SD card from the slot, if no data log is required. Settings are now stored in
onboard nonvolatile memory.
Step Action
1 Start a self test (automatic or manual) in order to see if the system is set up and con-
nected correctly. See how to run self test on page 26.
2 Go to HOME display and check that indoor/ outdoor temperature reading and set
point is correct.
• In case shelter temperature is below set point, indoor temperature sensor can
be heated by hand, to check that fan starts when temperature reach set point
• Be aware that if sensor temperature reach air conditioner set point and air
conditioner is started, it has a minimum runtime of 3 minutes.
Install product
specic
conguration
!
Installation check
Other manuals for CC 3000
1
Table of contents
Other Dantherm Controllers manuals